SolarEdge Inverter Error Codes
Every table in SolarEdge's official Error Codes and Troubleshooting guide — residential, commercial three-phase, Synergy, TerraMax and warnings — with owner-safe and installer guidance where the guide documents one.
361 of 361 codes
About this fault librarySources · scope
A reference compiled by Wattbench from SolarEdge's official Error Codes and Troubleshooting user guide (Version 1.1, January 2026). SolarEdge error codes are hexadecimal characters split by an x — for example 03x85 — shown on the inverter display where fitted and in the SolarEdge platform. This library covers all six tables in that guide: the communication list, the residential single- and three-phase list, the commercial three-phase list, the Synergy-technology list, the TerraMax utility list, and the warning-messages list. The guide reuses code numbers across tables for different faults — 8x1E and 8x22 each appear in both the commercial and TerraMax tables with different meanings and different instructions — so entries outside the residential list carry their section in the code, and both variants are published separately. Where the guide lists one code twice with genuinely conflicting instructions, the entry says so and carries both. A few rows contain errors in the guide's own layout, printing an instruction in the description column or splitting one procedure across both; those entries describe the defect rather than reproducing it as though it were the fault's meaning. The Synergy table is different in kind: it publishes only a code and an event-text constant, with no description or troubleshooting for any row, and the guide's own instruction for that whole table is to contact SolarEdge Support. Those 100 entries are therefore searchable but deliberately carry no remedy. Installer guidance throughout quotes the guide's own step for that exact row. Three TerraMax rows (33x47, 33x85, 33x86) are printed in the guide with an uppercase X separator; they are published here with the lowercase x the guide's own overview specifies, since search matches either. The guide does not establish the installed Australian variant or firmware. Safety note: owners should record the code and stop at safe visual observations. AC/DC isolation, electrical measurements, wiring, settings changes and opening equipment are licensed-worker tasks; ground-fault and arc codes in particular are shock hazards the guide itself gates behind qualified technicians.
- 361 SolarEdge (residential, commercial three-phase, Synergy and TerraMax inverters) fault and alarm codes, documented for the trade.
- Compiled from published documentation and field references; Wattbench is independent and not affiliated with SolarEdge (residential, commercial three-phase, Synergy and TerraMax inverters).
- Codes involving DC/AC isolation, wiring or opening the unit are licensed electrical work. Isolate safely and follow AS/NZS procedure.
Resolution text is manufacturer/service context, not permission for an owner to perform electrical work. Stop at visible observations unless the exact product instructions identify an owner control. Isolation, configuration, testing, opening equipment and wiring are for an appropriately licensed worker and, where required, an SAA-accredited person. Where a card says Product fit is unknown, treat it as brand-level guidance and confirm the exact model, role, regional variant, firmware and current manual before acting.
- 3xB · Communication
No Country Selected
Communication error codes list: No Country Selected.
Product fit · Unknown
Show field stepsHide field steps for 3xB · Communication: No Country Selected
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Select the country. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 3x2 · Communication
Software Error
Communication error codes list: Software Error.
Product fit · Unknown
Show field stepsHide field steps for 3x2 · Communication: Software Error
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact Support. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 3xA · Communication
Phase is unbalanced
Communication error codes list: Phase is unbalanced.
Product fit · Unknown
Show field stepsHide field steps for 3xA · Communication: Phase is unbalanced
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Select Power Control -> Phase Balance -> Disable. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 3x11 · Communication
Arc detection status interrupt
Communication error codes list: Arc detection status interrupt.
Product fit · Unknown
Show field stepsHide field steps for 3x11 · Communication: Arc detection status interrupt
Product fit · Unknown
Safe checks now
Treat this as an electrical-safety event. Record the code and conditions, keep clear of the inverter and its wiring, and do not reset the unit or operate isolators; contact your installer promptly.
Installer remedy
The guide's documented step for this code: Refer to Inverter Arc Detection and Interruption. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 3x6A · Communication
The device is locked, due to either human intervention, or automatically due to one or more…
Communication error codes list: The device is locked, due to either human intervention, or automatically due to one or more safety features.
Product fit · Unknown
Show field stepsHide field steps for 3x6A · Communication: The device is locked, due to either human intervention, or automatically due to one or more…
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Need to know why the system locked in the first place. · OFF/ON to Reconnect · Contact support.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 3x92 · Communication
The device is locked, due to either human intervention, or automatically due to one or more…
Communication error codes list: The device is locked, due to either human intervention, or automatically due to one or more safety features.
Product fit · Unknown
Show field stepsHide field steps for 3x92 · Communication: The device is locked, due to either human intervention, or automatically due to one or more…
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Need to know why the system locked in the first place. · OFF/ON to Reconnect · Contact support.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 3x93 · Communication
The device is locked, due to either human intervention, or automatically due to one or more…
Communication error codes list: The device is locked, due to either human intervention, or automatically due to one or more safety features.
Product fit · Unknown
Show field stepsHide field steps for 3x93 · Communication: The device is locked, due to either human intervention, or automatically due to one or more…
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Need to know why the system locked in the first place. · OFF/ON to Reconnect · contact support.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 3x94 · Communication
The device is locked, due to either human intervention, or automatically due to one or more…
Communication error codes list: The device is locked, due to either human intervention, or automatically due to one or more safety features.
Product fit · Unknown
Show field stepsHide field steps for 3x94 · Communication: The device is locked, due to either human intervention, or automatically due to one or more…
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Need to know why the system locked in the first place. · OFF/ON to Reconnect · Contact support.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 3x95 · Communication
The device is locked, due to either human intervention, or automatically due to one or more…
Communication error codes list: The device is locked, due to either human intervention, or automatically due to one or more safety features.
Product fit · Unknown
Show field stepsHide field steps for 3x95 · Communication: The device is locked, due to either human intervention, or automatically due to one or more…
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Need to know why the system locked in the first place. · OFF/ON to Reconnect · contact support.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 3x96 · Communication
The device is locked, due to either human intervention, or automatically due to one or more…
Communication error codes list: The device is locked, due to either human intervention, or automatically due to one or more safety features.
Product fit · Unknown
Show field stepsHide field steps for 3x96 · Communication: The device is locked, due to either human intervention, or automatically due to one or more…
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Need to know why the system locked in the first place. · OFF/ON to Reconnect · Contact support.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 3x97 · Communication
The device is locked, due to either human intervention, or automatically due to one or more…
Communication error codes list: The device is locked, due to either human intervention, or automatically due to one or more safety features.
Product fit · Unknown
Show field stepsHide field steps for 3x97 · Communication: The device is locked, due to either human intervention, or automatically due to one or more…
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Need to know why the system locked in the first place. · OFF/ON to Reconnect · Contact support.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 3x98 · Communication
The device is locked, due to either human intervention, or automatically due to one or more…
Communication error codes list: The device is locked, due to either human intervention, or automatically due to one or more safety features.
Product fit · Unknown
Show field stepsHide field steps for 3x98 · Communication: The device is locked, due to either human intervention, or automatically due to one or more…
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Need to know why the system locked in the first place. · OFF/ON to Reconnect · Contact support.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 3x99 · Communication
The device is locked, due to either human intervention, or automatically due to one or more…
Communication error codes list: The device is locked, due to either human intervention, or automatically due to one or more safety features.
Product fit · Unknown
Show field stepsHide field steps for 3x99 · Communication: The device is locked, due to either human intervention, or automatically due to one or more…
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Need to know why the system locked in the first place. · OFF/ON to Reconnect · Contact support.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 3x9A · Communication
The device is locked, due to either human intervention, or automatically due to one or more…
Communication error codes list: The device is locked, due to either human intervention, or automatically due to one or more safety features.
Product fit · Unknown
Show field stepsHide field steps for 3x9A · Communication: The device is locked, due to either human intervention, or automatically due to one or more…
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Need to know why the system locked in the first place. · OFF/ON to Reconnect · Contact support.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 3x9B · Communication
The device is locked, due to either human intervention, or automatically due to one or more…
Communication error codes list: The device is locked, due to either human intervention, or automatically due to one or more safety features.
Product fit · Unknown
Show field stepsHide field steps for 3x9B · Communication: The device is locked, due to either human intervention, or automatically due to one or more…
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Need to know why the system locked in the first place. · OFF/ON to Reconnect · Contact support.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 3x9C · Communication
The device is locked, due to either human intervention, or automatically due to one or more…
Communication error codes list: The device is locked, due to either human intervention, or automatically due to one or more safety features.
Product fit · Unknown
Show field stepsHide field steps for 3x9C · Communication: The device is locked, due to either human intervention, or automatically due to one or more…
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Need to know why the system locked in the first place. · OFF/ON to Reconnect · Contact support.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 3x9D · Communication
The device is locked, due to either human intervention, or automatically due to one or more…
Communication error codes list: The device is locked, due to either human intervention, or automatically due to one or more safety features.
Product fit · Unknown
Show field stepsHide field steps for 3x9D · Communication: The device is locked, due to either human intervention, or automatically due to one or more…
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Need to know why the system locked in the first place. · OFF/ON to Reconnect · Contact support.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 3x9E · Communication
The device is locked, due to either human intervention, or automatically due to one or more…
Communication error codes list: The device is locked, due to either human intervention, or automatically due to one or more safety features.
Product fit · Unknown
Show field stepsHide field steps for 3x9E · Communication: The device is locked, due to either human intervention, or automatically due to one or more…
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Need to know why the system locked in the first place. · OFF/ON to Reconnect · Contact support.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 3xA7 · Communication
Country mismatch
Communication error codes list: Country mismatch.
Product fit · Unknown
Show field stepsHide field steps for 3xA7 · Communication: Country mismatch
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Select the country. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 3x100 · Communication
The device is locked, due to either human intervention, or automatically due to one or more…
Communication error codes list: The device is locked, due to either human intervention, or automatically due to one or more safety features.
Product fit · Unknown
Show field stepsHide field steps for 3x100 · Communication: The device is locked, due to either human intervention, or automatically due to one or more…
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Need to know why the system locked in the first place. · OFF/ON to Reconnect · Contact support.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 3x10E · Communication
The device is locked, due to either human intervention, or automatically due to one or more…
Communication error codes list: The device is locked, due to either human intervention, or automatically due to one or more safety features.
Product fit · Unknown
Show field stepsHide field steps for 3x10E · Communication: The device is locked, due to either human intervention, or automatically due to one or more…
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Need to know why the system locked in the first place. · OFF/ON to Reconnect · Contact support.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 3x114 · Communication
The device is locked, due to either human intervention, or automatically due to one or more…
Communication error codes list: The device is locked, due to either human intervention, or automatically due to one or more safety features.
Product fit · Unknown
Show field stepsHide field steps for 3x114 · Communication: The device is locked, due to either human intervention, or automatically due to one or more…
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Need to know why the system locked in the first place. · OFF/ON to Reconnect · Contact support.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 3x125 · Communication
The device is locked, due to either human intervention, or automatically due to one or more…
Communication error codes list: The device is locked, due to either human intervention, or automatically due to one or more safety features.
Product fit · Unknown
Show field stepsHide field steps for 3x125 · Communication: The device is locked, due to either human intervention, or automatically due to one or more…
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact SolarEdge support. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 3x136 · Communication
RS485 / follower-detect condition (guide column error)
The guide's row for this code carries an instruction in its description cell — "Verify the RS 485 connections between the Inverters. Perform Follower detect in Go." — rather than a description of the fault, and its troubleshooting cell repeats the generic device-locked steps used by the surrounding 3x92–3x138 rows. The guide prints no description of what this code means.
Product fit · Unknown
Show field stepsHide field steps for 3x136 · Communication: RS485 / follower-detect condition (guide column error)
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Need to know why the system locked in the first place. · OFF/ON to Reconnect · Contact support.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 3x138 · Communication
The device is locked, due to either human intervention, or automatically due to one or more…
Communication error codes list: The device is locked, due to either human intervention, or automatically due to one or more safety features.
Product fit · Unknown
Show field stepsHide field steps for 3x138 · Communication: The device is locked, due to either human intervention, or automatically due to one or more…
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Need to know why the system locked in the first place. · OFF/ON to Reconnect · Contact support.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 2x2
Night Mode is an inverter status indicating that the input voltage is below 6V DC
Night Mode is an inverter status indicating that the input voltage is below 6V DC.
Product fit · Unknown
Show field stepsHide field steps for 2x2: Night Mode is an inverter status indicating that the input voltage is below 6V DC
Product fit · Unknown
Safe checks now
This is a status rather than a fault: the inverter reports its DC input below the operating threshold, which is normal outside daylight. Record it and contact your installer only if it shows when the array should be producing.
Installer remedy
The guide's documented step for this code: Test the DC side and contact support for further guidance. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 2x9
Ground current surge
Ground current surge.
Product fit · Unknown
Show field stepsHide field steps for 2x9: Ground current surge
Product fit · Unknown
Safe checks now
Treat this as an electrical-safety event. Record the code and conditions, keep clear of the inverter and its wiring, and do not reset the unit or operate isolators; contact your installer promptly.
Installer remedy
The guide's documented step for this code: · Check the AC connection to the inverter · Check with the grid operator if a large surge source or irregular load exists near the site. · If the grid does not have problems contact SolarEdge support.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 2xA
Ground faults may occur due to insufficient insulation to the ground
Ground faults may occur due to insufficient insulation to the ground.
