Growatt Error Codes

Current MOD XH codes separated from legacy TL/MTL search terms, with official remedies only where the exact current manual supports them.

Sources listedReviewed August 2026Source: Official current-family manual with a separately labelled legacy service-bulletin mirrorOur methodology

21 of 21 codes

About this fault librarySources · scope

This guide separates current MOD 3–10KTL3-XH evidence from legacy 1000–5000 TL / 2500–5000 MTL vocabulary. Reviewed remedies are attached only to the numbered MOD XH entries recovered in Growatt's official current manual, including warning 205, which the manual identifies as PV boost driver abnormal. Legacy codes and legacy named aliases remain remedy-blank because their service bulletin is available only through a secondary mirror. Australian and global Growatt pages both list the MOD family, but the installed Australian variant and firmware range are not established by the manual metadata. Safety note: owners should record the code and contact their installer. Isolation, measurements, wiring, parameter changes and internal repairs are licensed-worker tasks.

Key takeaways
  • 21 Growatt fault and alarm codes, documented for the trade.
  • Compiled from published documentation and field references; Wattbench is independent and not affiliated with Growatt.
  • Codes involving DC/AC isolation, wiring or opening the unit are licensed electrical work. Isolate safely and follow AS/NZS procedure.

Resolution text is manufacturer/service context, not permission for an owner to perform electrical work. Stop at visible observations unless the exact product instructions identify an owner control. Isolation, configuration, testing, opening equipment and wiring are for an appropriately licensed worker and, where required, an SAA-accredited person. Where a card says Product fit is unknown, treat it as brand-level guidance and confirm the exact model, role, regional variant, firmware and current manual before acting.

  • 100

    Reference-voltage fault

    Legacy TL/MTL family: the inverter detected an internal reference-voltage fault.

  • 101

    CPU communication fault

    Legacy TL/MTL family: communication between the inverter's internal processors failed.

  • 102

    Processor data mismatch

    Legacy TL/MTL family: the data reported by the two internal processors is inconsistent.

  • 116

    EEPROM fault

    Legacy TL/MTL family: the inverter reported an internal memory fault.

  • 117

    Relay-circuit fault

    Legacy TL/MTL family: the inverter detected an abnormality in its internal relay circuit.

  • 118

    Initialisation / model fault

    Legacy TL/MTL family: the inverter did not initialise with a valid model configuration.

  • 119

    GFCI device fault

    Legacy TL/MTL family: the inverter detected an internal ground-fault monitoring device fault.

  • 120

    Current-sensor fault

    Legacy TL/MTL family: the inverter detected an internal current-sensor fault.

  • 121

    CPU communication loss

    Legacy TL/MTL family: the main processor did not receive data from the secondary processor.

  • 122

    Bus-voltage fault

    Legacy TL/MTL family: the inverter's internal DC bus voltage is outside its expected range.

  • 201 · Residual I High

    Residual current high

    MOD XH: the inverter detected excessive leakage current. Legacy TL/MTL units can display the named message Residual I High for the same class of protection event.

    Product fit · Family-level · MOD 3–10KTL3-XH

    Show field steps for 201 · Residual I High: Residual current high

    Product fit

    • MOD 3–10KTL3-XH · Three-phase string inverter

      Family-level · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the code, time and weather conditions. Do not reset the inverter, touch PV wiring or operate isolators; arrange a licensed inspection if the event persists or returns.

    Installer remedy

    Apply the MOD 3–10KTL3-XH manual's insulation, residual-current or neutral-to-earth checks under safe isolation. Rectify the cause before returning the system to service; this remedy does not cover the legacy named label.

    Remedy sourceMOD XH manual

    Manufacturer / escalation handoff
  • 202 · PV Voltage High

    PV input voltage too high

    The PV input voltage exceeded the inverter's permitted limit.

    Product fit · Family-level · MOD 3–10KTL3-XH

    Show field steps for 202 · PV Voltage High: PV input voltage too high

    Product fit

    • MOD 3–10KTL3-XH · Three-phase string inverter

      Family-level · AU/region not confirmed · Firmware not documented

    Safe checks now

    Leave the inverter and array wiring alone, record the code and contact the installer promptly. Do not reset the unit or operate DC equipment to test whether it clears.

    Installer remedy

    Measure each string under the approved procedure and compare the temperature-corrected open-circuit voltage with the exact MOD XH input limit. Correct the design before reconnection.

    Remedy sourceMOD XH manual

    Manufacturer / escalation handoff
  • 203 · PV Isolation Low

    PV insulation resistance low

    The inverter measured low insulation resistance between the PV circuit and earth.

    Product fit · Family-level · MOD 3–10KTL3-XH

    Show field steps for 203 · PV Isolation Low: PV insulation resistance low

    Product fit

    • MOD 3–10KTL3-XH · Three-phase string inverter

      Family-level · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the code, time and weather conditions. Do not reset the inverter, touch PV wiring or operate isolators; arrange a licensed inspection if the event persists or returns.

    Installer remedy

    Apply the MOD 3–10KTL3-XH manual's insulation, residual-current or neutral-to-earth checks under safe isolation. Rectify the cause before returning the system to service; this remedy does not cover the legacy named label.

    Remedy sourceMOD XH manual

    Manufacturer / escalation handoff
  • 205 · PV boost driver abnormal

    PV boost driver abnormal

    MOD XH warning 205: the inverter detected an abnormal condition in the PV boost driver.

    Product fit · Family-level · MOD 3–10KTL3-XH

    Show field steps for 205 · PV boost driver abnormal: PV boost driver abnormal

    Product fit

    • MOD 3–10KTL3-XH · Three-phase string inverter

      Family-level · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record warning 205 and the exact inverter model. Do not open the inverter or operate PV equipment to investigate it; contact the installer if the warning remains.

