wattbench
Microinverter Fault Library

Hoymiles Microinverter Error Codes

Current official HMS/HMT alarms and remedies, separated from community-only OpenDTU decoder entries that remain remedy-blank.

Sources listedReviewed August 2026Source: Official current HMS/HMT manuals and separately labelled community decoder referencesOur methodology

30 of 30 codes

About this fault librarySources · scope

Hoymiles alarm codes vary by microinverter family and firmware. Codes 121 and 124–149 now resolve to official current HMS/HMT troubleshooting tables; code 124 was upgraded from community-only after recovery in the current HMS manual. Codes 11–73 and 9000 remain search aids from the community-maintained OpenDTU decoder because no matching official instruction was found; they stay explicitly remedy-blank. The cited manuals are global family references and do not establish the installed Australian variant or firmware. Confirm the exact model in S-Miles before acting. Safety note: owners should record the code and app status. AC/DC disconnection, measurements, wiring, connectors and protection settings are qualified-installer tasks.

Key takeaways
  • 30 Hoymiles (HM / MI / HMS / HMT-series microinverters and the DTU monitoring gateway) fault and alarm codes, documented for the trade.
  • Compiled from published documentation and field references; Wattbench is independent and not affiliated with Hoymiles (HM / MI / HMS / HMT-series microinverters and the DTU monitoring gateway).
  • Codes involving DC/AC isolation, wiring or opening the unit are licensed electrical work. Isolate safely and follow AS/NZS procedure.

Resolution text is manufacturer/service context, not permission for an owner to perform electrical work. Stop at visible observations unless the exact product instructions identify an owner control. Isolation, configuration, testing, opening equipment and wiring are for an appropriately licensed worker and, where required, an SAA-accredited person. Where a card says Product fit is unknown, treat it as brand-level guidance and confirm the exact model, role, regional variant, firmware and current manual before acting.

  • 11

    Grid voltage surge

    Community decoder: a sudden grid-voltage surge was reported. This label was not found in the reviewed manufacturer manuals.

  • 12

    Grid voltage sharp drop

    Community decoder: a sudden grid-voltage drop was reported. This label was not found in the reviewed manufacturer manuals.

  • 13

    Grid frequency mutation

    Community decoder: an abrupt grid-frequency change was reported. This label was not found in the reviewed manufacturer manuals.

  • 14

    Grid phase mutation

    Community decoder: an abrupt grid-phase change was reported. This label was not found in the reviewed manufacturer manuals.

  • 36

    INV overvoltage or overcurrent

    Community decoder: protection operated in the inverter stage. This label was not found in the reviewed manufacturer manuals.

  • 46

    FB overvoltage

    Community decoder: overvoltage in the flyback stage. This label was not found in the reviewed manufacturer manuals.

  • 47

    FB overcurrent

    Community decoder: overcurrent in the flyback stage. This label was not found in the reviewed manufacturer manuals.

  • 48

    FB clamp overvoltage

    Community decoder: flyback-clamp overvoltage. This label was not found in the reviewed manufacturer manuals.

  • 49

    FB clamp overvoltage

    Community decoder: a second flyback-clamp overvoltage event. This label was not found in the reviewed manufacturer manuals.

  • 71

    Grid overvoltage load reduction (VW) enabled

    Community decoder: Volt–Watt load reduction is active. This label was not found in the reviewed manufacturer manuals.

  • 72

    Grid overfrequency load reduction (FW) enabled

    Community decoder: Frequency–Watt load reduction is active. This label was not found in the reviewed manufacturer manuals.

  • 73

    Over-temperature load reduction (TW) enabled

    Community decoder: temperature-based load reduction is active. This label was not found in the reviewed manufacturer manuals.

  • 121

    Over temperature protection

    The microinverter has shut down on over-temperature protection because internal/ambient temperature exceeded safe limits.

    Product fit · Confirmed · 2 documented families

    Show field steps for 121: Over temperature protection

    Product fit

    • HMS-300/350/400/450/500-1T · Role not confirmed

      Confirmed · AU/region not confirmed · Firmware not documented

    • HMT-1600/1800/2000-4T LA · Role not confirmed

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    From a safe position, keep the array area unobstructed and record unusual heat or poor airflow. Do not go onto the roof; contact the installer if the alarm remains in normal conditions.

    Installer remedy

    Check the microinverter installation ventilation and ambient conditions against the exact HMS/HMT manual. Improve heat dissipation where required and escalate if suitable conditions do not clear the alarm.

    Remedy sourceHMS 1T manualHMT manual

    Manufacturer / escalation handoff
  • 124

    Shut down by remote control

    Current HMS family: the microinverter reports a remote shutdown command. The official handling path checks zero-export management and whether the unit was manually shut down.