Product fit · Unknown
Show field stepsHide field steps for 2xA: Ground faults may occur due to insufficient insulation to the ground
Product fit · Unknown
Safe checks now
Treat this as an electrical-safety event. Record the code and conditions, keep clear of the inverter and its wiring, and do not reset the unit or operate isolators; contact your installer promptly.
Installer remedy
The guide's documented step for this code: WARNING! ELECTRICAL SHOCK HAZARD. Do not touch uninsulated wires when the inverter cover is removed. RISQUE D’ÉLECTROCUTION, ne touchez pas les fils non isolés lorsque le couvercle de l'onduleur est retiré. Only a qualified technician should handle this problem, and only after taking proper precautions. 1. Turn the inverter ON/OFF switch to OFF. 2. Wait five minutes for the input capacitors to discharge. 3. Disconnect the AC breaker. 4. Disconnect the DC inputs. 5. Connect each DC string separately, turn the AC and the inverter ON/OFF switch to ON, until the error appears for the faulty string. · Do not connect strings with a grounding fault to the inverter. A certified installer must fix the faulty string before connecting it to the inverter · For further documentation, contact SolarEdge Support.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 2xD
Ground current surge
Ground current surge.
Product fit · Unknown
Show field stepsHide field steps for 2xD: Ground current surge
Product fit · Unknown
Safe checks now
Treat this as an electrical-safety event. Record the code and conditions, keep clear of the inverter and its wiring, and do not reset the unit or operate isolators; contact your installer promptly.
Installer remedy
The guide's documented step for this code: · Check the AC connection to the inverter · Check with the grid operator if a large surge source or irregular load exists near the site. · If the grid does not have problems contact SolarEdge support.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 2xE
AC voltage surge
AC voltage surge.
Product fit · Unknown
Show field stepsHide field steps for 2xE: AC voltage surge
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: If the fault persists: · Check the AC connection to inverter. · Verify that the inverter is set to the correct country. · Check with the grid operator if a large surge source or irregular load exists near the site. · Verify that the output wire size matches the distance between the inverter and the location of the grid connection. · Use a larger gauge wire for the AC output. · Refer to the AC Wiring Application Note at http://www.solaredge.us/files/pdfs/application-note-recommended-wiring.pdf.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 2xF
The SolarEdge system normally eliminates DC overvoltage errors
The SolarEdge system normally eliminates DC overvoltage errors.
Product fit · Unknown
Show field stepsHide field steps for 2xF: The SolarEdge system normally eliminates DC overvoltage errors
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · If the fault persists: · Turn OFF the inverter ON/OFF switch. If after five minutes, the LCD panel does not show a low safety voltage (1V per optimizer), check which string is malfunctioning and recheck its connections to the inverter. · Proceed according to Power Optimizer Troubleshooting · Re-commission all inverters in the site, as described in Commissioning the Installation.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 2x10
Vref1V or Vref2V > +/-3%
Vref1V or Vref2V > +/-3%.
Product fit · Unknown
Show field stepsHide field steps for 2x10: Vref1V or Vref2V > +/-3%
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact Support RMA. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 2x11
Over temperature
Over temperature.
Product fit · Unknown
Show field stepsHide field steps for 2x11: Over temperature
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify proper inverter clearances. · Make sure the heat-sink fins are clean and unobstructed.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 2x13
SW error
SW error.
Product fit · Unknown
Show field stepsHide field steps for 2x13: SW error
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact SolarEdge Support. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 2x18
Broken or unconnected temperature sensor
Broken or unconnected temperature sensor.
Product fit · Unknown
Show field stepsHide field steps for 2x18: Broken or unconnected temperature sensor
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact SolarEdge Support. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 2x19
PV solar array is not properly isolated from ground earth
PV solar array is not properly isolated from ground earth.
Product fit · Unknown
Show field stepsHide field steps for 2x19: PV solar array is not properly isolated from ground earth
Product fit · Unknown
Safe checks now
Treat this as an electrical-safety event. Record the code and conditions, keep clear of the inverter and its wiring, and do not reset the unit or operate isolators; contact your installer promptly.
Installer remedy
The guide's documented step for this code: · Check the PV installation for isolation problems and ground leakage. · Only a certified PV installer must fix the faulty string before connecting it to the inverter. · Refer to www.solaredge.us/files/pdfs/application_note_isolation_fault_troubleshooting.pdf.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 2x1A
2x1A
the guide prints no description for this code — its row carries only the instruction to contact SolarEdge Support, in the description column.
Product fit · Unknown
Show field stepsHide field steps for 2x1A: 2x1A
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code is to contact SolarEdge Support. It gives no field procedure, so preserve the event evidence and escalate rather than improvising one.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 2x1C
2x1C
the guide prints no description for this code — its row carries only the instruction to contact SolarEdge Support, in the description column.
Product fit · Unknown
Show field stepsHide field steps for 2x1C: 2x1C
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code is to contact SolarEdge Support. It gives no field procedure, so preserve the event evidence and escalate rather than improvising one.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 2x1D
Line to Neutral voltage is above threshold
Line to Neutral voltage is above threshold.
Product fit · Unknown
Show field stepsHide field steps for 2x1D: Line to Neutral voltage is above threshold
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Check the grid connection. · Check the GND connection. · Check the L1, L2 and Neutral connections. · Verify symmetric load between L1, and L2 · Consult the local grid authority.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 2x1E
Line to Neutral voltage is below threshold
Line to Neutral voltage is below threshold.
Product fit · Unknown
Show field stepsHide field steps for 2x1E: Line to Neutral voltage is below threshold
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Check the grid connection. · Check the GND connection. · Check the L1, L2 and Neutral connections. · Verify symmetric load between L1, and L2 · Consult the local grid authority.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 2x1F
Grid voltage is above the country limit
Grid voltage is above the country limit.
Product fit · Unknown
Show field stepsHide field steps for 2x1F: Grid voltage is above the country limit
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Turn OFF the inverters in the site and verify AC grid voltage. · If the inverter is located far from the connection point to the grid, use a larger gauge AC wire. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 2x20
Grid voltage is below the country limit
Grid voltage is below the country limit.
Product fit · Unknown
Show field stepsHide field steps for 2x20: Grid voltage is below the country limit
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 2x21
Grid voltage is above the country limit
Grid voltage is above the country limit.
Product fit · Unknown
Show field stepsHide field steps for 2x21: Grid voltage is above the country limit
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Turn OFF the inverters in the site and verify AC grid voltage. · If the inverter is located far from the connection point to the grid, use a larger gauge AC wire. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 2x25
Ground faults may occur due to insufficient insulation to the ground
Ground faults may occur due to insufficient insulation to the ground.
Product fit · Unknown
Show field stepsHide field steps for 2x25: Ground faults may occur due to insufficient insulation to the ground
Product fit · Unknown
Safe checks now
Treat this as an electrical-safety event. Record the code and conditions, keep clear of the inverter and its wiring, and do not reset the unit or operate isolators; contact your installer promptly.
Installer remedy
The guide's documented step for this code: WARNING! ELECTRICAL SHOCK HAZARD. Do not touch uninsulated wires when the inverter cover is removed. RISQUE D’ÉLECTROCUTION, ne touchez pas les fils non isolés lorsque le couvercle de l'onduleur est retiré. Only a qualified technician should handle this problem, and only after taking proper precautions. 1. Turn the inverter ON/OFF switch to OFF. 2. Wait five minutes for the input capacitors to discharge. 3. Disconnect the AC breaker. 4. Disconnect the DC inputs. 5. Connect each DC string separately, turn the AC and the inverter ON/OFF switch to ON, until the error appears for the faulty string. · Do not connect strings with a grounding fault to the inverter. A certified installer must fix the faulty string before connecting it to the inverter · For further documentation, contact SolarEdge Support.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 2x26
Ground faults may occur due to insufficient insulation to the ground
Ground faults may occur due to insufficient insulation to the ground.
Product fit · Unknown
Show field stepsHide field steps for 2x26: Ground faults may occur due to insufficient insulation to the ground
Product fit · Unknown
Safe checks now
Treat this as an electrical-safety event. Record the code and conditions, keep clear of the inverter and its wiring, and do not reset the unit or operate isolators; contact your installer promptly.
Installer remedy
The guide's documented step for this code: WARNING! ELECTRICAL SHOCK HAZARD. Do not touch uninsulated wires when the inverter cover is removed. RISQUE D’ÉLECTROCUTION, ne touchez pas les fils non isolés lorsque le couvercle de l'onduleur est retiré. Only a qualified technician should handle this problem, and only after taking proper precautions. 1. Turn the inverter ON/OFF switch to OFF. 2. Wait five minutes for the input capacitors to discharge. 3. Disconnect the AC breaker. 4. Disconnect the DC inputs. 5. Connect each DC string separately, turn the AC and the inverter ON/OFF switch to ON, until the error appears for the faulty string. · Do not connect strings with a grounding fault to the inverter. A certified installer must fix the faulty string before connecting it to the inverter · For further documentation, contact SolarEdge Support.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 2x28
Grid is down
Grid is down.
Product fit · Unknown
Show field stepsHide field steps for 2x28: Grid is down
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: When AC grid voltage returns, the inverter will restart after the reconnection time. If the problem persists, consult with the grid operator.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 2x29
Grid voltage is below the country limit
Grid voltage is below the country limit.
Product fit · Unknown
Show field stepsHide field steps for 2x29: Grid voltage is below the country limit
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Verify that the inverter is set to the correct country. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 2x2C
No country selected
No country selected.
Product fit · Unknown
Show field stepsHide field steps for 2x2C: No country selected
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Select the country. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 2x2D
Portia - DSP1 comm error (3x2)
Portia - DSP1 comm error (3x2).
Product fit · Unknown
Show field stepsHide field steps for 2x2D: Portia - DSP1 comm error (3x2)
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact Support. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 2x95
Power train error
Power train error.
Product fit · Unknown
Show field stepsHide field steps for 2x95: Power train error
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact Support RMA. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 2x96
Arc-DSP1
Arc-DSP1.
Product fit · Unknown
Show field stepsHide field steps for 2x96: Arc-DSP1
Product fit · Unknown
Safe checks now
Treat this as an electrical-safety event. Record the code and conditions, keep clear of the inverter and its wiring, and do not reset the unit or operate isolators; contact your installer promptly.
Installer remedy
The guide's documented step for this code: Refer to Inverter Arc Detection and Interruption. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 2x97
Arc-DSP2
Arc-DSP2.
Product fit · Unknown
Show field stepsHide field steps for 2x97: Arc-DSP2
Product fit · Unknown
Safe checks now
Treat this as an electrical-safety event. Record the code and conditions, keep clear of the inverter and its wiring, and do not reset the unit or operate isolators; contact your installer promptly.
Installer remedy
The guide's documented step for this code: Refer to Inverter Arc Detection and Interruption. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 2x98
Tx test (previously known as arc test error)
Tx test (previously known as arc test error).
Product fit · Unknown
Show field stepsHide field steps for 2x98: Tx test (previously known as arc test error)
Product fit · Unknown
Safe checks now
Treat this as an electrical-safety event. Record the code and conditions, keep clear of the inverter and its wiring, and do not reset the unit or operate isolators; contact your installer promptly.
Installer remedy
The guide's documented step for this code: Refer to Inverter Arc Detection and Interruption. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 2xB5
Relay feedback
Relay feedback.
Product fit · Unknown
Show field stepsHide field steps for 2xB5: Relay feedback
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact Support RMA. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x3
Night Mode is an inverter status indicating that the input voltage is below 6V DC
Night Mode is an inverter status indicating that the input voltage is below 6V DC.
Product fit · Unknown
Show field stepsHide field steps for 18x3: Night Mode is an inverter status indicating that the input voltage is below 6V DC
Product fit · Unknown
Safe checks now
This is a status rather than a fault: the inverter reports its DC input below the operating threshold, which is normal outside daylight. Record it and contact your installer only if it shows when the array should be producing.
Installer remedy
The guide's documented step for this code: Test the DC side and contact support for further guidance. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x19
AC voltage surge
AC voltage surge.
Product fit · Unknown
Show field stepsHide field steps for 18x19: AC voltage surge
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: AC voltage surge. If the fault persists: · Check the AC connection to inverter. · Verify that the inverter is set to the correct country. · Check with the grid operator if a large surge source or irregular load exists near the site. · erify that the output wire size matches the distance between the inverter and the location of the grid connection. · Use a larger gauge wire for the AC output. · Refer to the AC Wiring Application Note at http://www.solaredge.us/files/pdfs/application-note-recommended-wiring.pdf.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x1A
AC voltage surge
AC voltage surge.
Product fit · Unknown
Show field stepsHide field steps for 18x1A: AC voltage surge
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: AC voltage surge. If the fault persists: · Check the AC connection to inverter. · Verify that the inverter is set to the correct country. · Check with the grid operator if a large surge source or irregular load exists near the site. · erify that the output wire size matches the distance between the inverter and the location of the grid connection. · Use a larger gauge wire for the AC output. · Refer to the AC Wiring Application Note at http://www.solaredge.us/files/pdfs/application-note-recommended-wiring.pdf.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x1B
AC voltage surge
AC voltage surge.
