Sofar Inverter Error Codes

Legacy Sofar ME3000SP ID codes anchored to the official manual, without inferring the same remedies for HYD or later inverter families.

Sources listedReviewed August 2026Source: Official manufacturer manual; legacy-family scopeOur methodology

46 of 46 codes

About this fault librarySources · scope

This library is now anchored to the official ME3000SP manual. Sofar products reuse ID-style alarms, but numbering and meaning can shift between ME3000SP, HYD ES/EP and later string or storage families. Do not transfer an ME3000SP remedy to another family without its exact manual; those applicability fields remain deliberately blank. Safety note: owners should stop at recording the code, app status and safely visible conditions. DC/AC isolation, electrical measurements, opening equipment, firmware work and protection-setting changes are licensed-worker tasks. Any shutdown or restart must follow the procedure for the exact model and site; do not use this library as a switching sequence.

Key takeaways
  • 46 Sofar Solar (Shenzhen SOFARSOLAR): legacy ME3000SP retrofit inverter fault and alarm codes, documented for the trade.
  • Compiled from published documentation and field references; Wattbench is independent and not affiliated with Sofar Solar (Shenzhen SOFARSOLAR): legacy ME3000SP retrofit inverter.
  • Codes involving DC/AC isolation, wiring or opening the unit are licensed electrical work. Isolate safely and follow AS/NZS procedure.

Resolution text is manufacturer/service context, not permission for an owner to perform electrical work. Stop at visible observations unless the exact product instructions identify an owner control. Isolation, configuration, testing, opening equipment and wiring are for an appropriately licensed worker and, where required, an SAA-accredited person. Where a card says Product fit is unknown, treat it as brand-level guidance and confirm the exact model, role, regional variant, firmware and current manual before acting.

  • ID01

    GridOVP

    The grid (mains) voltage measured by the inverter is too high, above the safe range the inverter is set to operate within.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID01: GridOVP

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the code, time and whether the premises supply appears normal. Do not change grid settings; contact the installer if the event persists or repeats.

    Installer remedy

    Check the grid condition and AC circuit against the ME3000SP manual. Protection points may be changed only after approval from the local network operator; escalate to SOFAR if the event repeats.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID02

    GridUVP

    The grid (mains) voltage measured by the inverter is too low.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID02: GridUVP

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the code, time and whether the premises supply appears normal. Do not change grid settings; contact the installer if the event persists or repeats.

    Installer remedy

    Check the grid condition and AC circuit against the ME3000SP manual. Protection points may be changed only after approval from the local network operator; escalate to SOFAR if the event repeats.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID03

    GridOFP

    The grid (mains) frequency measured by the inverter is too high.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID03: GridOFP

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the code, time and whether the premises supply appears normal. Do not change grid settings; contact the installer if the event persists or repeats.

    Installer remedy

    Check the grid condition and AC circuit against the ME3000SP manual. Protection points may be changed only after approval from the local network operator; escalate to SOFAR if the event repeats.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID04

    GridUFP

    The grid (mains) frequency measured by the inverter is too low.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID04: GridUFP

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the code, time and whether the premises supply appears normal. Do not change grid settings; contact the installer if the event persists or repeats.

    Installer remedy

    Check the grid condition and AC circuit against the ME3000SP manual. Protection points may be changed only after approval from the local network operator; escalate to SOFAR if the event repeats.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID05

    BatOVP

    The inverter is measuring too high a voltage from the battery (battery overvoltage).

    Product fit · Confirmed · ME3000SP

    Show field steps for ID05: BatOVP

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the exact code, inverter model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer or SOFAR if the event remains.

    Installer remedy

    Follow the ME3000SP troubleshooting procedure for this exact code, including one controlled restart only where the manual directs it. Stop repeated resets and escalate a persistent internal, battery or protection fault to SOFAR.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID09

    HW_LLCBus_OVP

    LLC bus voltage is too high and has triggered hardware protection, an internal inverter fault.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID09: HW_LLCBus_OVP

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the exact code, inverter model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer or SOFAR if the event remains.

    Installer remedy

    Follow the ME3000SP troubleshooting procedure for this exact code, including one controlled restart only where the manual directs it. Stop repeated resets and escalate a persistent internal, battery or protection fault to SOFAR.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID10

    HW_Boost_OVP

    Boost voltage is too high and has triggered hardware protection, an internal inverter fault.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID10: HW_Boost_OVP

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the exact code, inverter model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer or SOFAR if the event remains.

    Installer remedy

    Follow the ME3000SP troubleshooting procedure for this exact code, including one controlled restart only where the manual directs it. Stop repeated resets and escalate a persistent internal, battery or protection fault to SOFAR.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID11

    HwBuckBoostOCP

    Buck-Boost current is too high and has triggered hardware protection, an internal inverter fault.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID11: HwBuckBoostOCP

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the exact code, inverter model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer or SOFAR if the event remains.