    Product fit · Confirmed · HMS-300/350/400/450/500-1T

    Show field steps for 124: Shut down by remote control

    Product fit

    • HMS-300/350/400/450/500-1T · Role not confirmed

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record that remote shutdown is reported and check only the visible S-Miles status. Do not override zero-export controls or operate equipment; contact the installer if the command is unexpected.

    Installer remedy

    Check zero-export management and the manual shutdown state using the HMS manual. Correct the command source rather than treating code 124 as an internal hardware fault, then escalate if it persists.

    Remedy sourceHMS 1T manual

    Manufacturer / escalation handoff
  • 125

    Grid configuration parameter error

    The grid profile / grid configuration parameters loaded on the microinverter are incorrect or invalid.

    Product fit · Confirmed · 2 documented families

    Show field steps for 125: Grid configuration parameter error

    Product fit

    • HMS-300/350/400/450/500-1T · Role not confirmed

      Confirmed · AU/region not confirmed · Firmware not documented

    • HMT-1600/1800/2000-4T LA · Role not confirmed

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the code and app status. Do not change the grid profile, firmware or device assignment; contact the installer if the alarm is frequent or does not recover.

    Installer remedy

    Verify the exact model's grid configuration or firmware and the DTU communication path using the HMS/HMT manual. Use only Hoymiles-supplied files and escalate a recurring software event.

    Remedy sourceHMS 1T manualHMT manual

    Manufacturer / escalation handoff
  • 126

    Software error code 126

    Internal software/firmware error reported by the microinverter. Often transient.

    Product fit · Confirmed · 2 documented families

    Show field steps for 126: Software error code 126

    Product fit

    • HMS-300/350/400/450/500-1T · Role not confirmed

      Confirmed · AU/region not confirmed · Firmware not documented

    • HMT-1600/1800/2000-4T LA · Role not confirmed

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the code and app status. Do not change the grid profile, firmware or device assignment; contact the installer if the alarm is frequent or does not recover.

    Installer remedy

    Verify the exact model's grid configuration or firmware and the DTU communication path using the HMS/HMT manual. Use only Hoymiles-supplied files and escalate a recurring software event.

    Remedy sourceHMS 1T manualHMT manual

    Manufacturer / escalation handoff
  • 127

    Firmware error

    A firmware error was detected on the microinverter, typically related to a firmware version or failed upgrade.

    Product fit · Confirmed · 2 documented families

    Show field steps for 127: Firmware error

    Product fit

    • HMS-300/350/400/450/500-1T · Role not confirmed

      Confirmed · AU/region not confirmed · Firmware not documented

    • HMT-1600/1800/2000-4T LA · Role not confirmed

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the code and app status. Do not change the grid profile, firmware or device assignment; contact the installer if the alarm is frequent or does not recover.

    Installer remedy

    Verify the exact model's grid configuration or firmware and the DTU communication path using the HMS/HMT manual. Use only Hoymiles-supplied files and escalate a recurring software event.

    Remedy sourceHMS 1T manualHMT manual

    Manufacturer / escalation handoff
  • 128

    Software error code 128

    Internal software/firmware error reported by the microinverter. Often transient.

    Product fit · Confirmed · 2 documented families

    Show field steps for 128: Software error code 128

    Product fit

    • HMS-300/350/400/450/500-1T · Role not confirmed

      Confirmed · AU/region not confirmed · Firmware not documented

    • HMT-1600/1800/2000-4T LA · Role not confirmed

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the code and app status. Do not change the grid profile, firmware or device assignment; contact the installer if the alarm is frequent or does not recover.

    Installer remedy

    Verify the exact model's grid configuration or firmware and the DTU communication path using the HMS/HMT manual. Use only Hoymiles-supplied files and escalate a recurring software event.

    Remedy sourceHMS 1T manualHMT manual

    Manufacturer / escalation handoff
  • 129

    Software error code 129

    The manufacturer troubleshooting table identifies an internal software error.

    Product fit · Confirmed · 2 documented families

    Show field steps for 129: Software error code 129

    Product fit

    • HMS-300/350/400/450/500-1T · Role not confirmed

      Confirmed · AU/region not confirmed · Firmware not documented

    • HMT-1600/1800/2000-4T LA · Role not confirmed

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the code and app status. Do not change the grid profile, firmware or device assignment; contact the installer if the alarm is frequent or does not recover.

    Installer remedy

    Verify the exact model's grid configuration or firmware and the DTU communication path using the HMS/HMT manual. Use only Hoymiles-supplied files and escalate a recurring software event.

    Remedy sourceHMS 1T manualHMT manual

    Manufacturer / escalation handoff
  • 130

    Offline

    The microinverter is offline. The DTU cannot communicate with it / it is not reporting to the monitoring system.