Product fit · Unknown
Show field stepsHide field steps for 18x1B: AC voltage surge
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: If the fault persists: · Check the AC connection to inverter. · Verify that the inverter is set to the correct country. · Check with the grid operator if a large surge source or irregular load exists near the site. · erify that the output wire size matches the distance between the inverter and the location of the grid connection. · Use a larger gauge wire for the AC output. · Refer to the AC Wiring Application Note at http://www.solaredge.us/files/pdfs/application-note-recommended-wiring.pdf.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x1C
Line voltage is low
Line voltage is low.
Product fit · Unknown
Show field stepsHide field steps for 18x1C: Line voltage is low
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x1D
Line voltage is low
Line voltage is low.
Product fit · Unknown
Show field stepsHide field steps for 18x1D: Line voltage is low
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x1E
Line voltage is low
Line voltage is low.
Product fit · Unknown
Show field stepsHide field steps for 18x1E: Line voltage is low
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x1F
Grid voltage is above the country limit
Grid voltage is above the country limit.
Product fit · Unknown
Show field stepsHide field steps for 18x1F: Grid voltage is above the country limit
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Turn OFF the inverters in the site and verify AC grid voltage. · If the inverter is located far from the connection point to the grid, use a larger gauge AC wire. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x20
Grid voltage is above the country limit
Grid voltage is above the country limit.
Product fit · Unknown
Show field stepsHide field steps for 18x20: Grid voltage is above the country limit
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Turn OFF the inverters in the site and verify AC grid voltage. · If the inverter is located far from the connection point to the grid, use a larger gauge AC wire. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x21
Grid voltage is above the country limit
Grid voltage is above the country limit.
Product fit · Unknown
Show field stepsHide field steps for 18x21: Grid voltage is above the country limit
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Turn OFF the inverters in the site and verify AC grid voltage. · If the inverter is located far from the connection point to the grid, use a larger gauge AC wire. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x22
Line voltage is low
Line voltage is low.
Product fit · Unknown
Show field stepsHide field steps for 18x22: Line voltage is low
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x23
Line voltage is low
Line voltage is low.
Product fit · Unknown
Show field stepsHide field steps for 18x23: Line voltage is low
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x24
Line voltage is low
Line voltage is low.
Product fit · Unknown
Show field stepsHide field steps for 18x24: Line voltage is low
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x25
Grid voltage is above the country limit
Grid voltage is above the country limit.
Product fit · Unknown
Show field stepsHide field steps for 18x25: Grid voltage is above the country limit
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Turn OFF the inverters in the site and verify AC grid voltage. · If the inverter is located far from the connection point to the grid, use a larger gauge AC wire. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x26
Grid voltage is above the country limit
Grid voltage is above the country limit.
Product fit · Unknown
Show field stepsHide field steps for 18x26: Grid voltage is above the country limit
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Turn OFF the inverters in the site and verify AC grid voltage. · If the inverter is located far from the connection point to the grid, use a larger gauge AC wire. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x27
Grid voltage is above the country limit
Grid voltage is above the country limit.
Product fit · Unknown
Show field stepsHide field steps for 18x27: Grid voltage is above the country limit
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Turn OFF the inverters in the site and verify AC grid voltage. · If the inverter is located far from the connection point to the grid, use a larger gauge AC wire. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x28
Line voltage is low
Line voltage is low.
Product fit · Unknown
Show field stepsHide field steps for 18x28: Line voltage is low
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x29
Line voltage is low
Line voltage is low.
Product fit · Unknown
Show field stepsHide field steps for 18x29: Line voltage is low
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x2A
Line voltage is low
Line voltage is low.
Product fit · Unknown
Show field stepsHide field steps for 18x2A: Line voltage is low
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x2B
Grid voltage is above the country limit
Grid voltage is above the country limit.
Product fit · Unknown
Show field stepsHide field steps for 18x2B: Grid voltage is above the country limit
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Turn OFF the inverters in the site and verify AC grid voltage. · If the inverter is located far from the connection point to the grid, use a larger gauge AC wire. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x2C
Grid voltage is above the country limit
Grid voltage is above the country limit.
Product fit · Unknown
Show field stepsHide field steps for 18x2C: Grid voltage is above the country limit
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Turn OFF the inverters in the site and verify AC grid voltage. · If the inverter is located far from the connection point to the grid, use a larger gauge AC wire. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x2D
Grid voltage is above the country limit
Grid voltage is above the country limit.
Product fit · Unknown
Show field stepsHide field steps for 18x2D: Grid voltage is above the country limit
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Turn OFF the inverters in the site and verify AC grid voltage. · If the inverter is located far from the connection point to the grid, use a larger gauge AC wire. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x2E
Line voltage is low
Line voltage is low.
Product fit · Unknown
Show field stepsHide field steps for 18x2E: Line voltage is low
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x2F
Line voltage is low
Line voltage is low.
Product fit · Unknown
Show field stepsHide field steps for 18x2F: Line voltage is low
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x30
Line voltage is low
Line voltage is low.
Product fit · Unknown
Show field stepsHide field steps for 18x30: Line voltage is low
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x31
Line voltage is high
Line voltage is high.
Product fit · Unknown
Show field stepsHide field steps for 18x31: Line voltage is high
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x32
Line voltage is high
Line voltage is high.
Product fit · Unknown
Show field stepsHide field steps for 18x32: Line voltage is high
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x33
Line voltage is high
Line voltage is high.
Product fit · Unknown
Show field stepsHide field steps for 18x33: Line voltage is high
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x34
Line voltage is low
Line voltage is low.
Product fit · Unknown
Show field stepsHide field steps for 18x34: Line voltage is low
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x35
Line voltage is low
Line voltage is low.
Product fit · Unknown
Show field stepsHide field steps for 18x35: Line voltage is low
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x36
Line voltage is low
Line voltage is low.
Product fit · Unknown
Show field stepsHide field steps for 18x36: Line voltage is low
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x37
Line voltage is high
Line voltage is high.
Product fit · Unknown
Show field stepsHide field steps for 18x37: Line voltage is high
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x38
Line voltage is low
Line voltage is low.
Product fit · Unknown
Show field stepsHide field steps for 18x38: Line voltage is low
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x39
If the error flags on all three phases at the same time, there is most likely a DC related…
If the error flags on all three phases at the same time, there is most likely a DC related issue on site.
Product fit · Unknown
Show field stepsHide field steps for 18x39: If the error flags on all three phases at the same time, there is most likely a DC related…
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Try landing one string at a time to the inverter, as well as swap strings between inverters (if there are multiple inverters), to see if the issue stays with the inverter or moved with the strings. · If the issue moves with the strings, there is likely an issue in the DC strings that need resolving, including but not limited to: Improper installation, improper stringing and design, etc. · Contact Support.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x3B
If the error flags on all three phases at the same time, there is most likely a DC related…
If the error flags on all three phases at the same time, there is most likely a DC related issue on site.
Product fit · Unknown
Show field stepsHide field steps for 18x3B: If the error flags on all three phases at the same time, there is most likely a DC related…
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Try landing one string at a time to the inverter, as well as swap strings between inverters (if there are multiple inverters), to see if the issue stays with the inverter or moved with the strings. · If the issue moves with the strings, there is likely an issue in the DC strings that need resolving, including but not limited to: Improper installation, improper stringing and design, etc. · Contact Support.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x3C
If the error flags on all three phases at the same time, there is most likely a DC related…
If the error flags on all three phases at the same time, there is most likely a DC related issue on site.
Product fit · Unknown
Show field stepsHide field steps for 18x3C: If the error flags on all three phases at the same time, there is most likely a DC related…
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Try landing one string at a time to the inverter, as well as swap strings between inverters (if there are multiple inverters), to see if the issue stays with the inverter or moved with the strings. · If the issue moves with the strings, there is likely an issue in the DC strings that need resolving, including but not limited to: Improper installation, improper stringing and design, etc. · Contact Support.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x40
The frequency measured on L1 is higher than the thresholds
The frequency measured on L1 is higher than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 18x40: The frequency measured on L1 is higher than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x41
The frequency measured on L2 is higher than the thresholds
The frequency measured on L2 is higher than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 18x41: The frequency measured on L2 is higher than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x42
The frequency measured on L3 is higher than the thresholds
The frequency measured on L3 is higher than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 18x42: The frequency measured on L3 is higher than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x43
The frequency measured on L1 is lower than the thresholds
The frequency measured on L1 is lower than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 18x43: The frequency measured on L1 is lower than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x44
The frequency measured on L2 is Lower than the thresholds
The frequency measured on L2 is Lower than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 18x44: The frequency measured on L2 is Lower than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code Verify AC frequency and voltages on site. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x45
The frequency measured on L3 is Lower than the thresholds
The frequency measured on L3 is Lower than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 18x45: The frequency measured on L3 is Lower than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x46
The frequency measured on L1 is higher than the thresholds
The frequency measured on L1 is higher than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 18x46: The frequency measured on L1 is higher than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x47
The frequency measured on L2 is higher than the thresholds
The frequency measured on L2 is higher than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 18x47: The frequency measured on L2 is higher than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x48
The frequency measured on L3 is higher than the thresholds
The frequency measured on L3 is higher than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 18x48: The frequency measured on L3 is higher than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x49
The frequency measured on L1 is lower than the thresholds
The frequency measured on L1 is lower than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 18x49: The frequency measured on L1 is lower than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x4A
The frequency measured on L2 is Lower than the thresholds
The frequency measured on L2 is Lower than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 18x4A: The frequency measured on L2 is Lower than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x4B
The frequency measured on L3 is Lower than the thresholds
The frequency measured on L3 is Lower than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 18x4B: The frequency measured on L3 is Lower than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x4C
The frequency measured on L1 is higher than the thresholds
The frequency measured on L1 is higher than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 18x4C: The frequency measured on L1 is higher than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x4D
The frequency measured on L2 is higher than the thresholds
The frequency measured on L2 is higher than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 18x4D: The frequency measured on L2 is higher than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x4E
The frequency measured on L3 is higher than the thresholds
The frequency measured on L3 is higher than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 18x4E: The frequency measured on L3 is higher than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x4F
The frequency measured on L1 is lower than the thresholds
The frequency measured on L1 is lower than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 18x4F: The frequency measured on L1 is lower than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x50
The frequency measured on L2 is Lower than the thresholds
The frequency measured on L2 is Lower than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 18x50: The frequency measured on L2 is Lower than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x51
The frequency measured on L3 is Lower than the thresholds
The frequency measured on L3 is Lower than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 18x51: The frequency measured on L3 is Lower than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x52
The frequency measured on L1 is higher than the thresholds
The frequency measured on L1 is higher than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 18x52: The frequency measured on L1 is higher than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x53
The frequency measured on L2 is higher than the thresholds
The frequency measured on L2 is higher than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 18x53: The frequency measured on L2 is higher than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x54
The frequency measured on L3 is higher than the thresholds
The frequency measured on L3 is higher than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 18x54: The frequency measured on L3 is higher than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x55
The frequency measured on L1 is lower than the thresholds
The frequency measured on L1 is lower than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 18x55: The frequency measured on L1 is lower than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x56
The frequency measured on L2 is Lower than the thresholds
The frequency measured on L2 is Lower than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 18x56: The frequency measured on L2 is Lower than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x57
The frequency measured on L3 is Lower than the thresholds
The frequency measured on L3 is Lower than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 18x57: The frequency measured on L3 is Lower than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x58
The frequency measured on L1 is higher than the thresholds
The frequency measured on L1 is higher than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 18x58: The frequency measured on L1 is higher than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x59
The frequency measured on L2 is higher than the thresholds
The frequency measured on L2 is higher than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 18x59: The frequency measured on L2 is higher than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x5A
The frequency measured on L3 is higher than the thresholds
The frequency measured on L3 is higher than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 18x5A: The frequency measured on L3 is higher than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x5B
The frequency measured on L1 is lower than the thresholds
The frequency measured on L1 is lower than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 18x5B: The frequency measured on L1 is lower than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x5C
The frequency measured on L2 is Lower than the thresholds
The frequency measured on L2 is Lower than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 18x5C: The frequency measured on L2 is Lower than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x5D
The frequency measured on L3 is Lower than the thresholds
The frequency measured on L3 is Lower than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 18x5D: The frequency measured on L3 is Lower than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x60
Grid is down
Grid is down. When AC grid voltage returns the inverter will restart after the reconnection time.
Product fit · Unknown
Show field stepsHide field steps for 18x60: Grid is down
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: If the problem persists, consult with the grid operator. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x62
Grid is down
Grid is down. When AC grid voltage returns the inverter will restart after the reconnection time.
Product fit · Unknown
Show field stepsHide field steps for 18x62: Grid is down
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: If the problem persists, consult with the grid operator. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x6F
Grid voltage is above the country limit
Grid voltage is above the country limit.
Product fit · Unknown
Show field stepsHide field steps for 18x6F: Grid voltage is above the country limit
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Turn OFF the inverters in the site and verify AC grid voltage. · If the inverter is located far from the connection point to the grid, use a larger gauge AC wire. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x70
Grid voltage is above the country limit
Grid voltage is above the country limit.
Product fit · Unknown
Show field stepsHide field steps for 18x70: Grid voltage is above the country limit
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Turn OFF the inverters in the site and verify AC grid voltage. · If the inverter is located far from the connection point to the grid, use a larger gauge AC wire. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18x71
Grid voltage is above the country limit
Grid voltage is above the country limit.
