Solis alarm vocabulary from official service material, with owner-safe and installer guidance while exact Australian model and firmware applicability remains blank.

Sources listedReviewed August 2026Source: Manufacturer documentationOur methodology

30 of 30 codes

About this fault librarySources · scope

Solis alarm names vary by inverter family and firmware. The reviewed remedies use Solis's official North American complete alarm list plus its global no-display article. That establishes manufacturer provenance, but it does not confirm an Australian variant, a single model family or a firmware range; those fields remain blank. Confirm the exact model and displayed wording before applying an entry. Safety note: owners should record the alarm and safely visible conditions. DC/AC isolation, measurements, connectors, wiring, settings and internal work are licensed-installer tasks performed to the exact model manual.

Key takeaways
  • 30 Solis (Ginlong) fault and alarm codes, documented for the trade.
  • Compiled from published documentation and field references; Wattbench is independent and not affiliated with Solis (Ginlong).
  • Codes involving DC/AC isolation, wiring or opening the unit are licensed electrical work. Isolate safely and follow AS/NZS procedure.

Resolution text is manufacturer/service context, not permission for an owner to perform electrical work. Stop at visible observations unless the exact product instructions identify an owner control. Isolation, configuration, testing, opening equipment and wiring are for an appropriately licensed worker and, where required, an SAA-accredited person. Where a card says Product fit is unknown, treat it as brand-level guidance and confirm the exact model, role, regional variant, firmware and current manual before acting.

  • LCD blank

    No display / inverter will not turn on

    The LCD or indicators remain blank and the inverter is not starting.

    Product fit · Unknown

    Show field steps for LCD blank: No display / inverter will not turn on

    Product fit · Unknown

    Safe checks now

    Record that the display and indicators are blank. Do not operate DC equipment or test live circuits; contact the installer to follow the Solis no-display procedure.

    Installer remedy

    Use the Solis no-display procedure to verify DC input, polarity and start voltage for the exact model under safe isolation. Escalate if valid input is present and the inverter remains dark.

    Remedy sourceSolis no-display guide

    Manufacturer / escalation handoff
  • Waiting / SoftRun (init loop)

    Waiting or SoftRun does not clear

    The inverter remains in a documented start-up state rather than progressing to generation. This is not the same as the separate INI-FAULT alarm.

    Product fit · Unknown

    Show field steps for Waiting / SoftRun (init loop): Waiting or SoftRun does not clear

    Product fit · Unknown

    Safe checks now

    Record the exact displayed message and system state. Do not change settings, operate isolators or open equipment; contact the installer if the condition remains.

    Installer remedy

    Follow the matching entry in the Solis alarm list for the exact product and displayed wording. Preserve configuration as found and escalate if the documented checks do not clear the condition.

    Remedy sourceSolis alarm list (NA)

    Manufacturer / escalation handoff
  • OV-G-V01–04

    Over grid voltage

    The measured grid voltage is above the configured protection limit.

    Product fit · Unknown

    Show field steps for OV-G-V01–04: Over grid voltage

    Product fit · Unknown

    Safe checks now

    Record the alarm, time and whether the premises supply appears normal. Do not change the grid standard or protection settings; contact the installer if the alarm repeats.

    Installer remedy

    Check the measured grid condition, AC connection and selected standard using the Solis alarm-list procedure. Preserve approved settings and obtain network approval before any protection-point change.

    Remedy sourceSolis alarm list (NA)

    Manufacturer / escalation handoff
  • UN-G-V01/02

    Under grid voltage

    The measured grid voltage is below the configured protection limit.

    Product fit · Unknown

    Show field steps for UN-G-V01/02: Under grid voltage

    Product fit · Unknown

    Safe checks now

    Record the alarm, time and whether the premises supply appears normal. Do not change the grid standard or protection settings; contact the installer if the alarm repeats.

    Installer remedy

    Check the measured grid condition, AC connection and selected standard using the Solis alarm-list procedure. Preserve approved settings and obtain network approval before any protection-point change.

    Remedy sourceSolis alarm list (NA)

    Manufacturer / escalation handoff
  • OV-G-F01/02

    Over grid frequency

    The measured grid frequency is above the configured protection limit.

