GoodWe Error Codes
GoodWe inverter error codes for grid, isolation, temperature and internal faults, with clear guidance on self-recovery versus service.
20 of 20 codes
About this fault librarySources · scope
A reference compiled by Wattbench from GoodWe documentation and field sources. GoodWe shows faults as a numbered error code and/or a named fault depending on the model. On an LCD unit, short-press the front button and scroll to “Error”/“Fault”; on ET/EH/EHB hybrid units, check Alarms in the SolarGo app or the SEMS portal. Where a fault has both a number and a name, we list them together, and both are searchable. Five ET G2 codes previously carried plain numbers (16, 19, 20, 24/31, 26/32) that did not match this model's own fault-code table; they are now labelled with the exact F-code the ET G2 manual uses (F133, F35, F132, F30, F31) after direct verification against that table. Safety note: earth, insulation and PV over-voltage faults need a licensed worker. An owner should record the alarm and keep clear of isolators, wiring and connectors while the responsible installer follows the exact product procedure.
- 20 GoodWe fault and alarm codes, documented for the trade.
- Compiled from published documentation and field references; Wattbench is independent and not affiliated with GoodWe.
- Codes involving DC/AC isolation, wiring or opening the unit are licensed electrical work. Isolate safely and follow AS/NZS procedure.
Resolution text is manufacturer/service context, not permission for an owner to perform electrical work. Stop at visible observations unless the exact product instructions identify an owner control. Isolation, configuration, testing, opening equipment and wiring are for an appropriately licensed worker and, where required, an SAA-accredited person. Where a card says Product fit is unknown, treat it as brand-level guidance and confirm the exact model, role, regional variant, firmware and current manual before acting.
- 1
SPI failure
An internal communication (SPI bus) failure inside the inverter.
Product fit · Confirmed · ETC Series
Show field stepsHide field steps for 1: SPI failure
Product fit
ETC Series · Hybrid inverter
Confirmed · Manual V1.1 · AU/region not confirmed · Firmware not documented
Safe checks now
Record the exact code, inverter model and time. Do not operate isolators or open the inverter; contact your installer or GoodWe if the code remains.
Installer remedy
Follow the controlled shutdown and restart sequence for the exact model. If the fault returns, preserve the code and escalate to GoodWe after-sales rather than repeatedly resetting it.
Remedy sourceETC manual V1.1
Manufacturer / escalation handoff
- 2
EEPROM R/W failure
A read/write failure on the inverter's memory chip.
Product fit · Confirmed · ETC Series
Show field stepsHide field steps for 2: EEPROM R/W failure
Product fit
ETC Series · Hybrid inverter
Confirmed · Manual V1.1 · AU/region not confirmed · Firmware not documented
Safe checks now
Record the exact code, inverter model and time. Do not operate isolators or open the inverter; contact your installer or GoodWe if the code remains.
Installer remedy
Follow the controlled shutdown and restart sequence for the exact model. If the fault returns, preserve the code and escalate to GoodWe after-sales rather than repeatedly resetting it.
Remedy sourceETC manual V1.1
Manufacturer / escalation handoff
- 3 · Fac Failure
Grid frequency fault
The grid frequency is outside the inverter's permissible range.
Product fit · Confirmed · ET Series / ET Plus Series
Show field stepsHide field steps for 3 · Fac Failure: Grid frequency fault
Product fit
ET Series / ET Plus Series · Three-phase hybrid inverter
Confirmed · Manual V1.1 · AU/region not confirmed · Firmware not documented
Safe checks now
Note when the alarm occurs and whether the property supply appears normal. It should clear when grid frequency returns to range; contact your installer if it persists or repeats.
Installer remedy
Check the displayed and measured grid frequency against the approved operating settings. Preserve the configured country/protection profile and escalate persistent supply abnormalities through the authorised network process.
Remedy sourceGoodWe FAQET manual
Manufacturer / escalation handoff
- 7 · 25
Relay check failure
The inverter's grid relay failed its self-check.