Product fit · Unknown
Show field stepsHide field steps for 18x71: Grid voltage is above the country limit
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Turn OFF the inverters in the site and verify AC grid voltage. · If the inverter is located far from the connection point to the grid, use a larger gauge AC wire. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18xB5
DC/AC in-stage overvoltage
DC/AC in-stage overvoltage.
Product fit · Unknown
Show field stepsHide field steps for 18xB5: DC/AC in-stage overvoltage
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact Support RMA related. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18xB6
DC/AC out-stage overvoltage
DC/AC out-stage overvoltage.
Product fit · Unknown
Show field stepsHide field steps for 18xB6: DC/AC out-stage overvoltage
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact Support RMA related. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18xB7
DC/AC in-stage overvoltage
DC/AC in-stage overvoltage.
Product fit · Unknown
Show field stepsHide field steps for 18xB7: DC/AC in-stage overvoltage
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact Support RMA related. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18xB8
DC/AC out-stage overvoltage
DC/AC out-stage overvoltage.
Product fit · Unknown
Show field stepsHide field steps for 18xB8: DC/AC out-stage overvoltage
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact Support RMA related. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18xB9
DC/DC in-stage overvoltage
DC/DC in-stage overvoltage.
Product fit · Unknown
Show field stepsHide field steps for 18xB9: DC/DC in-stage overvoltage
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact Support RMA related. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18xBA
DC/DC out-stage overvoltage
DC/DC out-stage overvoltage.
Product fit · Unknown
Show field stepsHide field steps for 18xBA: DC/DC out-stage overvoltage
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact Support RMA related. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18xBB
Vin min
Vin min.
Product fit · Unknown
Show field stepsHide field steps for 18xBB: Vin min
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide gives no troubleshooting for this code. Record the event and escalate to SolarEdge support rather than improvising a procedure.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18xBC
Power module voltage imbalance
Power module voltage imbalance.
Product fit · Unknown
Show field stepsHide field steps for 18xBC: Power module voltage imbalance
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact Support RMA related. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18xBD
Power module voltage imbalance
Power module voltage imbalance.
Product fit · Unknown
Show field stepsHide field steps for 18xBD: Power module voltage imbalance
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact Support RMA related. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18xD8
Grid voltage is above the country limit
Grid voltage is above the country limit.
Product fit · Unknown
Show field stepsHide field steps for 18xD8: Grid voltage is above the country limit
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Turn OFF the inverters in the site and verify AC grid voltage. · If the inverter is located far from the connection point to the grid, use a larger gauge AC wire. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18xD9
Grid voltage is above the country limit
Grid voltage is above the country limit.
Product fit · Unknown
Show field stepsHide field steps for 18xD9: Grid voltage is above the country limit
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Turn OFF the inverters in the site and verify AC grid voltage. · If the inverter is located far from the connection point to the grid, use a larger gauge AC wire. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18xDA
Grid voltage is above the country limit
Grid voltage is above the country limit.
Product fit · Unknown
Show field stepsHide field steps for 18xDA: Grid voltage is above the country limit
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Turn OFF the inverters in the site and verify AC grid voltage. · If the inverter is located far from the connection point to the grid, use a larger gauge AC wire. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18xDB
Grid voltage is below the country limit
Grid voltage is below the country limit.
Product fit · Unknown
Show field stepsHide field steps for 18xDB: Grid voltage is below the country limit
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Turn OFF the inverters in the site and verify AC grid voltage. · If the inverter is located far from the connection point to the grid, use a larger gauge AC wire. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18xDC
Grid voltage is below the country limit
Grid voltage is below the country limit.
Product fit · Unknown
Show field stepsHide field steps for 18xDC: Grid voltage is below the country limit
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Turn OFF the inverters in the site and verify AC grid voltage. · If the inverter is located far from the connection point to the grid, use a larger gauge AC wire. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18xDD
Grid voltage is below the country limit
Grid voltage is below the country limit.
Product fit · Unknown
Show field stepsHide field steps for 18xDD: Grid voltage is below the country limit
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Turn OFF the inverters in the site and verify AC grid voltage. · If the inverter is located far from the connection point to the grid, use a larger gauge AC wire. · Consult the grid operator. · If permitted by local authorities, change the grid protection values..
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18xDE
The frequency measured on L1 is lower than the thresholds
The frequency measured on L1 is lower than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 18xDE: The frequency measured on L1 is lower than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18xDF
The frequency measured on L2 is Lower than the thresholds
The frequency measured on L2 is Lower than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 18xDF: The frequency measured on L2 is Lower than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18xE0
The frequency measured on L3 is Lower than the thresholds
The frequency measured on L3 is Lower than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 18xE0: The frequency measured on L3 is Lower than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18xE1
The frequency measured on L1 is lower than the thresholds
The frequency measured on L1 is lower than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 18xE1: The frequency measured on L1 is lower than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18xE2
The frequency measured on L2 is higher than the thresholds
The frequency measured on L2 is higher than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 18xE2: The frequency measured on L2 is higher than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18xE3
The frequency measured on L3 is higher than the thresholds
The frequency measured on L3 is higher than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 18xE3: The frequency measured on L3 is higher than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18xE4
The line to neutral voltage on the AC side of the system is out of range, based on the trip…
The line to neutral voltage on the AC side of the system is out of range, based on the trip points set by the country code. The guide lists this code more than once; its other entry instead gives: Contact SolarEdge Support.
Product fit · Unknown
Show field stepsHide field steps for 18xE4: The line to neutral voltage on the AC side of the system is out of range, based on the trip…
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Turn OFF the inverters in the site and verify AC grid voltage. · If the inverter is located far from the connection point to the grid, use a larger gauge AC wire. · Consult the grid operator. · If permitted by local authorities, change the grid protection values. The guide's other listing for this code instead gives: Contact SolarEdge Support.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 18xE5
The line to neutral voltage on the AC side of the system is out of range, based on the trip…
The line to neutral voltage on the AC side of the system is out of range, based on the trip points set by the country code. The guide lists this code more than once; its other entry instead gives: Contact SolarEdge Support.
Product fit · Unknown
Show field stepsHide field steps for 18xE5: The line to neutral voltage on the AC side of the system is out of range, based on the trip…
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Turn OFF the inverters in the site and verify AC grid voltage. · If the inverter is located far from the connection point to the grid, use a larger gauge AC wire. · Consult the grid operator. · If permitted by local authorities, change the grid protection values. The guide's other listing for this code instead gives: Contact SolarEdge Support.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x3 · Commercial
Night Mode is an inverter status indicating that the input voltage is below 6V DC
Commercial three-phase inverters: Night Mode is an inverter status indicating that the input voltage is below 6V DC.
Product fit · Unknown
Show field stepsHide field steps for 8x3 · Commercial: Night Mode is an inverter status indicating that the input voltage is below 6V DC
Product fit · Unknown
Safe checks now
This is a status rather than a fault: the inverter reports its DC input below the operating threshold, which is normal outside daylight. Record it and contact your installer only if it shows when the array should be producing.
Installer remedy
The guide's documented step for this code: · Test the DC side · Contact support for further guidance. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x10 · Commercial
Communication
Commercial three-phase inverters: Communication.
Product fit · Unknown
Show field stepsHide field steps for 8x10 · Commercial: Communication
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact SolarEdge Support. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x11 · Commercial
Unexpected Mode
Commercial three-phase inverters: Unexpected Mode.
Product fit · Unknown
Show field stepsHide field steps for 8x11 · Commercial: Unexpected Mode
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact SolarEdge Support. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x12 · Commercial
Vf ESR meas
Commercial three-phase inverters: Vf ESR meas.
Product fit · Unknown
Show field stepsHide field steps for 8x12 · Commercial: Vf ESR meas
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact SolarEdge Support. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x13 · Commercial
Reset\Stop
Commercial three-phase inverters: Reset\Stop.
Product fit · Unknown
Show field stepsHide field steps for 8x13 · Commercial: Reset\Stop
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact SolarEdge Support. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x16 · Commercial
Main Capacitor estimation event
Commercial three-phase inverters: Main Capacitor estimation event.
Product fit · Unknown
Show field stepsHide field steps for 8x16 · Commercial: Main Capacitor estimation event
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact SolarEdge Support. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x18 · Commercial
RSD Error
Commercial three-phase inverters: RSD Error.
Product fit · Unknown
Show field stepsHide field steps for 8x18 · Commercial: RSD Error
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact SolarEdge Support. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x19 · Commercial
AC voltage surge
Commercial three-phase inverters: AC voltage surge.
Product fit · Unknown
Show field stepsHide field steps for 8x19 · Commercial: AC voltage surge
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Check the AC connection to inverter. · Verify that the inverter is set to the correct country. · Check with the grid operator if a large surge source or irregular load exists near the site. · Verify that the output wire size matches the distance between the inverter and the location of the grid connection. · Use a larger gauge wire for the AC output. · Refer to the AC Wiring Application Note at http://www.solaredge.us/files/pdfs/application-note-recommended-wiring.pdf.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x1A · Commercial
AC voltage surge
Commercial three-phase inverters: AC voltage surge.
Product fit · Unknown
Show field stepsHide field steps for 8x1A · Commercial: AC voltage surge
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: If the fault persists: · Check the AC connection to inverter. · Verify that the inverter is set to the correct country. · Check with the grid operator if a large surge source or irregular load exists near the site. · Verify that the output wire size matches the distance between the inverter and the location of the grid connection. · Use a larger gauge wire for the AC output. · Refer to the AC Wiring Application Note at http://www.solaredge.us/files/pdfs/application-note-recommended-wiring.pdf.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x1B · Commercial
AC voltage surge
Commercial three-phase inverters: AC voltage surge.
Product fit · Unknown
Show field stepsHide field steps for 8x1B · Commercial: AC voltage surge
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: If the fault persists: · Check the AC connection to inverter. · Verify that the inverter is set to the correct country. · Check with the grid operator if a large surge source or irregular load exists near the site. · Verify that the output wire size matches the distance between the inverter and the location of the grid connection. · Use a larger gauge wire for the AC output. · Refer to the AC Wiring Application Note at http://www.solaredge.us/files/pdfs/application-note-recommended-wiring.pdf.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x1C · Commercial
Grid Voltage is below the country limit
Commercial three-phase inverters: Grid Voltage is below the country limit.
Product fit · Unknown
Show field stepsHide field steps for 8x1C · Commercial: Grid Voltage is below the country limit
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x1D · Commercial
Grid Voltage is below the country limit
Commercial three-phase inverters: Grid Voltage is below the country limit.
Product fit · Unknown
Show field stepsHide field steps for 8x1D · Commercial: Grid Voltage is below the country limit
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x1E · Commercial
Grid Voltage is below the country limit
Commercial three-phase inverters: Grid Voltage is below the country limit.
Product fit · Unknown
Show field stepsHide field steps for 8x1E · Commercial: Grid Voltage is below the country limit
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x1F · Commercial
Grid voltage is above the country limit
Commercial three-phase inverters: Grid voltage is above the country limit.
Product fit · Unknown
Show field stepsHide field steps for 8x1F · Commercial: Grid voltage is above the country limit
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Turn OFF the inverters in the site and verify AC grid voltage. · If the inverter is located far from the connection point to the grid, use a larger gauge AC wire. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x20 · Commercial
Grid voltage is above the country limit
Commercial three-phase inverters: Grid voltage is above the country limit.
Product fit · Unknown
Show field stepsHide field steps for 8x20 · Commercial: Grid voltage is above the country limit
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Turn OFF the inverters in the site and verify AC grid voltage. · If the inverter is located far from the connection point to the grid, use a larger gauge AC wire. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x21 · Commercial
Grid voltage is above the country limit
Commercial three-phase inverters: Grid voltage is above the country limit.
Product fit · Unknown
Show field stepsHide field steps for 8x21 · Commercial: Grid voltage is above the country limit
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country. · Turn OFF the inverters in the site and verify AC grid voltage. · If the inverter is located far from the connection point to the grid, use a larger gauge AC wire. · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x22 · Commercial
Grid Voltage is below the country limit
Commercial three-phase inverters: Grid Voltage is below the country limit.
Product fit · Unknown
Show field stepsHide field steps for 8x22 · Commercial: Grid Voltage is below the country limit
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x23 · Commercial
Grid Voltage is below the country limit
Commercial three-phase inverters: Grid Voltage is below the country limit.
Product fit · Unknown
Show field stepsHide field steps for 8x23 · Commercial: Grid Voltage is below the country limit
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x24 · Commercial
Grid Voltage is below the country limit
Commercial three-phase inverters: Grid Voltage is below the country limit.
Product fit · Unknown
Show field stepsHide field steps for 8x24 · Commercial: Grid Voltage is below the country limit
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x25 · Commercial
Grid voltage above country limit
Commercial three-phase inverters: Grid voltage above country limit.
Product fit · Unknown
Show field stepsHide field steps for 8x25 · Commercial: Grid voltage above country limit
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x26 · Commercial
Grid voltage below country limit
Commercial three-phase inverters: Grid voltage below country limit.