    Product fit · Unknown

    Show field steps for OV-G-F01/02: Over grid frequency

    Product fit · Unknown

    Safe checks now

    Record the alarm, time and whether the premises supply appears normal. Do not change the grid standard or protection settings; contact the installer if the alarm repeats.

    Installer remedy

    Check the measured grid condition, AC connection and selected standard using the Solis alarm-list procedure. Preserve approved settings and obtain network approval before any protection-point change.

    Remedy sourceSolis alarm list (NA)

    Manufacturer / escalation handoff
  • UN-G-F01/02

    Under grid frequency

    The measured grid frequency is below the configured protection limit.

    Product fit · Unknown

    Show field steps for UN-G-F01/02: Under grid frequency

    Product fit · Unknown

    Safe checks now

    Record the alarm, time and whether the premises supply appears normal. Do not change the grid standard or protection settings; contact the installer if the alarm repeats.

    Installer remedy

    Check the measured grid condition, AC connection and selected standard using the Solis alarm-list procedure. Preserve approved settings and obtain network approval before any protection-point change.

    Remedy sourceSolis alarm list (NA)

    Manufacturer / escalation handoff
  • Reverse-GRID

    AC polarity incorrect

    The inverter detects an incorrect AC connection polarity.

    Product fit · Unknown

    Show field steps for Reverse-GRID: AC polarity incorrect

    Product fit · Unknown

    Safe checks now

    Record the exact displayed message and system state. Do not change settings, operate isolators or open equipment; contact the installer if the condition remains.

    Installer remedy

    Follow the matching entry in the Solis alarm list for the exact product and displayed wording. Preserve configuration as found and escalate if the documented checks do not clear the condition.

    Remedy sourceSolis alarm list (NA)

    Manufacturer / escalation handoff
  • Reverse-DC

    DC polarity reversed

    The inverter detects reverse polarity at a DC input.

    Product fit · Unknown

    Show field steps for Reverse-DC: DC polarity reversed

    Product fit · Unknown

    Safe checks now

    Record the exact alarm and weather conditions, keep clear of the array and do not reset the inverter or operate DC equipment. Arrange a licensed inspection promptly.

    Installer remedy

    Follow the Solis alarm-list checks for polarity, PV voltage, insulation, leakage or arcing under the exact model's safe-isolation procedure. Rectify the cause before returning the system to service.

    Remedy sourceSolis alarm list (NA)

    Manufacturer / escalation handoff
  • NO-GRID

    No grid detected

    The inverter cannot detect an acceptable grid supply.

    Product fit · Unknown

    Show field steps for NO-GRID: No grid detected

    Product fit · Unknown

    Safe checks now

    Record the alarm, time and whether the premises supply appears normal. Do not change the grid standard or protection settings; contact the installer if the alarm repeats.

    Installer remedy

    Check the measured grid condition, AC connection and selected standard using the Solis alarm-list procedure. Preserve approved settings and obtain network approval before any protection-point change.

    Remedy sourceSolis alarm list (NA)

    Manufacturer / escalation handoff
  • OV-DC01–04

    Over DC voltage

    The DC input voltage is above the inverter's permitted limit.

    Product fit · Unknown

    Show field steps for OV-DC01–04: Over DC voltage

    Product fit · Unknown

    Safe checks now

    Record the exact alarm and weather conditions, keep clear of the array and do not reset the inverter or operate DC equipment. Arrange a licensed inspection promptly.

    Installer remedy

    Follow the Solis alarm-list checks for polarity, PV voltage, insulation, leakage or arcing under the exact model's safe-isolation procedure. Rectify the cause before returning the system to service.

    Remedy sourceSolis alarm list (NA)

    Manufacturer / escalation handoff
  • OV-BUS

    Over DC bus voltage

    The inverter's internal DC bus voltage is too high.

    Product fit · Unknown

    Show field steps for OV-BUS: Over DC bus voltage

    Product fit · Unknown

    Safe checks now

    Record the exact alarm, model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer if the alarm does not clear.

    Installer remedy

    Use the current Solis alarm-list procedure for the exact message, including one controlled restart only where documented. Escalate a persistent internal sensing, bus, relay or current fault to Solis.