Product fit · Confirmed · ETC Series
Show field stepsHide field steps for 7 · 25: Relay check failure
Product fit
ETC Series · Hybrid inverter
Confirmed · Manual V1.1 · AU/region not confirmed · Firmware not documented
Safe checks now
Record the exact code, inverter model and time. Do not operate isolators or open the inverter; contact your installer or GoodWe if the code remains.
Installer remedy
Check the AC neutral-to-earth condition under the model-specific procedure, then perform one controlled restart. A recurring relay check failure requires GoodWe service assessment.
Remedy sourceETC manual V1.1
Manufacturer / escalation handoff
- 12
LCD communication failure
A communication error between the LCD/display and the master DSP.
Product fit · Confirmed · ETC Series
Show field stepsHide field steps for 12: LCD communication failure
Product fit
ETC Series · Hybrid inverter
Confirmed · Manual V1.1 · AU/region not confirmed · Firmware not documented
Safe checks now
Record the exact code, inverter model and time. Do not operate isolators or open the inverter; contact your installer or GoodWe if the code remains.
Installer remedy
Follow the controlled shutdown and restart sequence for the exact model. If the fault returns, preserve the code and escalate to GoodWe after-sales rather than repeatedly resetting it.
Remedy sourceETC manual V1.1
Manufacturer / escalation handoff
- 13
DC injection high
The DC component of the AC output current exceeds the inverter's limit.
Product fit · Confirmed · ETC Series
Show field stepsHide field steps for 13: DC injection high
Product fit
ETC Series · Hybrid inverter
Confirmed · Manual V1.1 · AU/region not confirmed · Firmware not documented
Safe checks now
Record the exact code, inverter model and time. Do not operate isolators or open the inverter; contact your installer or GoodWe if the code remains.
Installer remedy
Perform one controlled restart under the exact product procedure. If the DC-injection fault returns, stop resetting and escalate immediately to GoodWe after-sales.
Remedy sourceETC manual V1.1
Manufacturer / escalation handoff
- 14 · Isolation Fail
Isolation failure
Insulation resistance between the PV array and ground is too low, most common in rain or high humidity.
Product fit · Confirmed · ET Series / ET Plus Series
Show field stepsHide field steps for 14 · Isolation Fail: Isolation failure
Product fit
ET Series / ET Plus Series · Three-phase hybrid inverter
Confirmed · Manual V1.1 · AU/region not confirmed · Firmware not documented
Safe checks now
Record the code, time and weather conditions. Do not reset the inverter, touch PV connectors or operate isolators; arrange a licensed inspection if it persists or returns.
Installer remedy
Test the PV insulation resistance to earth using the exact model limits and safe-isolation procedure. Inspect the affected string wiring, connectors, earthing and moisture exposure before returning the system to service.
Remedy sourceGoodWe FAQET manual
Manufacturer / escalation handoff
- 15 · Vac Failure
Grid voltage fault
The grid voltage is outside the acceptable range for the inverter.
Product fit · Confirmed · ET Series / ET Plus Series
Show field stepsHide field steps for 15 · Vac Failure: Grid voltage fault
Product fit
ET Series / ET Plus Series · Three-phase hybrid inverter
Confirmed · Manual V1.1 · AU/region not confirmed · Firmware not documented
Safe checks now
Note when the alarm occurs and whether other equipment has lost supply. The inverter should reconnect when grid voltage returns to range; contact your installer if it persists or repeats.
Installer remedy
Measure the inverter AC supply, verify wiring and the approved country/protection profile, and retain the settings as found. Escalate a confirmed supply-voltage issue through the authorised network process.
Remedy sourceGoodWe FAQET manual
Manufacturer / escalation handoff
- F133 · External Fan Abnormal
External fan abnormal
The external cooling fan is not operating correctly. The ET G2 manual lists the possible causes as a fan power-supply fault, a mechanical stall, or fan ageing/damage.