    Product fit · Confirmed · 2 documented families

    Show field steps for 130: Offline

    Product fit

    • HMS-300/350/400/450/500-1T · Role not confirmed

      Confirmed · AU/region not confirmed · Firmware not documented

    • HMT-1600/1800/2000-4T LA · Role not confirmed

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Check the microinverter's last-report time in S-Miles and record which unit is offline. Do not operate solar switches or go onto the roof; contact the installer if it remains offline.

    Installer remedy

    Confirm the recorded serial number and separate DTU-to-cloud from DTU-to-microinverter communication using the exact HMS/HMT procedure. Correct the communication path before considering device replacement.

    Remedy sourceHMS 1T manualHMT manual

    Manufacturer / escalation handoff
  • 141

    Grid overvoltage

    AC grid voltage exceeded the upper protection limit, so the microinverter stopped feeding in.

    Product fit · Confirmed · 2 documented families

    Show field steps for 141: Grid overvoltage

    Product fit

    • HMS-300/350/400/450/500-1T · Role not confirmed

      Confirmed · AU/region not confirmed · Firmware not documented

    • HMT-1600/1800/2000-4T LA · Role not confirmed

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the alarm, time and whether the premises supply appears normal. It may recover when the grid returns to range; do not change grid limits and contact the installer if it repeats.

    Installer remedy

    Check the measured grid voltage, frequency or rate of change against the exact HMS/HMT profile. Obtain the local network operator's consent before any protection-limit change and escalate persistent supply abnormalities.

    Remedy sourceHMS 1T manualHMT manual

    Manufacturer / escalation handoff
  • 142

    10 min value grid overvoltage

    The 10-minute average grid voltage exceeded the allowed limit (sustained overvoltage protection).

    Product fit · Confirmed · 2 documented families

    Show field steps for 142: 10 min value grid overvoltage

    Product fit

    • HMS-300/350/400/450/500-1T · Role not confirmed

      Confirmed · AU/region not confirmed · Firmware not documented

    • HMT-1600/1800/2000-4T LA · Role not confirmed

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the alarm, time and whether the premises supply appears normal. It may recover when the grid returns to range; do not change grid limits and contact the installer if it repeats.

    Installer remedy

    Check the measured grid voltage, frequency or rate of change against the exact HMS/HMT profile. Obtain the local network operator's consent before any protection-limit change and escalate persistent supply abnormalities.

    Remedy sourceHMS 1T manualHMT manual

    Manufacturer / escalation handoff
  • 143

    Grid undervoltage

    AC grid voltage fell below the lower protection limit.

    Product fit · Confirmed · 2 documented families

    Show field steps for 143: Grid undervoltage

    Product fit

    • HMS-300/350/400/450/500-1T · Role not confirmed

      Confirmed · AU/region not confirmed · Firmware not documented

    • HMT-1600/1800/2000-4T LA · Role not confirmed

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the alarm, time and whether the premises supply appears normal. It may recover when the grid returns to range; do not change grid limits and contact the installer if it repeats.

    Installer remedy

    Check the measured grid voltage, frequency or rate of change against the exact HMS/HMT profile. Obtain the local network operator's consent before any protection-limit change and escalate persistent supply abnormalities.

    Remedy sourceHMS 1T manualHMT manual

    Manufacturer / escalation handoff
  • 144

    Grid overfrequency

    AC grid frequency exceeded the upper protection limit.

    Product fit · Confirmed · 2 documented families

    Show field steps for 144: Grid overfrequency

    Product fit

    • HMS-300/350/400/450/500-1T · Role not confirmed

      Confirmed · AU/region not confirmed · Firmware not documented

    • HMT-1600/1800/2000-4T LA · Role not confirmed

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the alarm, time and whether the premises supply appears normal. It may recover when the grid returns to range; do not change grid limits and contact the installer if it repeats.

    Installer remedy

    Check the measured grid voltage, frequency or rate of change against the exact HMS/HMT profile. Obtain the local network operator's consent before any protection-limit change and escalate persistent supply abnormalities.

    Remedy sourceHMS 1T manualHMT manual

    Manufacturer / escalation handoff
  • 145

    Grid underfrequency

    AC grid frequency fell below the lower protection limit.

    Product fit · Confirmed · 2 documented families

    Show field steps for 145: Grid underfrequency

    Product fit

    • HMS-300/350/400/450/500-1T · Role not confirmed

      Confirmed · AU/region not confirmed · Firmware not documented

    • HMT-1600/1800/2000-4T LA · Role not confirmed

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the alarm, time and whether the premises supply appears normal. It may recover when the grid returns to range; do not change grid limits and contact the installer if it repeats.