Product fit · Unknown
Show field stepsHide field steps for 8x26 · Commercial: Grid voltage below country limit
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x27 · Commercial
If the error flags on all three phases at the same time, there is most likely a DC related…
Commercial three-phase inverters: If the error flags on all three phases at the same time, there is most likely a DC related issue on site.
Product fit · Unknown
Show field stepsHide field steps for 8x27 · Commercial: If the error flags on all three phases at the same time, there is most likely a DC related…
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Try landing one string at a time to the inverter, as well as swap strings between inverters (if there are multiple inverters), to see if the issue stays with the inverter or moved with the strings. · If the issue moves with the strings, there is likely an issue in the DC strings that need resolving, including but not limited to: Improper installation, improper stringing and design, etc. · Contact Support.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x29 · Commercial
If the error flags on all three phases at the same time, there is most likely a DC related…
Commercial three-phase inverters: If the error flags on all three phases at the same time, there is most likely a DC related issue on site.
Product fit · Unknown
Show field stepsHide field steps for 8x29 · Commercial: If the error flags on all three phases at the same time, there is most likely a DC related…
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Try landing one string at a time to the inverter, as well as swap strings between inverters (if there are multiple inverters), to see if the issue stays with the inverter or moved with the strings. · If the issue moves with the strings, there is likely an issue in the DC strings that need resolving, including but not limited to: Improper installation, improper stringing and design, etc. · Contact Support.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x2A · Commercial
If the error flags on all three phases at the same time, there is most likely a DC related…
Commercial three-phase inverters: If the error flags on all three phases at the same time, there is most likely a DC related issue on site.
Product fit · Unknown
Show field stepsHide field steps for 8x2A · Commercial: If the error flags on all three phases at the same time, there is most likely a DC related…
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Try landing one string at a time to the inverter, as well as swap strings between inverters (if there are multiple inverters), to see if the issue stays with the inverter or moved with the strings. · If the issue moves with the strings, there is likely an issue in the DC strings that need resolving, including but not limited to: Improper installation, improper stringing and design, etc. · Contact Support.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x2B · Commercial
Ground faults may occur due to insufficient insulation to the ground
Commercial three-phase inverters: Ground faults may occur due to insufficient insulation to the ground.
Product fit · Unknown
Show field stepsHide field steps for 8x2B · Commercial: Ground faults may occur due to insufficient insulation to the ground
Product fit · Unknown
Safe checks now
Treat this as an electrical-safety event. Record the code and conditions, keep clear of the inverter and its wiring, and do not reset the unit or operate isolators; contact your installer promptly.
Installer remedy
The guide's documented step for this code: WARNING! ELECTRICAL SHOCK HAZARD. Do not touch uninsulated wires when the inverter cover is removed. RISQUE D’ÉLECTROCUTION, ne touchez pas les fils non isolés lorsque le couvercle de l'onduleur est retiré. Only a qualified technician should handle this problem, and only after taking proper precautions. 1. Turn the inverter ON/OFF switch to OFF. 2. Wait five minutes for the input capacitors to discharge. 3. Disconnect the AC breaker. 4. Disconnect the DC inputs. 5. Connect each DC string separately, turn the AC and the inverter ON/OFF switch to ON, until the error appears for the faulty string. · Do not connect strings with a grounding fault to the inverter. A certified installer must fix the faulty string before connecting it to the inverter · For further documentation, contact SolarEdge Support.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x2C · Commercial
Ground faults may occur due to insufficient insulation to the ground
Commercial three-phase inverters: Ground faults may occur due to insufficient insulation to the ground.
Product fit · Unknown
Show field stepsHide field steps for 8x2C · Commercial: Ground faults may occur due to insufficient insulation to the ground
Product fit · Unknown
Safe checks now
Treat this as an electrical-safety event. Record the code and conditions, keep clear of the inverter and its wiring, and do not reset the unit or operate isolators; contact your installer promptly.
Installer remedy
The guide's documented step for this code: WARNING! ELECTRICAL SHOCK HAZARD. Do not touch uninsulated wires when the inverter cover is removed. RISQUE D’ÉLECTROCUTION, ne touchez pas les fils non isolés lorsque le couvercle de l'onduleur est retiré. Only a qualified technician should handle this problem, and only after taking proper precautions. 1. Turn the inverter ON/OFF switch to OFF. 2. Wait five minutes for the input capacitors to discharge. 3. Disconnect the AC breaker. 4. Disconnect the DC inputs. 5. Connect each DC string separately, turn the AC and the inverter ON/OFF switch to ON, until the error appears for the faulty string. · Do not connect strings with a grounding fault to the inverter. A certified installer must fix the faulty string before connecting it to the inverter · For further documentation, contact SolarEdge Support.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x2E · Commercial
The frequency measured on L1 is higher than the thresholds
Commercial three-phase inverters: The frequency measured on L1 is higher than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 8x2E · Commercial: The frequency measured on L1 is higher than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x2F · Commercial
The frequency measured on L2 is higher than the thresholds
Commercial three-phase inverters: The frequency measured on L2 is higher than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 8x2F · Commercial: The frequency measured on L2 is higher than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x30 · Commercial
The frequency measured on L3 is higher than the thresholds
Commercial three-phase inverters: The frequency measured on L3 is higher than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 8x30 · Commercial: The frequency measured on L3 is higher than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x31 · Commercial
The frequency measured on L1 is Lower than the thresholds
Commercial three-phase inverters: The frequency measured on L1 is Lower than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 8x31 · Commercial: The frequency measured on L1 is Lower than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x32 · Commercial
The frequency measured on L2 is Lower than the thresholds
Commercial three-phase inverters: The frequency measured on L2 is Lower than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 8x32 · Commercial: The frequency measured on L2 is Lower than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x33 · Commercial
The frequency measured on L3 is Lower than the thresholds
Commercial three-phase inverters: The frequency measured on L3 is Lower than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 8x33 · Commercial: The frequency measured on L3 is Lower than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x34 · Commercial
The SolarEdge system normally eliminates DC overvoltage errors
Commercial three-phase inverters: The SolarEdge system normally eliminates DC overvoltage errors.
Product fit · Unknown
Show field stepsHide field steps for 8x34 · Commercial: The SolarEdge system normally eliminates DC overvoltage errors
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: If the fault persists: · Turn OFF the inverter ON/OFF switch. If after five minutes, the LCD panel does not show a low safety voltage (1V per optimizer), check which string is malfunctioning and recheck its connections to the inverter. · Proceed according to Power Optimizer Troubleshooting · Re-commission all inverters in the site, as described in Commissioning the Installation.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x35 · Commercial
The SolarEdge system normally eliminates DC overvoltage errors
Commercial three-phase inverters: The SolarEdge system normally eliminates DC overvoltage errors.
Product fit · Unknown
Show field stepsHide field steps for 8x35 · Commercial: The SolarEdge system normally eliminates DC overvoltage errors
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: If the fault persists: · Turn OFF the inverter ON/OFF switch. If after five minutes, the LCD panel does not show a low safety voltage (1V per optimizer), check which string is malfunctioning and recheck its connections to the inverter. · Proceed according to Power Optimizer Troubleshooting · Re-commission all inverters in the site, as described in Commissioning the Installation.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x36 · Commercial
AC grid voltage malfunction
Commercial three-phase inverters: AC grid voltage malfunction.
Product fit · Unknown
Show field stepsHide field steps for 8x36 · Commercial: AC grid voltage malfunction
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · When AC voltage returns the inverter should restart after the reconnection time. · If the problem persists, consult with the grid operator.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x37 · Commercial
The SolarEdge system normally eliminates DC overvoltage errors
Commercial three-phase inverters: The SolarEdge system normally eliminates DC overvoltage errors.
Product fit · Unknown
Show field stepsHide field steps for 8x37 · Commercial: The SolarEdge system normally eliminates DC overvoltage errors
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: If the fault persists: · Turn OFF the inverter ON/OFF switch. If after five minutes, the LCD panel does not show a low safety voltage (1V per optimizer), check which string is malfunctioning and recheck its connections to the inverter. · Proceed according to Power Optimizer Troubleshooting · Re-commission all inverters in the site, as described in Commissioning the Installation.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x38 · Commercial
AC grid voltage malfunction
Commercial three-phase inverters: AC grid voltage malfunction. When AC voltage returns the inverter should restart after the reconnection time.
Product fit · Unknown
Show field stepsHide field steps for 8x38 · Commercial: AC grid voltage malfunction
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: If the problem persists, consult with the grid operator. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x39 · Commercial
Ground faults may occur due to insufficient insulation to the ground
Commercial three-phase inverters: Ground faults may occur due to insufficient insulation to the ground.
Product fit · Unknown
Show field stepsHide field steps for 8x39 · Commercial: Ground faults may occur due to insufficient insulation to the ground
Product fit · Unknown
Safe checks now
Treat this as an electrical-safety event. Record the code and conditions, keep clear of the inverter and its wiring, and do not reset the unit or operate isolators; contact your installer promptly.
Installer remedy
The guide's documented step for this code: WARNING! ELECTRICAL SHOCK HAZARD. Do not touch uninsulated wires when the inverter cover is removed. RISQUE D’ÉLECTROCUTION, ne touchez pas les fils non isolés lorsque le couvercle de l'onduleur est retiré. Only a qualified technician should handle this problem, and only after taking proper precautions. 1. Turn the inverter ON/OFF switch to OFF. 2. Wait five minutes for the input capacitors to discharge. 3. Disconnect the AC breaker. 4. Disconnect the DC inputs. 5. Connect each DC string separately, turn the AC and the inverter ON/OFF switch to ON, until the error appears for the faulty string. · Do not connect strings with a grounding fault to the inverter. A certified installer must fix the faulty string before connecting it to the inverter · For further documentation, contact SolarEdge Support.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x42 · Commercial
Grid Voltage Spike
Commercial three-phase inverters: Grid Voltage Spike.
Product fit · Unknown
Show field stepsHide field steps for 8x42 · Commercial: Grid Voltage Spike
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x43 · Commercial
Grid Voltage Spike
Commercial three-phase inverters: Grid Voltage Spike.
Product fit · Unknown
Show field stepsHide field steps for 8x43 · Commercial: Grid Voltage Spike
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x44 · Commercial
Grid Voltage Spike
Commercial three-phase inverters: Grid Voltage Spike.
Product fit · Unknown
Show field stepsHide field steps for 8x44 · Commercial: Grid Voltage Spike
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify that the inverter is set to the correct country · Consult the grid operator. · If permitted by local authorities, change the grid protection values.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x45 · Commercial
DC Voltage Spike
Commercial three-phase inverters: DC Voltage Spike.
Product fit · Unknown
Show field stepsHide field steps for 8x45 · Commercial: DC Voltage Spike
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact SolarEdge support. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x46 · Commercial
DC Voltage Spike
Commercial three-phase inverters: DC Voltage Spike.
Product fit · Unknown
Show field stepsHide field steps for 8x46 · Commercial: DC Voltage Spike
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact SolarEdge support. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x47 · Commercial
Over temperature
Commercial three-phase inverters: Over temperature.
Product fit · Unknown
Show field stepsHide field steps for 8x47 · Commercial: Over temperature
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify proper inverter clearances. · Make sure the heat-sink fins are clean and unobstructed.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x48 · Commercial
Under temperature
Commercial three-phase inverters: Under temperature.
Product fit · Unknown
Show field stepsHide field steps for 8x48 · Commercial: Under temperature
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Make sure the inverter is installed in a location with ambient temperatures within the range specified in the datasheet.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x4F · Commercial
Wrong AC connection
Commercial three-phase inverters: Wrong AC connection.
Product fit · Unknown
Show field stepsHide field steps for 8x4F · Commercial: Wrong AC connection
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Switch between L1 and L2 or L2 and L3 connections. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x52 · Commercial
VDC+/- capacitors banks unbalanced
Commercial three-phase inverters: VDC+/- capacitors banks unbalanced.
Product fit · Unknown
Show field stepsHide field steps for 8x52 · Commercial: VDC+/- capacitors banks unbalanced
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact SolarEdge support. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x53 · Commercial
VNN error
Commercial three-phase inverters: VNN error.
Product fit · Unknown
Show field stepsHide field steps for 8x53 · Commercial: VNN error
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact SolarEdge support. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x54 · Commercial
Low power
Commercial three-phase inverters: Low power.
Product fit · Unknown
Show field stepsHide field steps for 8x54 · Commercial: Low power
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact SolarEdge support. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x56 · Commercial
Power train error
Commercial three-phase inverters: Power train error.
Product fit · Unknown
Show field stepsHide field steps for 8x56 · Commercial: Power train error
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact support RMA. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x57 · Commercial
Broken or unconnected temperature sensor
Commercial three-phase inverters: Broken or unconnected temperature sensor.
Product fit · Unknown
Show field stepsHide field steps for 8x57 · Commercial: Broken or unconnected temperature sensor
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact SolarEdge Support. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x58 · Commercial
PV solar array is not properly isolated from ground earth
Commercial three-phase inverters: PV solar array is not properly isolated from ground earth.
Product fit · Unknown
Show field stepsHide field steps for 8x58 · Commercial: PV solar array is not properly isolated from ground earth
Product fit · Unknown
Safe checks now
Treat this as an electrical-safety event. Record the code and conditions, keep clear of the inverter and its wiring, and do not reset the unit or operate isolators; contact your installer promptly.