Product fit · Confirmed · ET G2 6–15 kW
Show field stepsHide field steps for F133 · External Fan Abnormal: External fan abnormal
Product fit
ET G2 6–15 kW · Three-phase hybrid inverter
Confirmed · Manual V2.1 · AU/region not confirmed · Firmware not documented
Safe checks now
From a safe position, check that the inverter's external airflow is not visibly obstructed. Do not touch the fan or open the unit; contact your installer if the alarm remains.
Installer remedy
Follow the ET G2 manual's fan-fault procedure: turn off the AC output and DC input switches, wait 5 minutes, then restart. Replace a failed external fan through the authorised service process if the alarm persists.
Remedy sourceET G2 manual V2.1
Manufacturer / escalation handoff
- 17 · PV Over Voltage
PV over-voltage
The PV array voltage exceeds the inverter's maximum input.
Product fit · Confirmed · ET Series / ET Plus Series
Show field stepsHide field steps for 17 · PV Over Voltage: PV over-voltage
Product fit
ET Series / ET Plus Series · Three-phase hybrid inverter
Confirmed · Manual V1.1 · AU/region not confirmed · Firmware not documented
Safe checks now
Leave the inverter and PV wiring alone, record the code and contact your installer promptly. Do not reset the inverter or operate isolators to test whether it clears.
Installer remedy
Measure each string's open-circuit voltage under the approved procedure and compare it with the exact inverter input limit and temperature-corrected design. Correct the string design before reconnection.
Remedy sourceGoodWe FAQET manual
Manufacturer / escalation handoff
- F35
Cabinet over temperature
The inverter cabinet's temperature has exceeded its safe limit. The ET G2 manual lists the possible causes as poor ventilation at the install location, high ambient temperature, or abnormal internal fan operation.
Product fit · Confirmed · ET G2 6–15 kW
Show field stepsHide field steps for F35: Cabinet over temperature
Product fit
ET G2 6–15 kW · Three-phase hybrid inverter
Confirmed · Manual V2.1 · AU/region not confirmed · Firmware not documented
Safe checks now
From a safe position, keep the area around the inverter clear and note whether it is in direct sun, poorly ventilated or unusually hot. Do not open the unit; contact your installer if it does not recover after cooling.
Installer remedy
Check the installation ventilation and ambient temperature against the ET G2 manual's limits. If both are within range and the alarm persists, escalate to GoodWe rather than opening the enclosure.
Remedy sourceET G2 manual V2.1
Manufacturer / escalation handoff
- F132 · Internal Fan Abnormal
Internal fan abnormal
The internal cooling fan is not operating correctly. The ET G2 manual lists the possible causes as a fan power-supply fault, a mechanical stall, or fan ageing/damage.
Product fit · Confirmed · ET G2 6–15 kW
Show field stepsHide field steps for F132 · Internal Fan Abnormal: Internal fan abnormal
Product fit
ET G2 6–15 kW · Three-phase hybrid inverter
Confirmed · Manual V2.1 · AU/region not confirmed · Firmware not documented
Safe checks now
Record the exact code, inverter model and time. Do not operate isolators or open the inverter; contact your installer or GoodWe if the code remains.
Installer remedy
Follow the ET G2 manual's fan-fault procedure: turn off the AC output and DC input switches, wait 5 minutes, then restart. An internal fan fault that remains requires authorised service; do not leave the enclosure open in operation.
Remedy sourceET G2 manual V2.1
Manufacturer / escalation handoff
- 21
DC bus high
The internal DC bus voltage is too high.
Product fit · Confirmed · ETC Series
Show field stepsHide field steps for 21: DC bus high
Product fit
ETC Series · Hybrid inverter
Confirmed · Manual V1.1 · AU/region not confirmed · Firmware not documented
Safe checks now
Record the exact code, inverter model and time. Do not operate isolators or open the inverter; contact your installer or GoodWe if the code remains.
Installer remedy
Follow the controlled shutdown and restart sequence for the exact model. If the fault returns, preserve the code and escalate to GoodWe after-sales rather than repeatedly resetting it.