    Remedy sourceSolis alarm list (NA)

    Manufacturer / escalation handoff
  • UN-BUS01/02

    Under DC bus voltage

    The inverter's internal DC bus voltage is too low.

    Product fit · Unknown

    Show field steps for UN-BUS01/02: Under DC bus voltage

    Product fit · Unknown

    Safe checks now

    Record the exact alarm, model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer if the alarm does not clear.

    Installer remedy

    Use the current Solis alarm-list procedure for the exact message, including one controlled restart only where documented. Escalate a persistent internal sensing, bus, relay or current fault to Solis.

    Remedy sourceSolis alarm list (NA)

    Manufacturer / escalation handoff
  • GRID-INTF01/02

    Grid interference

    The inverter detected interference or instability on the grid connection.

    Product fit · Unknown

    Show field steps for GRID-INTF01/02: Grid interference

    Product fit · Unknown

    Safe checks now

    Record the alarm, time and whether the premises supply appears normal. Do not change the grid standard or protection settings; contact the installer if the alarm repeats.

    Installer remedy

    Check the measured grid condition, AC connection and selected standard using the Solis alarm-list procedure. Preserve approved settings and obtain network approval before any protection-point change.

    Remedy sourceSolis alarm list (NA)

    Manufacturer / escalation handoff
  • OV-G-I

    Over grid current

    The inverter measured AC output current above its allowed limit.

    Product fit · Unknown

    Show field steps for OV-G-I: Over grid current

    Product fit · Unknown

    Safe checks now

    Record the exact alarm, model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer if the alarm does not clear.

    Installer remedy

    Use the current Solis alarm-list procedure for the exact message, including one controlled restart only where documented. Escalate a persistent internal sensing, bus, relay or current fault to Solis.

    Remedy sourceSolis alarm list (NA)

    Manufacturer / escalation handoff
  • IGBT-OV-I

    Over IGBT current

    The inverter detected excessive current in its power-conversion stage.

    Product fit · Unknown

    Show field steps for IGBT-OV-I: Over IGBT current

    Product fit · Unknown

    Safe checks now

    Record the exact alarm, model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer if the alarm does not clear.

    Installer remedy

    Use the current Solis alarm-list procedure for the exact message, including one controlled restart only where documented. Escalate a persistent internal sensing, bus, relay or current fault to Solis.

    Remedy sourceSolis alarm list (NA)

    Manufacturer / escalation handoff
  • G-IMP

    High grid impedance

    The inverter measured grid impedance outside its permitted range.

    Product fit · Unknown

    Show field steps for G-IMP: High grid impedance

    Product fit · Unknown

    Safe checks now

    Record the alarm, time and whether the premises supply appears normal. Do not change the grid standard or protection settings; contact the installer if the alarm repeats.

    Installer remedy

    Check the measured grid condition, AC connection and selected standard using the Solis alarm-list procedure. Preserve approved settings and obtain network approval before any protection-point change.

    Remedy sourceSolis alarm list (NA)

    Manufacturer / escalation handoff
  • DC-INTF / OV-DCA-I

    DC input over-current

    The inverter detected excessive current at a DC input or MPPT.

    Product fit · Unknown

    Show field steps for DC-INTF / OV-DCA-I: DC input over-current

    Product fit · Unknown

    Safe checks now

    Record the exact alarm, model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer if the alarm does not clear.

    Installer remedy

    Use the current Solis alarm-list procedure for the exact message, including one controlled restart only where documented. Escalate a persistent internal sensing, bus, relay or current fault to Solis.

    Remedy sourceSolis alarm list (NA)

    Manufacturer / escalation handoff
  • IGFOL-F

    Grid-current tracking failed

    The inverter could not correctly track the grid current.

    Product fit · Unknown

    Show field steps for IGFOL-F: Grid-current tracking failed

    Product fit · Unknown

    Safe checks now

    Record the exact alarm, model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer if the alarm does not clear.

    Installer remedy

    Use the current Solis alarm-list procedure for the exact message, including one controlled restart only where documented. Escalate a persistent internal sensing, bus, relay or current fault to Solis.