    Installer remedy

    Follow the ME3000SP troubleshooting procedure for this exact code, including one controlled restart only where the manual directs it. Stop repeated resets and escalate a persistent internal, battery or protection fault to SOFAR.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID12

    HwBatOCP

    The battery current is too high and has triggered hardware protection.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID12: HwBatOCP

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the exact code, inverter model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer or SOFAR if the event remains.

    Installer remedy

    Follow the ME3000SP troubleshooting procedure for this exact code, including one controlled restart only where the manual directs it. Stop repeated resets and escalate a persistent internal, battery or protection fault to SOFAR.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID15

    HwAcOCP

    The grid (AC) current is too high and has triggered hardware protection.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID15: HwAcOCP

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the exact code, inverter model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer or SOFAR if the event remains.

    Installer remedy

    Follow the ME3000SP troubleshooting procedure for this exact code, including one controlled restart only where the manual directs it. Stop repeated resets and escalate a persistent internal, battery or protection fault to SOFAR.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID17

    HwADFaultIGrid

    Internal A/D sampling fault on the grid current channel.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID17: HwADFaultIGrid

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the exact code, inverter model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer or SOFAR if the event remains.

    Installer remedy

    Follow the ME3000SP troubleshooting procedure for this exact code, including one controlled restart only where the manual directs it. Stop repeated resets and escalate a persistent internal, battery or protection fault to SOFAR.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID19

    HwADFaultVGrid

    Internal A/D sampling fault on the grid voltage channel.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID19: HwADFaultVGrid

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the exact code, inverter model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer or SOFAR if the event remains.

    Installer remedy

    Follow the ME3000SP troubleshooting procedure for this exact code, including one controlled restart only where the manual directs it. Stop repeated resets and escalate a persistent internal, battery or protection fault to SOFAR.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID27

    BatOCP

    The inverter is measuring too much current from the batteries (battery overcurrent).

    Product fit · Confirmed · ME3000SP

    Show field steps for ID27: BatOCP

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the exact code, inverter model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer or SOFAR if the event remains.

    Installer remedy

    Follow the ME3000SP troubleshooting procedure for this exact code, including one controlled restart only where the manual directs it. Stop repeated resets and escalate a persistent internal, battery or protection fault to SOFAR.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID29

    SwOCPInstan

    Software-detected instantaneous AC overcurrent. The grid current is too high.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID29: SwOCPInstan

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the exact code, inverter model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer or SOFAR if the event remains.

    Installer remedy

    Follow the ME3000SP troubleshooting procedure for this exact code, including one controlled restart only where the manual directs it. Stop repeated resets and escalate a persistent internal, battery or protection fault to SOFAR.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID30

    BuckOCP

    Buck circuit current is too high.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID30: BuckOCP

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the exact code, inverter model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer or SOFAR if the event remains.

    Installer remedy

    Follow the ME3000SP troubleshooting procedure for this exact code, including one controlled restart only where the manual directs it. Stop repeated resets and escalate a persistent internal, battery or protection fault to SOFAR.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID31

    AcRmsOCP

    The AC output current (RMS) is too high.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID31: AcRmsOCP

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the exact code, inverter model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer or SOFAR if the event remains.

    Installer remedy

    Follow the ME3000SP troubleshooting procedure for this exact code, including one controlled restart only where the manual directs it. Stop repeated resets and escalate a persistent internal, battery or protection fault to SOFAR.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID49

    ConsistentFault_VGrid

    Grid-voltage consistency fault. The two independent voltage measurements disagree.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID49: ConsistentFault_VGrid

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the exact code, inverter model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer or SOFAR if the event remains.

    Installer remedy

    Follow the ME3000SP troubleshooting procedure for this exact code, including one controlled restart only where the manual directs it. Stop repeated resets and escalate a persistent internal, battery or protection fault to SOFAR.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID50

    ConsistentFault_FGrid

    Grid-frequency consistency fault. The two independent frequency measurements disagree.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID50: ConsistentFault_FGrid

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the exact code, inverter model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer or SOFAR if the event remains.

    Installer remedy

    Follow the ME3000SP troubleshooting procedure for this exact code, including one controlled restart only where the manual directs it. Stop repeated resets and escalate a persistent internal, battery or protection fault to SOFAR.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID53

    SpiCommLose

    SPI internal communication lost between control boards.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID53: SpiCommLose

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the exact code, inverter model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer or SOFAR if the event remains.

    Installer remedy

    Follow the ME3000SP troubleshooting procedure for this exact code, including one controlled restart only where the manual directs it. Stop repeated resets and escalate a persistent internal, battery or protection fault to SOFAR.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID54

    SciCommLose

    SCI communication fault between the control and communication boards.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID54: SciCommLose

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the exact code, inverter model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer or SOFAR if the event remains.

    Installer remedy

    Follow the ME3000SP troubleshooting procedure for this exact code, including one controlled restart only where the manual directs it. Stop repeated resets and escalate a persistent internal, battery or protection fault to SOFAR.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID57

    OverTempFault_BAT

    Battery temperature is too high.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID57: OverTempFault_BAT

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    From a safe position, keep the equipment area clear and note any obvious heat source or blocked airflow. Do not open equipment or change charge settings; contact the installer if it remains.