    Installer remedy

    Check the measured grid voltage, frequency or rate of change against the exact HMS/HMT profile. Obtain the local network operator's consent before any protection-limit change and escalate persistent supply abnormalities.

    Remedy sourceHMS 1T manualHMT manual

    Manufacturer / escalation handoff
  • 146

    Rapid grid frequency change rate

    The rate of change of grid frequency (ROCOF) exceeded the allowed limit.

    Product fit · Confirmed · 2 documented families

    Show field steps for 146: Rapid grid frequency change rate

    Product fit

    • HMS-300/350/400/450/500-1T · Role not confirmed

      Confirmed · AU/region not confirmed · Firmware not documented

    • HMT-1600/1800/2000-4T LA · Role not confirmed

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the alarm, time and whether the premises supply appears normal. It may recover when the grid returns to range; do not change grid limits and contact the installer if it repeats.

    Installer remedy

    Check the measured grid voltage, frequency or rate of change against the exact HMS/HMT profile. Obtain the local network operator's consent before any protection-limit change and escalate persistent supply abnormalities.

    Remedy sourceHMS 1T manualHMT manual

    Manufacturer / escalation handoff
  • 147

    Power grid outage

    The microinverter detected a grid outage.

    Product fit · Confirmed · 2 documented families

    Show field steps for 147: Power grid outage

    Product fit

    • HMS-300/350/400/450/500-1T · Role not confirmed

      Confirmed · AU/region not confirmed · Firmware not documented

    • HMT-1600/1800/2000-4T LA · Role not confirmed

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Confirm whether the premises has grid supply and record the alarm. Do not operate solar switches or rooftop equipment; contact the installer if normal supply is present but the alarm remains.

    Installer remedy

    Check the AC supply, connection and anti-islanding condition under the exact HMS/HMT procedure. Restore service only after a stable grid and sound AC connection are confirmed.

    Remedy sourceHMS 1T manualHMT manual

    Manufacturer / escalation handoff
  • 148

    Grid disconnection

    The microinverter detected disconnection from the grid (loss of AC connection).

    Product fit · Confirmed · 2 documented families

    Show field steps for 148: Grid disconnection

    Product fit

    • HMS-300/350/400/450/500-1T · Role not confirmed

      Confirmed · AU/region not confirmed · Firmware not documented

    • HMT-1600/1800/2000-4T LA · Role not confirmed

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Confirm whether the premises has grid supply and record the alarm. Do not operate solar switches or rooftop equipment; contact the installer if normal supply is present but the alarm remains.

    Installer remedy

    Check the AC supply, connection and anti-islanding condition under the exact HMS/HMT procedure. Restore service only after a stable grid and sound AC connection are confirmed.

    Remedy sourceHMS 1T manualHMT manual

    Manufacturer / escalation handoff
  • 149

    Island detected

    Anti-islanding protection tripped. The microinverter detected an islanding condition and disconnected for safety.

    Product fit · Confirmed · 2 documented families

    Show field steps for 149: Island detected

    Product fit

    • HMS-300/350/400/450/500-1T · Role not confirmed

      Confirmed · AU/region not confirmed · Firmware not documented

    • HMT-1600/1800/2000-4T LA · Role not confirmed

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Confirm whether the premises has grid supply and record the alarm. Do not operate solar switches or rooftop equipment; contact the installer if normal supply is present but the alarm remains.

    Installer remedy

    Check the AC supply, connection and anti-islanding condition under the exact HMS/HMT procedure. Restore service only after a stable grid and sound AC connection are confirmed.

    Remedy sourceHMS 1T manualHMT manual

    Manufacturer / escalation handoff
  • 9000

    Microinverter suspected stolen

    Community decoder: an anti-theft event was reported. This code was not found in the reviewed manufacturer manuals.

Sources

Continue this work

Did this help you move the job forward?

Tell us what is missing
Good to know

Frequently asked

Where do these Hoymiles fault codes come from?
Compiled from publicly available Hoymiles inverter and battery documentation and field references, then rewritten for the trade. Wattbench is independent and not affiliated with Hoymiles.
Which of these can I clear on site?
Some clear on their own once grid or environmental conditions return to normal. Anything involving DC isolation, AC switching, wiring or opening the unit is licensed electrical work. Isolate safely, follow AS/NZS 5033 and AS/NZS 3000 procedure and use appropriate PPE before touching a live system.
The exact code isn't listed. Why not?
Firmware and model variants differ, and manufacturers revise their code tables. We document the most common ones; for a variant that isn't here, check the unit's current manual or the manufacturer's service portal.
How current is this reference?
This reference was last reviewed on 3 August 2026. We revise entries when the underlying manufacturer documentation changes.