Installer remedy
The guide's documented step for this code: · Check the PV installation for isolation problems and ground leakage. · Only a certified PV installer must fix the faulty string before connecting it to the inverter. · Refer to www.solaredge.us/files/pdfs/application_note_isolation_fault_troubleshooting.pdf.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x59 · Commercial
Relay Test
Commercial three-phase inverters: Relay Test.
Product fit · Unknown
Show field stepsHide field steps for 8x59 · Commercial: Relay Test
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact SolarEdge support. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x5B · Commercial
RCD Test
Commercial three-phase inverters: RCD Test.
Product fit · Unknown
Show field stepsHide field steps for 8x5B · Commercial: RCD Test
Product fit · Unknown
Safe checks now
Treat this as an electrical-safety event. Record the code and conditions, keep clear of the inverter and its wiring, and do not reset the unit or operate isolators; contact your installer promptly.
Installer remedy
The guide's documented step for this code: Contact SolarEdge support. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x5D · Commercial
Test Iso Test
Commercial three-phase inverters: Test Iso Test.
Product fit · Unknown
Show field stepsHide field steps for 8x5D · Commercial: Test Iso Test
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact SolarEdge support. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x6A · Commercial
Cooling-fan check (guide column error)
The guide's row for this code is split across its two columns by a layout error: the description cell holds only the first step, "Power off AC to the inverter", and the troubleshooting cell holds the rest of the same fan-inspection procedure, ending with "Power on AC to the inverter". The code itself concerns a cooling fan; the guide prints no separate description of the fault.
Product fit · Unknown
Show field stepsHide field steps for 8x6A · Commercial: Cooling-fan check (guide column error)
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify the specified fan is plugged in, has no damage to the wiring, and has no debris caught in the fan that could prevent it from spinning · Fan 1: External - Usually found on the bottom of the inverter screwed in with a small grate cover · Fan 2: Internal - Usually found on or near one of the boards inside the inverter · Power on AC to the inverter.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x6B · Commercial
Cooling-fan check (guide column error)
The guide's row for this code is split across its two columns by a layout error: the description cell holds only the first step, "Power off AC to the inverter", and the troubleshooting cell holds the rest of the same fan-inspection procedure, ending with "Power on AC to the inverter". The code itself concerns a cooling fan; the guide prints no separate description of the fault.
Product fit · Unknown
Show field stepsHide field steps for 8x6B · Commercial: Cooling-fan check (guide column error)
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify the specified fan is plugged in, has no damage to the wiring, and has no debris caught in the fan that could prevent it from spinning · Fan 1: External - Usually found on the bottom of the inverter screwed in with a small grate cover · Fan 2: Internal - Usually found on or near one of the boards inside the inverter · Power on AC to the inverter.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x75 · Commercial
Capacitor over voltage
Commercial three-phase inverters: Capacitor over voltage.
Product fit · Unknown
Show field stepsHide field steps for 8x75 · Commercial: Capacitor over voltage
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact Support RMA. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x76 · Commercial
Capacitor over voltage
Commercial three-phase inverters: Capacitor over voltage.
Product fit · Unknown
Show field stepsHide field steps for 8x76 · Commercial: Capacitor over voltage
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact Support RMA. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x77 · Commercial
Over temperature
Commercial three-phase inverters: Over temperature.
Product fit · Unknown
Show field stepsHide field steps for 8x77 · Commercial: Over temperature
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify proper inverter clearances. · Make sure the heat-sink fins are clean and unobstructed.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x78 · Commercial
Over temperature
Commercial three-phase inverters: Over temperature.
Product fit · Unknown
Show field stepsHide field steps for 8x78 · Commercial: Over temperature
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify proper inverter clearances. · Make sure the heat-sink fins are clean and unobstructed..
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x79 · Commercial
Over temperature
Commercial three-phase inverters: Over temperature.
Product fit · Unknown
Show field stepsHide field steps for 8x79 · Commercial: Over temperature
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Verify proper inverter clearances. · Make sure the heat-sink fins are clean and unobstructed.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x7A · Commercial
Over current
Commercial three-phase inverters: Over current.
Product fit · Unknown
Show field stepsHide field steps for 8x7A · Commercial: Over current
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact Support RMA. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x7B · Commercial
Over current
Commercial three-phase inverters: Over current.
Product fit · Unknown
Show field stepsHide field steps for 8x7B · Commercial: Over current
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact Support RMA. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x7C · Commercial
Over current
Commercial three-phase inverters: Over current.
Product fit · Unknown
Show field stepsHide field steps for 8x7C · Commercial: Over current
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact Support RMA. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x7D · Commercial
Driver Short
Commercial three-phase inverters: Driver Short.
Product fit · Unknown
Show field stepsHide field steps for 8x7D · Commercial: Driver Short
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact Support RMA. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x7E · Commercial
Driver Short
Commercial three-phase inverters: Driver Short.
Product fit · Unknown
Show field stepsHide field steps for 8x7E · Commercial: Driver Short
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact Support RMA. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x7F · Commercial
Driver Short
Commercial three-phase inverters: Driver Short.
Product fit · Unknown
Show field stepsHide field steps for 8x7F · Commercial: Driver Short
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact Support RMA. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x80 · Commercial
Balancer Fault
Commercial three-phase inverters: Balancer Fault.
Product fit · Unknown
Show field stepsHide field steps for 8x80 · Commercial: Balancer Fault
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact Support RMA. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x81 · Commercial
RCD Over Current
Commercial three-phase inverters: RCD Over Current.
Product fit · Unknown
Show field stepsHide field steps for 8x81 · Commercial: RCD Over Current
Product fit · Unknown
Safe checks now
Treat this as an electrical-safety event. Record the code and conditions, keep clear of the inverter and its wiring, and do not reset the unit or operate isolators; contact your installer promptly.
Installer remedy
The guide's documented step for this code: Contact Support RMA. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x82 · Commercial
EVENT_NC_TZ
Commercial three-phase inverters: EVENT_NC_TZ.
Product fit · Unknown
Show field stepsHide field steps for 8x82 · Commercial: EVENT_NC_TZ
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact Support RMA. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x83 · Commercial
Global Fault
Commercial three-phase inverters: Global Fault.
Product fit · Unknown
Show field stepsHide field steps for 8x83 · Commercial: Global Fault
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact Support RMA. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x87 · Commercial
The frequency measured on L1 is higher than the thresholds
Commercial three-phase inverters: The frequency measured on L1 is higher than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 8x87 · Commercial: The frequency measured on L1 is higher than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x88 · Commercial
The frequency measured on L2 is higher than the thresholds
Commercial three-phase inverters: The frequency measured on L2 is higher than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 8x88 · Commercial: The frequency measured on L2 is higher than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x89 · Commercial
The frequency measured on L3 is higher than the thresholds
Commercial three-phase inverters: The frequency measured on L3 is higher than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 8x89 · Commercial: The frequency measured on L3 is higher than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x8A · Commercial
The frequency measured on L1 is Lower than the thresholds
Commercial three-phase inverters: The frequency measured on L1 is Lower than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 8x8A · Commercial: The frequency measured on L1 is Lower than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x8B · Commercial
The frequency measured on L2 is lower than the thresholds
Commercial three-phase inverters: The frequency measured on L2 is lower than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 8x8B · Commercial: The frequency measured on L2 is lower than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x8C · Commercial
The frequency measured on L3 is lower than the thresholds
Commercial three-phase inverters: The frequency measured on L3 is lower than the thresholds.
Product fit · Unknown
Show field stepsHide field steps for 8x8C · Commercial: The frequency measured on L3 is lower than the thresholds
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Reselect country code · Verify AC frequency and voltages on site.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 32x0 · Synergy
WAKEUP
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text WAKEUP, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x1 · Synergy
LOCATION_ACQUIRING
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text LOCATION_ACQUIRING, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x2 · Synergy
SPD_ENABLED
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text SPD_ENABLED, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x3 · Synergy
BATTERY_CONNECTED
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text BATTERY_CONNECTED, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x4 · Synergy
BATTERY_DISCONNECTED
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text BATTERY_DISCONNECTED, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x5 · Synergy
PD_EVENT
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text PD_EVENT, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x6 · Synergy
PID_ACTIVATED
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text PID_ACTIVATED, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x7 · Synergy
PID_DEACTIVATED
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text PID_DEACTIVATED, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x8 · Synergy
ERROR_PID_DISCHARGE
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text ERROR_PID_DISCHARGE, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x9 · Synergy
ERROR_PID_NO_DC_READ
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text ERROR_PID_NO_DC_READ, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32xA · Synergy
DC_SWITCH_TOGGLE
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text DC_SWITCH_TOGGLE, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32xB · Synergy
ERROR_PID_OUT_V_DONT_RISE
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text ERROR_PID_OUT_V_DONT_RISE, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32xC · Synergy
ERROR_PID_NIGHT_OVER_VOLTAGE
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text ERROR_PID_NIGHT_OVER_VOLTAGE, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32xD · Synergy
ERROR_PID_NIGHT_UNDER_VOLTAGE
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text ERROR_PID_NIGHT_UNDER_VOLTAGE, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32xE · Synergy
WAKEUP_NUMBER_OF_RESET
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text WAKEUP_NUMBER_OF_RESET, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32xF · Synergy
APP_UPGRADE_FAIL
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text APP_UPGRADE_FAIL, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x10 · Synergy
ERROR_SPD_DC_LEFT_TRIGGERED
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text ERROR_SPD_DC_LEFT_TRIGGERED, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x11 · Synergy
ERROR_SPD_DC_CENTER_TRIGGERED
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text ERROR_SPD_DC_CENTER_TRIGGERED, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x12 · Synergy
ERROR_SPD_DC_RIGHT_TRIGGERED
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text ERROR_SPD_DC_RIGHT_TRIGGERED, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x13 · Synergy
ERROR_SPD_AC_TRIGGERED
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text ERROR_SPD_AC_TRIGGERED, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x14 · Synergy
TEMPRATURE_DC_P_LEFT_WARNING_START
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text TEMPRATURE_DC_P_LEFT_WARNING_START, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x15 · Synergy
TEMPRATURE_DC_P_CENTER_WARNING_START
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text TEMPRATURE_DC_P_CENTER_WARNING_START, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x16 · Synergy
TEMPRATURE_DC_P_RIGHT_WARNING_START
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text TEMPRATURE_DC_P_RIGHT_WARNING_START, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x17 · Synergy
TEMPRATURE_DC_P_LEFT_CRITICAL_START
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text TEMPRATURE_DC_P_LEFT_CRITICAL_START, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x18 · Synergy
TEMPRATURE_DC_P_CENTER_CRITICAL_START
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text TEMPRATURE_DC_P_CENTER_CRITICAL_START, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x19 · Synergy
TEMPRATURE_DC_P_RIGHT_CRITICAL_START
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text TEMPRATURE_DC_P_RIGHT_CRITICAL_START, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x1A · Synergy
TEMPRATURE_DC_P_LEFT_WARNING_STOP
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text TEMPRATURE_DC_P_LEFT_WARNING_STOP, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x1B · Synergy
TEMPRATURE_DC_P_CENTER_WARNING_STOP
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text TEMPRATURE_DC_P_CENTER_WARNING_STOP, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x1C · Synergy
TEMPRATURE_DC_P_RIGHT_WARNING_STOP
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text TEMPRATURE_DC_P_RIGHT_WARNING_STOP, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x1D · Synergy
TEMPRATURE_DC_N_LEFT_WARNING_START
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text TEMPRATURE_DC_N_LEFT_WARNING_START, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x1E · Synergy
TEMPRATURE_DC_N_CENTER_WARNING_START
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text TEMPRATURE_DC_N_CENTER_WARNING_START, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x1F · Synergy
TEMPRATURE_DC_N_RIGHT_WARNING_START
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text TEMPRATURE_DC_N_RIGHT_WARNING_START, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x20 · Synergy
TEMPRATURE_DC_N_LEFT_CRITICAL_START
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text TEMPRATURE_DC_N_LEFT_CRITICAL_START, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x21 · Synergy
TEMPRATURE_DC_N_CENTER_CRITICAL_START
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text TEMPRATURE_DC_N_CENTER_CRITICAL_START, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x22 · Synergy
TEMPRATURE_DC_N_RIGHT_CRITICAL_START
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text TEMPRATURE_DC_N_RIGHT_CRITICAL_START, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x23 · Synergy
TEMPRATURE_DC_N_LEFT_WARNING_STOP
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text TEMPRATURE_DC_N_LEFT_WARNING_STOP, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x24 · Synergy