    Remedy sourceSolis alarm list (NA)

    Manufacturer / escalation handoff
  • IG-AD

    Grid-current sampling failed

    The inverter detected a fault in its grid-current sampling circuit.

    Product fit · Unknown

    Show field steps for IG-AD: Grid-current sampling failed

    Product fit · Unknown

    Safe checks now

    Record the exact alarm, model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer if the alarm does not clear.

    Installer remedy

    Use the current Solis alarm-list procedure for the exact message, including one controlled restart only where documented. Escalate a persistent internal sensing, bus, relay or current fault to Solis.

    Remedy sourceSolis alarm list (NA)

    Manufacturer / escalation handoff
  • OV-TEM

    Over temperature

    The inverter temperature exceeded its permitted operating range.

    Product fit · Unknown

    Show field steps for OV-TEM: Over temperature

    Product fit · Unknown

    Safe checks now

    From a safe position, keep the area around the inverter clear and note direct sun, unusual heat or visibly blocked airflow. Do not open the unit; contact the installer if it remains.

    Installer remedy

    Check ambient conditions, installation clearances and cooling against the exact Solis model instructions. If conditions are normal and the alarm persists, follow the manufacturer escalation path.

    Remedy sourceSolis alarm list (NA)

    Manufacturer / escalation handoff
  • INI-FAULT

    Initialisation system fault

    The inverter detected a system fault during initialisation.

    Product fit · Unknown

    Show field steps for INI-FAULT: Initialisation system fault

    Product fit · Unknown

    Safe checks now

    Record the exact alarm, model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer if the alarm does not clear.

    Installer remedy

    Use the current Solis alarm-list procedure for the exact message, including one controlled restart only where documented. Escalate a persistent internal sensing, bus, relay or current fault to Solis.

    Remedy sourceSolis alarm list (NA)

    Manufacturer / escalation handoff
  • DSP-B-FAULT

    Main–slave DSP communication failure

    Communication between the inverter's internal control processors failed.

    Product fit · Unknown

    Show field steps for DSP-B-FAULT: Main–slave DSP communication failure

    Product fit · Unknown

    Safe checks now

    Record the exact alarm, model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer if the alarm does not clear.

    Installer remedy

    Use the current Solis alarm-list procedure for the exact message, including one controlled restart only where documented. Escalate a persistent internal sensing, bus, relay or current fault to Solis.

    Remedy sourceSolis alarm list (NA)

    Manufacturer / escalation handoff
  • 12power-FAULT

    12 V power-supply fault

    The inverter detected a fault in its internal 12 V supply.

    Product fit · Unknown

    Show field steps for 12power-FAULT: 12 V power-supply fault

    Product fit · Unknown

    Safe checks now

    Record the exact alarm, model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer if the alarm does not clear.

    Installer remedy

    Use the current Solis alarm-list procedure for the exact message, including one controlled restart only where documented. Escalate a persistent internal sensing, bus, relay or current fault to Solis.

    Remedy sourceSolis alarm list (NA)

    Manufacturer / escalation handoff
  • PV ISO-PRO01/02

    PV insulation protection

    The inverter measured low insulation resistance between the PV circuit and earth.

    Product fit · Unknown

    Show field steps for PV ISO-PRO01/02: PV insulation protection

    Product fit · Unknown

    Safe checks now

    Record the exact alarm and weather conditions, keep clear of the array and do not reset the inverter or operate DC equipment. Arrange a licensed inspection promptly.

    Installer remedy

    Follow the Solis alarm-list checks for polarity, PV voltage, insulation, leakage or arcing under the exact model's safe-isolation procedure. Rectify the cause before returning the system to service.

    Remedy sourceSolis alarm list (NA)

    Manufacturer / escalation handoff
  • ILeak-PRO01–04

    Leakage-current protection

    The measured residual current exceeded the protection limit.

    Product fit · Unknown

    Show field steps for ILeak-PRO01–04: Leakage-current protection

    Product fit · Unknown

    Safe checks now

    Record the exact alarm and weather conditions, keep clear of the array and do not reset the inverter or operate DC equipment. Arrange a licensed inspection promptly.