    Installer remedy

    For a MOD 3–10KTL3-XH displaying warning 205, follow the exact model procedure for one controlled restart. If the PV boost-driver warning remains, stop and escalate to Growatt support rather than inferring a string-side repair.

    Remedy sourceMOD XH manual

    Manufacturer / escalation handoff
  • 300 · AC V Outrange

    Grid voltage out of range

    MOD XH: the grid voltage is outside the configured operating range. Legacy TL/MTL units use the named AC V Outrange message.

    Product fit · Family-level · MOD 3–10KTL3-XH

    Show field steps for 300 · AC V Outrange: Grid voltage out of range

    Product fit

    • MOD 3–10KTL3-XH · Three-phase string inverter

      Family-level · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the event and whether the premises supply appears normal. Do not change the grid profile or operate solar isolators; contact the installer if it repeats.

    Installer remedy

    Check the grid condition, AC connection and approved settings using the MOD 3–10KTL3-XH manual. Preserve the grid profile and escalate a confirmed supply issue through the network process.

    Remedy sourceMOD XH manual

    Manufacturer / escalation handoff
  • 302 · No AC Connection

    No AC connection

    The inverter cannot detect an acceptable grid connection.

    Product fit · Family-level · MOD 3–10KTL3-XH

    Show field steps for 302 · No AC Connection: No AC connection

    Product fit

    • MOD 3–10KTL3-XH · Three-phase string inverter

      Family-level · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the event and whether the premises supply appears normal. Do not change the grid profile or operate solar isolators; contact the installer if it repeats.

    Installer remedy

    Check the grid condition, AC connection and approved settings using the MOD 3–10KTL3-XH manual. Preserve the grid profile and escalate a confirmed supply issue through the network process.

    Remedy sourceMOD XH manual

    Manufacturer / escalation handoff
  • 303

    Neutral-to-earth abnormal

    MOD XH: the inverter detected an abnormal neutral-to-earth condition (NE abnormal). This code is not labelled PE Abnormal in the reviewed MOD XH manual.

    Product fit · Family-level · MOD 3–10KTL3-XH

    Show field steps for 303: Neutral-to-earth abnormal

    Product fit

    • MOD 3–10KTL3-XH · Three-phase string inverter

      Family-level · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the code, time and weather conditions. Do not reset the inverter, touch PV wiring or operate isolators; arrange a licensed inspection if the event persists or returns.

    Installer remedy

    Apply the MOD 3–10KTL3-XH manual's insulation, residual-current or neutral-to-earth checks under safe isolation. Rectify the cause before returning the system to service; this remedy does not cover the legacy named label.

    Remedy sourceMOD XH manual

    Manufacturer / escalation handoff
  • 304 · AC F Outrange

    Grid frequency out of range

    MOD XH: the grid frequency is outside the configured operating range. Legacy TL/MTL units use the named AC F Outrange message.

    Product fit · Family-level · MOD 3–10KTL3-XH

    Show field steps for 304 · AC F Outrange: Grid frequency out of range

    Product fit

    • MOD 3–10KTL3-XH · Three-phase string inverter

      Family-level · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the event and whether the premises supply appears normal. Do not change the grid profile or operate solar isolators; contact the installer if it repeats.

    Installer remedy

    Check the grid condition, AC connection and approved settings using the MOD 3–10KTL3-XH manual. Preserve the grid profile and escalate a confirmed supply issue through the network process.

    Remedy sourceMOD XH manual

    Manufacturer / escalation handoff
  • 408 · Over Temperature

    Over temperature

    The inverter temperature exceeded its operating limit.

    Product fit · Family-level · MOD 3–10KTL3-XH

    Show field steps for 408 · Over Temperature: Over temperature

    Product fit

    • MOD 3–10KTL3-XH · Three-phase string inverter

      Family-level · AU/region not confirmed · Firmware not documented

    Safe checks now

    From a safe position, keep the inverter area clear and note direct sun, abnormal heat or visibly blocked airflow. Do not open the enclosure; contact the installer if it remains.

    Installer remedy

    Check the MOD 3–10KTL3-XH installation clearances, ventilation and ambient conditions. Escalate if the inverter continues to report over-temperature in normal conditions.

    Remedy sourceMOD XH manual

    Manufacturer / escalation handoff
  • Output High DCI

    Output DC injection high

    Legacy TL/MTL family: the measured DC component of the AC output exceeded the permitted value.

  • Auto Test Failed

    Auto-test failed

    Legacy TL/MTL family: the automatic grid-protection test used for the Italy configuration did not pass.

Sources

Continue this work

Did this help you move the job forward?

Tell us what is missing
Good to know

Frequently asked

Where do these Growatt fault codes come from?
Compiled from publicly available Growatt inverter and battery documentation and field references, then rewritten for the trade. Wattbench is independent and not affiliated with Growatt.
Which of these can I clear on site?
Some clear on their own once grid or environmental conditions return to normal. Anything involving DC isolation, AC switching, wiring or opening the unit is licensed electrical work. Isolate safely, follow AS/NZS 5033 and AS/NZS 3000 procedure and use appropriate PPE before touching a live system.
The exact code isn't listed. Why not?
Firmware and model variants differ, and manufacturers revise their code tables. We document the most common ones; for a variant that isn't here, check the unit's current manual or the manufacturer's service portal.
How current is this reference?
This reference was last reviewed on 3 August 2026. We revise entries when the underlying manufacturer documentation changes.