TEMPRATURE_DC_N_CENTER_WARNING_STOP
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text TEMPRATURE_DC_N_CENTER_WARNING_STOP, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x25 · Synergy
TEMPRATURE_DC_N_RIGHT_WARNING_STOP
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text TEMPRATURE_DC_N_RIGHT_WARNING_STOP, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x26 · Synergy
TEMPRATURE_AC_L1_WARNING_START
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text TEMPRATURE_AC_L1_WARNING_START, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x27 · Synergy
TEMPRATURE_AC_L2_WARNING_START
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text TEMPRATURE_AC_L2_WARNING_START, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x28 · Synergy
TEMPRATURE_AC_L3_WARNING_START
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text TEMPRATURE_AC_L3_WARNING_START, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x29 · Synergy
EVENT_TEMPRATURE_AMB_WARNING_START
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_TEMPRATURE_AMB_WARNING_START, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x2A · Synergy
TEMPRATURE_AC_L1_CRITICAL_START
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text TEMPRATURE_AC_L1_CRITICAL_START, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x2B · Synergy
TEMPRATURE_AC_L2_CRITICAL_START
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text TEMPRATURE_AC_L2_CRITICAL_START, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x2C · Synergy
TEMPRATURE_AC_L3_CRITICAL_START
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text TEMPRATURE_AC_L3_CRITICAL_START, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x2D · Synergy
EVENT_TEMPRATURE_AMB_CRITICAL_START
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_TEMPRATURE_AMB_CRITICAL_START, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x2E · Synergy
TEMPRATURE_AC_L1_WARNING_STOP
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text TEMPRATURE_AC_L1_WARNING_STOP, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x2F · Synergy
TEMPRATURE_AC_L2_WARNING_STOP
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text TEMPRATURE_AC_L2_WARNING_STOP, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x30 · Synergy
TEMPRATURE_AC_L3_WARNING_STOP
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text TEMPRATURE_AC_L3_WARNING_STOP, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x31 · Synergy
EVENT_TEMPRATURE_AMB_WARNING_STOP
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_TEMPRATURE_AMB_WARNING_STOP, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x32 · Synergy
EVENT_FAN_LOW_RPM_ERROR
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_FAN_LOW_RPM_ERROR, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x33 · Synergy
EVENT_FAN_HIGH_RPM_ERROR
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_FAN_HIGH_RPM_ERROR, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x34 · Synergy
EVENT_ABS_TEMPRATURE_DC_P_LEFT_CRITICAL_START
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_ABS_TEMPRATURE_DC_P_LEFT_CRITICAL_START, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x35 · Synergy
EVENT_ABS_TEMPRATURE_DC_P_CENTER_CRITICAL_START
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_ABS_TEMPRATURE_DC_P_CENTER_CRITICAL_START, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x36 · Synergy
EVENT_ABS_TEMPRATURE_DC_P_RIGHT_CRITICAL_START
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_ABS_TEMPRATURE_DC_P_RIGHT_CRITICAL_START, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x37 · Synergy
EVENT_ABS_TEMPRATURE_DC_P_LEFT_WARNING_STOP
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_ABS_TEMPRATURE_DC_P_LEFT_WARNING_STOP, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x38 · Synergy
EVENT_ABS_TEMPRATURE_DC_P_CENTER_WARNING_STOP
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_ABS_TEMPRATURE_DC_P_CENTER_WARNING_STOP, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x39 · Synergy
EVENT_ABS_TEMPRATURE_DC_P_RIGHT_WARNING_STOP
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_ABS_TEMPRATURE_DC_P_RIGHT_WARNING_STOP, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x3A · Synergy
EVENT_ABS_TEMPRATURE_DC_N_LEFT_CRITICAL_START
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_ABS_TEMPRATURE_DC_N_LEFT_CRITICAL_START, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x3B · Synergy
EVENT_ABS_TEMPRATURE_DC_N_CENTER_CRITICAL_START
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_ABS_TEMPRATURE_DC_N_CENTER_CRITICAL_START, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x3C · Synergy
EVENT_ABS_TEMPRATURE_DC_N_RIGHT_CRITICAL_START
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_ABS_TEMPRATURE_DC_N_RIGHT_CRITICAL_START, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x3D · Synergy
EVENT_ABS_TEMPRATURE_DC_N_LEFT_WARNING_STOP
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_ABS_TEMPRATURE_DC_N_LEFT_WARNING_STOP, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x3E · Synergy
EVENT_ABS_TEMPRATURE_DC_N_CENTER_WARNING_STOP
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_ABS_TEMPRATURE_DC_N_CENTER_WARNING_STOP, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x3F · Synergy
EVENT_ABS_TEMPRATURE_DC_N_RIGHT_WARNING_STOP
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_ABS_TEMPRATURE_DC_N_RIGHT_WARNING_STOP, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x40 · Synergy
EVENT_ABS_TEMPRATURE_AC_L1_CRITICAL_START
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_ABS_TEMPRATURE_AC_L1_CRITICAL_START, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x41 · Synergy
EVENT_ABS_TEMPRATURE_AC_L2_CRITICAL_START
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_ABS_TEMPRATURE_AC_L2_CRITICAL_START, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x42 · Synergy
EVENT_ABS_TEMPRATURE_AC_L3_CRITICAL_START
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_ABS_TEMPRATURE_AC_L3_CRITICAL_START, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x43 · Synergy
EVENT_ABS_TEMPRATURE_AC_L1_WARNING_STOP
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_ABS_TEMPRATURE_AC_L1_WARNING_STOP, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x44 · Synergy
EVENT_ABS_TEMPRATURE_AC_L2_WARNING_STOP
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_ABS_TEMPRATURE_AC_L2_WARNING_STOP, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x45 · Synergy
EVENT_ABS_TEMPRATURE_AC_L3_WARNING_STOP
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_ABS_TEMPRATURE_AC_L3_WARNING_STOP, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x46 · Synergy
EVENT_SPD_DC_LEFT_ENABLED
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_SPD_DC_LEFT_ENABLED, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x47 · Synergy
EVENT_SPD_DC_CENTER_ENABLED
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_SPD_DC_CENTER_ENABLED, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x48 · Synergy
EVENT_SPD_DC_RIGHT_ENABLED
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_SPD_DC_RIGHT_ENABLED, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x49 · Synergy
EVENT_SPD_AC_ENABLED
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_SPD_AC_ENABLED, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x4A · Synergy
EVENT_TEMPRATURE_DC_P_LEFT_LOCK
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_TEMPRATURE_DC_P_LEFT_LOCK, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x4B · Synergy
EVENT_TEMPRATURE_DC_P_CENTER_LOCK
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_TEMPRATURE_DC_P_CENTER_LOCK, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x4C · Synergy
EVENT_TEMPRATURE_DC_P_RIGHT_LOCK
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_TEMPRATURE_DC_P_RIGHT_LOCK, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x4D · Synergy
EVENT_TEMPRATURE_DC_N_LEFT_LOCK
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_TEMPRATURE_DC_N_LEFT_LOCK, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x4E · Synergy
EVENT_TEMPRATURE_DC_N_CENTER_LOCK
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_TEMPRATURE_DC_N_CENTER_LOCK, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x4F · Synergy
EVENT_TEMPRATURE_DC_N_RIGHT_LOCK
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_TEMPRATURE_DC_N_RIGHT_LOCK, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x50 · Synergy
EVENT_TEMPRATURE_AC_L1_LOCK
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_TEMPRATURE_AC_L1_LOCK, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x51 · Synergy
EVENT_TEMPRATURE_AC_L2_LOCK
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_TEMPRATURE_AC_L2_LOCK, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x52 · Synergy
EVENT_TEMPRATURE_AC_L3_LOCK
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_TEMPRATURE_AC_L3_LOCK, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x53 · Synergy
EVENT_POWER_OFF
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_POWER_OFF, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x54 · Synergy
EVENT_WATCHDOG
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_WATCHDOG, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x55 · Synergy
EVENT_HARD_FAULT
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_HARD_FAULT, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x56 · Synergy
EVENT_ASSERT
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_ASSERT, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x57 · Synergy
EVENT_STACK_OVERFLOW
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_STACK_OVERFLOW, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x58 · Synergy
EVENT_HEAP_OVERFLOW
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_HEAP_OVERFLOW, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x59 · Synergy
EVENT_APPLICATION_RESET
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_APPLICATION_RESET, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x5A · Synergy
EVENT_TEMPRATURE_DC_P_LEFT_NTC_DISABLE
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_TEMPRATURE_DC_P_LEFT_NTC_DISABLE, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x5B · Synergy
EVENT_TEMPRATURE_DC_P_CENTER_NTC_DISABLE
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_TEMPRATURE_DC_P_CENTER_NTC_DISABLE, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x5C · Synergy
EVENT_TEMPRATURE_DC_P_RIGHT_NTC_DISABLE
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_TEMPRATURE_DC_P_RIGHT_NTC_DISABLE, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x5D · Synergy
EVENT_TEMPRATURE_DC_N_LEFT_NTC_DISABLE
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_TEMPRATURE_DC_N_LEFT_NTC_DISABLE, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x5E · Synergy
EVENT_TEMPRATURE_DC_N_CENTER_NTC_DISABLE
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_TEMPRATURE_DC_N_CENTER_NTC_DISABLE, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x5F · Synergy
EVENT_TEMPRATURE_DC_N_RIGHT_NTC_DISABLE
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_TEMPRATURE_DC_N_RIGHT_NTC_DISABLE, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x60 · Synergy
EVENT_TEMPRATURE_AC_L1_NTC_DISABLE
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_TEMPRATURE_AC_L1_NTC_DISABLE, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x61 · Synergy
EVENT_TEMPRATURE_AC_L2_NTC_DISABLE
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_TEMPRATURE_AC_L2_NTC_DISABLE, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x62 · Synergy
EVENT_TEMPRATURE_AC_L3_NTC_DISABLE
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_TEMPRATURE_AC_L3_NTC_DISABLE, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 32x63 · Synergy
EVENT_TEMPRATURE_AMB_NTC_DISABLE
Commercial three-phase inverters with Synergy technology: the guide lists this code only as the event text EVENT_TEMPRATURE_AMB_NTC_DISABLE, with no description or troubleshooting of its own. Its stated instruction for that whole table is to contact SolarEdge Support for troubleshooting details.
- 33xD · TerraMax
The inverter fan is not working
TerraMax inverters: The inverter fan is not working.
Product fit · Unknown
Show field stepsHide field steps for 33xD · TerraMax: The inverter fan is not working
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Check the physical cable connection · Clean the fan · Replace the fan · If issue remains, contact the SolarEdge Support team.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 33x10 · TerraMax
Internal communication error
TerraMax inverters: Internal communication error.
Product fit · Unknown
Show field stepsHide field steps for 33x10 · TerraMax: Internal communication error
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact SolarEdge Support. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 33x14 · TerraMax
TerraMax™ PID Night
TerraMax inverters: TerraMax™ PID Night.
Product fit · Unknown
Show field stepsHide field steps for 33x14 · TerraMax: TerraMax™ PID Night
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact SolarEdge Support. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 33x19 · TerraMax
AC voltage surge
TerraMax inverters: AC voltage surge.
Product fit · Unknown
Show field stepsHide field steps for 33x19 · TerraMax: AC voltage surge
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: If the fault persists: · Check the AC connection to inverter. · Verify that the inverter is set to the correct country. · Check with the grid operator if a large surge source or irregular load exists near the site. · Verify that the output wire size matches the distance between the inverter and the location of the grid connection. · Use a larger gauge wire for the AC output. · Refer to the AC Wiring Application Note at http://www.solaredge.us/files/pdfs/application-note-recommended-wiring.pdf.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 33x1A · TerraMax
AC voltage surge
TerraMax inverters: AC voltage surge.
Product fit · Unknown
Show field stepsHide field steps for 33x1A · TerraMax: AC voltage surge
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: If the fault persists: · Check the AC connection to inverter. · Verify that the inverter is set to the correct country. · Check with the grid operator if a large surge source or irregular load exists near the site. · Verify that the output wire size matches the distance between the inverter and the location of the grid connection. · Use a larger gauge wire for the AC output. · Refer to the AC Wiring Application Note at http://www.solaredge.us/files/pdfs/application-note-recommended-wiring.pdf.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 33x1B · TerraMax
AC voltage surge
TerraMax inverters: AC voltage surge.
Product fit · Unknown
Show field stepsHide field steps for 33x1B · TerraMax: AC voltage surge
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Check the AC connection to inverter. · Verify that the inverter is set to the correct country. · Check with the grid operator if a large surge source or irregular load exists near the site. · Verify that the output wire size matches the distance between the inverter and the location of the grid connection. · Use a larger gauge wire for the AC output. · Refer to the AC Wiring Application Note at http://www.solaredge.us/files/pdfs/application-note-recommended-wiring.pdf.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 33x1C · TerraMax
Line voltage is low
TerraMax inverters: Line voltage is low.
Product fit · Unknown
Show field stepsHide field steps for 33x1C · TerraMax: Line voltage is low
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Check the AC connection to inverter. · Verify that the inverter is set to the correct country. · Check with the grid operator if a large surge source or irregular load exists near the site. · Verify that the output wire size matches the distance between the inverter and the location of the grid connection. · Use a larger gauge wire for the AC output. · Refer to the AC Wiring Application Note at http://www.solaredge.us/files/pdfs/application-note-recommended-wiring.pdf.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 33x1D · TerraMax
Line voltage is low
TerraMax inverters: Line voltage is low.
Product fit · Unknown
Show field stepsHide field steps for 33x1D · TerraMax: Line voltage is low
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Check the AC connection to inverter. · Verify that the inverter is set to the correct country. · Check with the grid operator if a large surge source or irregular load exists near the site. · Verify that the output wire size matches the distance between the inverter and the location of the grid connection. · Use a larger gauge wire for the AC output. · Refer to the AC Wiring Application Note at http://www.solaredge.us/files/pdfs/application-note-recommended-wiring.pdf.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x1E · TerraMax
Line voltage is low
TerraMax inverters: Line voltage is low.