    Installer remedy

    Follow the Solis alarm-list checks for polarity, PV voltage, insulation, leakage or arcing under the exact model's safe-isolation procedure. Rectify the cause before returning the system to service.

    Remedy sourceSolis alarm list (NA)

    Manufacturer / escalation handoff
  • RelayChk-FAIL

    Relay check failed

    The inverter's internal relay self-check did not pass.

    Product fit · Unknown

    Show field steps for RelayChk-FAIL: Relay check failed

    Product fit · Unknown

    Safe checks now

    Record the exact alarm, model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer if the alarm does not clear.

    Installer remedy

    Use the current Solis alarm-list procedure for the exact message, including one controlled restart only where documented. Escalate a persistent internal sensing, bus, relay or current fault to Solis.

    Remedy sourceSolis alarm list (NA)

    Manufacturer / escalation handoff
  • DCinj-FAULT

    High DC injection current

    The measured DC component of the AC output exceeded its protection limit.

    Product fit · Unknown

    Show field steps for DCinj-FAULT: High DC injection current

    Product fit · Unknown

    Safe checks now

    Record the exact alarm, model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer if the alarm does not clear.

    Installer remedy

    Use the current Solis alarm-list procedure for the exact message, including one controlled restart only where documented. Escalate a persistent internal sensing, bus, relay or current fault to Solis.

    Remedy sourceSolis alarm list (NA)

    Manufacturer / escalation handoff
  • Screen off

    Screen off with DC present

    The display is off even though the PV circuit may still be energised; the inverter may have an internal fault.

    Product fit · Unknown

    Show field steps for Screen off: Screen off with DC present

    Product fit · Unknown

    Safe checks now

    Record the exact alarm, model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer if the alarm does not clear.

    Installer remedy

    Use the current Solis alarm-list procedure for the exact message, including one controlled restart only where documented. Escalate a persistent internal sensing, bus, relay or current fault to Solis.

    Remedy sourceSolis alarm list (NA)

    Manufacturer / escalation handoff
  • AFCI self-test

    AFCI self-detection fault

    The arc-fault detection module did not pass its self-check.

    Product fit · Unknown

    Show field steps for AFCI self-test: AFCI self-detection fault

    Product fit · Unknown

    Safe checks now

    Record the exact alarm and weather conditions, keep clear of the array and do not reset the inverter or operate DC equipment. Arrange a licensed inspection promptly.

    Installer remedy

    Follow the Solis alarm-list checks for polarity, PV voltage, insulation, leakage or arcing under the exact model's safe-isolation procedure. Rectify the cause before returning the system to service.

    Remedy sourceSolis alarm list (NA)

    Manufacturer / escalation handoff
  • Arcing

    Arc detected in DC circuit

    The inverter's arc-fault protection detected a possible DC arc.

    Product fit · Unknown

    Show field steps for Arcing: Arc detected in DC circuit

    Product fit · Unknown

    Safe checks now

    Record the exact alarm and weather conditions, keep clear of the array and do not reset the inverter or operate DC equipment. Arrange a licensed inspection promptly.

    Installer remedy

    Follow the Solis alarm-list checks for polarity, PV voltage, insulation, leakage or arcing under the exact model's safe-isolation procedure. Rectify the cause before returning the system to service.

    Remedy sourceSolis alarm list (NA)

    Manufacturer / escalation handoff

Sources

Continue this work

Did this help you move the job forward?

Tell us what is missing
Good to know

Frequently asked

Where do these Solis fault codes come from?
Compiled from publicly available Solis inverter and battery documentation and field references, then rewritten for the trade. Wattbench is independent and not affiliated with Solis.
Which of these can I clear on site?
Some clear on their own once grid or environmental conditions return to normal. Anything involving DC isolation, AC switching, wiring or opening the unit is licensed electrical work. Isolate safely, follow AS/NZS 5033 and AS/NZS 3000 procedure and use appropriate PPE before touching a live system.
The exact code isn't listed. Why not?
Firmware and model variants differ, and manufacturers revise their code tables. We document the most common ones; for a variant that isn't here, check the unit's current manual or the manufacturer's service portal.
How current is this reference?
This reference was last reviewed on 2 August 2026. We revise entries when the underlying manufacturer documentation changes.