Remedy sourceETC manual V1.1
Manufacturer / escalation handoff
- 22 · Ground I Fail
Ground (residual) current failure
Residual-current (earth-leakage) protection has tripped. Current is leaking to ground.
Product fit · Confirmed · ETC Series
Show field stepsHide field steps for 22 · Ground I Fail: Ground (residual) current failure
Product fit
ETC Series · Hybrid inverter
Confirmed · Manual V1.1 · AU/region not confirmed · Firmware not documented
Safe checks now
Record the code, time and weather conditions. Do not reset the inverter or touch system wiring; arrange a licensed inspection if the alarm persists or returns.
Installer remedy
Test the PV strings and AC earthing/neutral conditions under the exact product procedure. Locate damaged insulation, moisture ingress or an abnormal earth path before returning the system to service.
Remedy sourceGoodWe FAQETC manual V1.1
Manufacturer / escalation handoff
- 23 · Utility Loss
Utility (grid) loss
Loss of connection between the inverter and the utility grid, an outage or a disconnection.
Product fit · Confirmed · ET Series / ET Plus Series
Show field stepsHide field steps for 23 · Utility Loss: Utility (grid) loss
Product fit
ET Series / ET Plus Series · Three-phase hybrid inverter
Confirmed · Manual V1.1 · AU/region not confirmed · Firmware not documented
Safe checks now
Check whether the property and neighbourhood have grid supply, then record the code and time. Do not operate solar isolators; contact your installer if normal grid supply is present but the alarm remains.
Installer remedy
Verify AC supply at the inverter, protective-device state and AC wiring under the approved procedure. If supply and wiring are sound, follow the model troubleshooting path and escalate to GoodWe.
Remedy sourceGoodWe FAQET manual
Manufacturer / escalation handoff
- F30 · AC HCT Check Abnormal
AC current-sensor (HCT) check abnormal
The ET G2 manual describes this as abnormal sampling detected in the AC current sensor.
Product fit · Confirmed · ET G2 6–15 kW
Show field stepsHide field steps for F30 · AC HCT Check Abnormal: AC current-sensor (HCT) check abnormal
Product fit
ET G2 6–15 kW · Three-phase hybrid inverter
Confirmed · Manual V2.1 · AU/region not confirmed · Firmware not documented
Safe checks now
Record the exact code, inverter model and time. Do not operate isolators or open the inverter; contact your installer or GoodWe if the code remains.
Installer remedy
Follow the ET G2 manual's sensor-fault procedure: turn off the AC output and DC input switches, wait 5 minutes, then restart. If the AC current-sensor fault persists, arrange GoodWe service rather than attempting an internal repair.
Remedy sourceET G2 manual V2.1
Manufacturer / escalation handoff
- F31 · GFCI HCT Check Abnormal
Leakage-current sensor (GFCI HCT) check abnormal
The ET G2 manual describes this as abnormal sampling detected in the leakage-current sensor.
Product fit · Confirmed · ET G2 6–15 kW
Show field stepsHide field steps for F31 · GFCI HCT Check Abnormal: Leakage-current sensor (GFCI HCT) check abnormal
Product fit
ET G2 6–15 kW · Three-phase hybrid inverter
Confirmed · Manual V2.1 · AU/region not confirmed · Firmware not documented
Safe checks now
Record the exact code, inverter model and time. Do not operate isolators or open the inverter; contact your installer or GoodWe if the code remains.
Installer remedy
Follow the ET G2 manual's sensor-fault procedure: turn off the AC output and DC input switches, wait 5 minutes, then restart. A persistent leakage-current sensor fault requires prompt service because the protection it provides cannot be relied upon.
Remedy sourceET G2 manual V2.1
Manufacturer / escalation handoff
- 30
Reference 1.5 V failure
The internal 1.5 V reference voltage is out of range.
Product fit · Confirmed · ETC Series
Show field stepsHide field steps for 30: Reference 1.5 V failure
Product fit
ETC Series · Hybrid inverter
Confirmed · Manual V1.1 · AU/region not confirmed · Firmware not documented
Safe checks now
Record the exact code, inverter model and time. Do not operate isolators or open the inverter; contact your installer or GoodWe if the code remains.