Product fit · Unknown
Show field stepsHide field steps for 8x1E · TerraMax: Line voltage is low
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Check the AC connection to inverter. · Verify that the inverter is set to the correct country. · Check with the grid operator if a large surge source or irregular load exists near the site. · Verify that the output wire size matches the distance between the inverter and the location of the grid connection. · Use a larger gauge wire for the AC output. · Refer to the AC Wiring Application Note at http://www.solaredge.us/files/pdfs/application-note-recommended-wiring.pdf.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 33x1F · TerraMax
AC voltage surge
TerraMax inverters: AC voltage surge.
Product fit · Unknown
Show field stepsHide field steps for 33x1F · TerraMax: AC voltage surge
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Check the AC connection to inverter. · Verify that the inverter is set to the correct country. · Check with the grid operator if a large surge source or irregular load exists near the site. · Verify that the output wire size matches the distance between the inverter and the location of the grid connection. · Use a larger gauge wire for the AC output. · Refer to the AC Wiring Application Note at http://www.solaredge.us/files/pdfs/application-note-recommended-wiring.pdf.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 33x20 · TerraMax
AC voltage surge
TerraMax inverters: AC voltage surge.
Product fit · Unknown
Show field stepsHide field steps for 33x20 · TerraMax: AC voltage surge
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Check the AC connection to inverter. · Verify that the inverter is set to the correct country. · Check with the grid operator if a large surge source or irregular load exists near the site. · Verify that the output wire size matches the distance between the inverter and the location of the grid connection. · Use a larger gauge wire for the AC output. · Refer to the AC Wiring Application Note at http://www.solaredge.us/files/pdfs/application-note-recommended-wiring.pdf.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 33x21 · TerraMax
AC voltage surge
TerraMax inverters: AC voltage surge.
Product fit · Unknown
Show field stepsHide field steps for 33x21 · TerraMax: AC voltage surge
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Check the AC connection to inverter. · Verify that the inverter is set to the correct country. · Check with the grid operator if a large surge source or irregular load exists near the site. · Verify that the output wire size matches the distance between the inverter and the location of the grid connection. · Use a larger gauge wire for the AC output. · Refer to the AC Wiring Application Note at http://www.solaredge.us/files/pdfs/application-note-recommended-wiring.pdf.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 8x22 · TerraMax
Line voltage is low
TerraMax inverters: Line voltage is low.
Product fit · Unknown
Show field stepsHide field steps for 8x22 · TerraMax: Line voltage is low
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Check the AC connection to inverter. · Verify that the inverter is set to the correct country. · Check with the grid operator if a large surge source or irregular load exists near the site. · Verify that the output wire size matches the distance between the inverter and the location of the grid connection. · Use a larger gauge wire for the AC output. · Refer to the AC Wiring Application Note at http://www.solaredge.us/files/pdfs/application-note-recommended-wiring.pdf.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 33x23 · TerraMax
Line voltage is low
TerraMax inverters: Line voltage is low.
Product fit · Unknown
Show field stepsHide field steps for 33x23 · TerraMax: Line voltage is low
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Check the AC connection to inverter. · Verify that the inverter is set to the correct country. · Check with the grid operator if a large surge source or irregular load exists near the site. · Verify that the output wire size matches the distance between the inverter and the location of the grid connection. · Use a larger gauge wire for the AC output. · Refer to the AC Wiring Application Note at http://www.solaredge.us/files/pdfs/application-note-recommended-wiring.pdf.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 33x24 · TerraMax
Line voltage is low
TerraMax inverters: Line voltage is low.
Product fit · Unknown
Show field stepsHide field steps for 33x24 · TerraMax: Line voltage is low
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Check the AC connection to inverter. · Verify that the inverter is set to the correct country. · Check with the grid operator if a large surge source or irregular load exists near the site. · Verify that the output wire size matches the distance between the inverter and the location of the grid connection. · Use a larger gauge wire for the AC output. · Refer to the AC Wiring Application Note at http://www.solaredge.us/files/pdfs/application-note-recommended-wiring.pdf.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 33x25 · TerraMax
AC voltage surge
TerraMax inverters: AC voltage surge.
Product fit · Unknown
Show field stepsHide field steps for 33x25 · TerraMax: AC voltage surge
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Check the AC connection to inverter. · Verify that the inverter is set to the correct country. · Check with the grid operator if a large surge source or irregular load exists near the site. · Verify that the output wire size matches the distance between the inverter and the location of the grid connection. · Use a larger gauge wire for the AC output. · Refer to the AC Wiring Application Note at http://www.solaredge.us/files/pdfs/application-note-recommended-wiring.pdf.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 33x26 · TerraMax
Line voltage is low
TerraMax inverters: Line voltage is low.
Product fit · Unknown
Show field stepsHide field steps for 33x26 · TerraMax: Line voltage is low
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Check the AC connection to inverter. · Verify that the inverter is set to the correct country. · Check with the grid operator if a large surge source or irregular load exists near the site. · Verify that the output wire size matches the distance between the inverter and the location of the grid connection. · Use a larger gauge wire for the AC output. · Refer to the AC Wiring Application Note at http://www.solaredge.us/files/pdfs/application-note-recommended-wiring.pdf.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 33x36 · TerraMax
Anti islanding
TerraMax inverters: Anti islanding.
Product fit · Unknown
Show field stepsHide field steps for 33x36 · TerraMax: Anti islanding
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact SolarEdge Support. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 33x38 · TerraMax
Anti islanding
TerraMax inverters: Anti islanding.
Product fit · Unknown
Show field stepsHide field steps for 33x38 · TerraMax: Anti islanding
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact SolarEdge Support. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 33x56 · TerraMax
Power train error
TerraMax inverters: Power train error.
Product fit · Unknown
Show field stepsHide field steps for 33x56 · TerraMax: Power train error
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact SolarEdge Support. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 33x58 · TerraMax
Isolation Test
TerraMax inverters: Isolation Test.
Product fit · Unknown
Show field stepsHide field steps for 33x58 · TerraMax: Isolation Test
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact SolarEdge Support. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 33x59 · TerraMax
Relay Test
TerraMax inverters: Relay Test.
Product fit · Unknown
Show field stepsHide field steps for 33x59 · TerraMax: Relay Test
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact SolarEdge Support. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 33xB8 · TerraMax
Pairing Error
TerraMax inverters: Pairing Error.
Product fit · Unknown
Show field stepsHide field steps for 33xB8 · TerraMax: Pairing Error
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Re-initiate pairing process. · If the issue persists, contact SolarEdge Support.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 33xB9 · TerraMax
Locked
TerraMax inverters: Locked.
Product fit · Unknown
Show field stepsHide field steps for 33xB9 · TerraMax: Locked
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: Contact SolarEdge Support. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 33x86 · TerraMax
The DC SPD is not functioning
TerraMax inverters: The DC SPD is not functioning.
Product fit · Unknown
Show field stepsHide field steps for 33x86 · TerraMax: The DC SPD is not functioning
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Validate that the DC SPD board is installed correctly as instructed in the installation guide. · If the issue persists, it is possible that the DC SPD board absorbed an electrical surge. In this case, the board should be replaced. · Upon remediation of the failure, the event 33XDB is received.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 33x85 · TerraMax
The AC SPD is not functioning
TerraMax inverters: The AC SPD is not functioning.
Product fit · Unknown
Show field stepsHide field steps for 33x85 · TerraMax: The AC SPD is not functioning
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Validate that the AC SPD board is installed correctly as instructed in the installation guide. · If the issue persists, it is possible that the AC SPD board absorbed an electrical surge. In this case, the board should be replaced. · Upon remediation of the failure, the event 33XDA is received.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 33x9C · TerraMax
The temperature of the Y of the AC terminal block is high/critical
TerraMax inverters: The temperature of the Y of the AC terminal block is high/critical. Y = L1 conductor, L2 conductor, L3 conductor.
Product fit · Unknown
Show field stepsHide field steps for 33x9C · TerraMax: The temperature of the Y of the AC terminal block is high/critical
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Validate that the AC lugs are properly installed. · Validate that the torque of the screws in the AC terminal block is set to 35 Nm. · If the issue persists, contact the SolarEdge Support team.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- 33x47 · TerraMax
Inverter temperature is critical, the production has stopped
TerraMax inverters: Inverter temperature is critical, the production has stopped.
Product fit · Unknown
Show field stepsHide field steps for 33x47 · TerraMax: Inverter temperature is critical, the production has stopped
Product fit · Unknown
Safe checks now
Record the exact code, inverter model and time. Do not repeatedly restart the inverter, change settings or open equipment; contact your installer if the code remains.
Installer remedy
The guide's documented step for this code: · Check that the inverter has been installed according to the instructions in the installation guide. · If the issue persists, contact the SolarEdge Support team.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- WARNING 1
Fan failure
The guide's warning-messages list gives the cause for this warning as "Fan Failure".
Product fit · Unknown
Show field stepsHide field steps for WARNING 1: Fan failure
Product fit · Unknown
Safe checks now
Record the warning and contact your installer. Do not open the inverter or attempt to inspect, clean or replace the fan yourself.
Installer remedy
The guide's documented step for this warning: Contact Support. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- WARNING 2
Fan failure
The guide's warning-messages list gives the cause for this warning as "Fan Failure".
Product fit · Unknown
Show field stepsHide field steps for WARNING 2: Fan failure
Product fit · Unknown
Safe checks now
Record the warning and contact your installer. Do not open the inverter or attempt to inspect, clean or replace the fan yourself.
Installer remedy
The guide's documented step for this warning: Contact Support. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- WARNING 3
Fan failure
The guide's warning-messages list gives the cause for this warning as "Fan Failure".
Product fit · Unknown
Show field stepsHide field steps for WARNING 3: Fan failure
Product fit · Unknown
Safe checks now
Record the warning and contact your installer. Do not open the inverter or attempt to inspect, clean or replace the fan yourself.
Installer remedy
The guide's documented step for this warning: Contact Support. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- WARNING 4
Fan failure
The guide's warning-messages list gives the cause for this warning as "Fan Failure".
Product fit · Unknown
Show field stepsHide field steps for WARNING 4: Fan failure
Product fit · Unknown
Safe checks now
Record the warning and contact your installer. Do not open the inverter or attempt to inspect, clean or replace the fan yourself.
Installer remedy
The guide's documented step for this warning: Contact Support. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- WARNING 5
Menu accessed during production
The guide's warning-messages list gives the cause for this warning as "Raised when trying to access Menus during production".
Product fit · Unknown
Show field stepsHide field steps for WARNING 5: Menu accessed during production
Product fit · Unknown
Safe checks now
Record the warning and contact your installer. The action for this one is a control step on the inverter itself, which is an installer task rather than an owner task.
Installer remedy
The guide's documented step for this warning: Turn Toggle Switch to OFF. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- WARNING 6
Fan failure
The guide's warning-messages list gives the cause for this warning as "Fan Failure".
Product fit · Unknown
Show field stepsHide field steps for WARNING 6: Fan failure
Product fit · Unknown
Safe checks now
Record the warning and contact your installer. Do not open the inverter or attempt to inspect, clean or replace the fan yourself.
Installer remedy
The guide's documented step for this warning: Contact Support. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
- WARNING 7
Fan failure
The guide's warning-messages list gives the cause for this warning as "Fan Failure".
Product fit · Unknown
Show field stepsHide field steps for WARNING 7: Fan failure
Product fit · Unknown
Safe checks now
Record the warning and contact your installer. Do not open the inverter or attempt to inspect, clean or replace the fan yourself.
Installer remedy
The guide's documented step for this warning: Contact Support. Preserve the event evidence and escalate rather than improvising a field procedure beyond what the guide states.
Remedy sourceSolarEdge error-codes guide
Manufacturer / escalation handoff
Sources
Best next action
Did this help you move the job forward?
Frequently asked
- Where do these SolarEdge fault codes come from?
- Compiled from publicly available SolarEdge inverter and battery documentation and field references, then rewritten for the trade. Wattbench is independent and not affiliated with SolarEdge.
- Which of these can I clear on site?
- Some clear on their own once grid or environmental conditions return to normal. Anything involving DC isolation, AC switching, wiring or opening the unit is licensed electrical work. Isolate safely, follow AS/NZS 5033 and AS/NZS 3000 procedure and use appropriate PPE before touching a live system.
- The exact code isn't listed. Why not?
- Firmware and model variants differ, and manufacturers revise their code tables. We document the most common ones; for a variant that isn't here, check the unit's current manual or the manufacturer's service portal.
- How current is this reference?
- This reference was last reviewed on 26 August 2026. We revise entries when the underlying manufacturer documentation changes.
Other fault libraries
Fronius Error Codes
Common Fronius State codes from the current Symo / Eco operating instructions, explained for owners and installers.
29 codesInverter Fault LibrarySMA Error Codes
SMA event-code reference with source-linked remedies for Australian Sunny Tripower X models and explicit boundaries around older Sunny Boy and mixed-family records.
25 codesInverter Fault LibrarySolaX Inverter Error Codes
Current X1/X3-Hybrid G4 faults with source-linked remedies, kept separate from remedy-blank legacy X-Hybrid C1 and DM9000 entries.
30 codes