Solar Cable Voltage Drop Calculator
Work out voltage drop on a DC string or single-phase AC run from the entered length, current, conductor size, voltage and material.
Inputs
View resultLive result
Edit inputsVoltage drop
0.88V
Drop percentage
0.22%
Compare this result with the criteria applicable to the actual circuit and installation. Wattbench does not infer a permitted limit from these inputs.
Save or file this result
- Works out voltage drop on a DC string or single-phase AC run.
- Uses run length, current, conductor size, voltage and material as inputs.
- Returns the drop in volts and as a percentage without inferring the applicable design limit.
How it works
For a two-wire DC string or single-phase AC run, voltage drop is:
V drop = (2 × length × current × ρ) ÷ area, where the factor of 2 covers the active and return conductors, and ρ is conductor resistivity (~0.0175 Ω·mm²/m for copper, ~0.0282 for aluminium, near 20 °C).- Drop % =
V drop ÷ system voltage × 100.
Real designs use the applicable temperature, installation method, conductor data and circuit criteria. Three-phase circuits also use a different factor. This tool reports the arithmetic result without inventing a pass limit; it is a first check, not a substitute for a licensed electrician's cable sizing.
Estimates only: for guidance, not a quote or a compliance certificate. Verify against the current AS/NZS standards and a licensed design. The maths runs in your browser. Nothing is sent to Wattbench unless you sign in and deliberately save the result.
Source ledger2 sources
- Standards bodyAS/NZS 3008.1.1:2017 — Standards Australia catalogue
- Standards bodyAS/NZS 5033:2021 — Standards Australia catalogue
Best next action
Did this help you move the job forward?
Frequently asked
- Is this calculator free to use?
- Yes. The voltage drop calculator is free and needs no sign-up. It runs entirely in your browser.
- Is my data stored or sent anywhere?
- The calculation runs in your browser. Nothing is sent to Wattbench unless you sign in and deliberately select Save result.
- Does it support both DC and AC runs?
- It works out two-wire DC or single-phase AC voltage drop from the values entered. It does not infer a permitted limit or replace a complete cable design.
More tools
Engineering Tool
Cable Sizing Calculator
Find the minimum conductor size that keeps a DC string or AC run under its voltage-drop limit, then round up to the next standard cable size, with the resulting drop shown.
Test Worksheet
Continuity and Loop Impedance Expectation
When an inverter or battery AC circuit, or an array bonding reading, looks high: the R1+R2, R2 and Zs the conductors you enter give by arithmetic, beside your measured value, with the difference and the causes to check.
Identification Tool
Single or Three-Phase Supply Check
Use visible main-switch or meter clues to identify a likely single- or three-phase supply without opening the switchboard.