Installer remedy
Follow the controlled shutdown and restart sequence for the exact model. If the fault returns, preserve the code and escalate to GoodWe after-sales rather than repeatedly resetting it.
Remedy sourceETC manual V1.1
Manufacturer / escalation handoff
- PE Loss
Protective earth (PE) loss
A missing or faulty protective-earth connection, possibly loose wiring, corrosion, or grounding-system damage.
Product fit · Confirmed · ET Series / ET Plus Series
Show field stepsHide field steps for PE Loss: Protective earth (PE) loss
Product fit
ET Series / ET Plus Series · Three-phase hybrid inverter
Confirmed · Manual V1.1 · AU/region not confirmed · Firmware not documented
Safe checks now
Do not reset the inverter or touch electrical equipment. Record the code and arrange a licensed electrician or your installer to attend.
Installer remedy
Verify the protective-earth connection and continuity under the approved safe-isolation procedure. Rectify the earthing fault before the inverter is returned to service.
Remedy sourceGoodWe FAQET manual
Manufacturer / escalation handoff
- Device Failure
Internal device failure
A general internal device failure (shown for faults outside the listed codes).
Product fit · Confirmed · ET G2 6–15 kW
Show field stepsHide field steps for Device Failure: Internal device failure
Product fit
ET G2 6–15 kW · Three-phase hybrid inverter
Confirmed · Manual V2.1 · AU/region not confirmed · Firmware not documented
Safe checks now
Record the exact code, inverter model and time. Do not operate isolators or open the inverter; contact your installer or GoodWe if the code remains.
Installer remedy
Follow the controlled shutdown and restart sequence for the exact model. If the fault returns, preserve the code and escalate to GoodWe after-sales rather than repeatedly resetting it.
Remedy sourceET G2 manual V2.1
Manufacturer / escalation handoff
Sources
- ManufacturerGoodWe Official FAQs: inverter error displays & troubleshooting (official)
- ManufacturerGoodWe ET Series User Manual V1.1 (official)
- ManufacturerGoodWe ETC Series User Manual V1.1 (official)
- ManufacturerGoodWe ET G2 6–15 kW User Manual V2.1 (official)
- GoodWe Inverter Fault Codes – The Complete Aussie Guide (2025), Universe Solar
- The 9 Most Common GoodWe Inverter Fault Codes, Static Electrics (Australia)
Best next action
Did this help you move the job forward?
Frequently asked
- Where do these GoodWe fault codes come from?
- Compiled from publicly available GoodWe inverter and battery documentation and field references, then rewritten for the trade. Wattbench is independent and not affiliated with GoodWe.
- Which of these can I clear on site?
- Some clear on their own once grid or environmental conditions return to normal. Anything involving DC isolation, AC switching, wiring or opening the unit is licensed electrical work. Isolate safely, follow AS/NZS 5033 and AS/NZS 3000 procedure and use appropriate PPE before touching a live system.
- The exact code isn't listed. Why not?
- Firmware and model variants differ, and manufacturers revise their code tables. We document the most common ones; for a variant that isn't here, check the unit's current manual or the manufacturer's service portal.
- How current is this reference?
- This reference was last reviewed on 2 August 2026. We revise entries when the underlying manufacturer documentation changes.
Other fault libraries
Solis Alarm Codes
Solis alarm vocabulary from official service material, with owner-safe and installer guidance while exact Australian model and firmware applicability remains blank.
29 codesInverter Fault LibrarySungrow Alarm Codes
A searchable Sungrow fault reference with current SH5T–SH25T remedies separated from earlier SH/RT/RS, string-inverter, battery and BDC records.
175 codesInverter Fault LibraryDeye Inverter Fault Codes
Deye SG04LP3-AU fault-table guidance, with deployed-firmware F08/F35 residues labelled and left without unsupported remedies.
26 codes