    Installer remedy

    Check the ME3000SP or connected-battery ventilation and ambient conditions described by the manual. Review battery current settings only where the exact battery specification permits it, then escalate persistent alarms to SOFAR.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID58

    OverTempFault_HeatSink

    The inverter heatsink temperature is too high (inverter overheating).

    Product fit · Confirmed · ME3000SP

    Show field steps for ID58: OverTempFault_HeatSink

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    From a safe position, keep the equipment area clear and note any obvious heat source or blocked airflow. Do not open equipment or change charge settings; contact the installer if it remains.

    Installer remedy

    Check the ME3000SP or connected-battery ventilation and ambient conditions described by the manual. Review battery current settings only where the exact battery specification permits it, then escalate persistent alarms to SOFAR.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID59

    OverTempFault_Env

    The ambient/environmental temperature around the inverter is too high.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID59: OverTempFault_Env

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    From a safe position, keep the equipment area clear and note any obvious heat source or blocked airflow. Do not open equipment or change charge settings; contact the installer if it remains.

    Installer remedy

    Check the ME3000SP or connected-battery ventilation and ambient conditions described by the manual. Review battery current settings only where the exact battery specification permits it, then escalate persistent alarms to SOFAR.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID66

    unrecoverBusOVP

    Bus voltage is too high and has caused an unrecoverable fault.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID66: unrecoverBusOVP

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the exact code, inverter model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer or SOFAR if the event remains.

    Installer remedy

    Follow the ME3000SP troubleshooting procedure for this exact code, including one controlled restart only where the manual directs it. Stop repeated resets and escalate a persistent internal, battery or protection fault to SOFAR.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID67

    BitEPSunrecover

    Unrecoverable battery overcurrent fault while operating in EPS (backup) mode.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID67: BitEPSunrecover

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the exact code, inverter model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer or SOFAR if the event remains.

    Installer remedy

    Follow the ME3000SP troubleshooting procedure for this exact code, including one controlled restart only where the manual directs it. Stop repeated resets and escalate a persistent internal, battery or protection fault to SOFAR.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID75

    unrecoverEEPROM_W

    Unrecoverable EEPROM write fault, internal memory error.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID75: unrecoverEEPROM_W

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the exact code, inverter model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer or SOFAR if the event remains.

    Installer remedy

    Follow the ME3000SP troubleshooting procedure for this exact code, including one controlled restart only where the manual directs it. Stop repeated resets and escalate a persistent internal, battery or protection fault to SOFAR.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID76

    unrecoverEEPROM_R

    Unrecoverable EEPROM read fault, internal memory error.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID76: unrecoverEEPROM_R

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the exact code, inverter model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer or SOFAR if the event remains.

    Installer remedy

    Follow the ME3000SP troubleshooting procedure for this exact code, including one controlled restart only where the manual directs it. Stop repeated resets and escalate a persistent internal, battery or protection fault to SOFAR.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID81

    Over temperature

    The ambient temperature around the inverter is too hot.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID81: Over temperature

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    From a safe position, keep the equipment area clear and note any obvious heat source or blocked airflow. Do not open equipment or change charge settings; contact the installer if it remains.

    Installer remedy

    Check the ME3000SP or connected-battery ventilation and ambient conditions described by the manual. Review battery current settings only where the exact battery specification permits it, then escalate persistent alarms to SOFAR.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID82

    Over frequency

    The grid (mains) frequency measured by the inverter is too high.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID82: Over frequency

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the code, time and whether the premises supply appears normal. Do not change grid settings; contact the installer if the event persists or repeats.

    Installer remedy

    Check the grid condition and AC circuit against the ME3000SP manual. Protection points may be changed only after approval from the local network operator; escalate to SOFAR if the event repeats.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID83

    Long dist Load Shedding

    The inverter has received a remote command to decrease its power output.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID83: Long dist Load Shedding

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the remote-control event and system state. Do not override controls or operate isolators; contact the installer if the command is unexpected or does not clear.

    Installer remedy

    Confirm the source and intended state of the remote load-shedding or shutdown command in the ME3000SP controls. Correct the external command path rather than treating this as an internal fault.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID84

    Long dist Off

    The inverter has received a remote command to turn off.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID84: Long dist Off

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the remote-control event and system state. Do not override controls or operate isolators; contact the installer if the command is unexpected or does not clear.

    Installer remedy

    Confirm the source and intended state of the remote load-shedding or shutdown command in the ME3000SP controls. Correct the external command path rather than treating this as an internal fault.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID85

    SOC is greater or equal to DOD or Battery voltage is low

    The inverter has stopped discharging because the user-set depth-of-discharge (DOD) limit has been reached or the battery voltage is too low.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID85: SOC is greater or equal to DOD or Battery voltage is low

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the code and allow the battery to recharge under its normal configured mode. Do not alter depth-of-discharge, voltage or charge settings; contact the installer if it recurs.

    Installer remedy

    Check battery state, configured limits and charging availability against the ME3000SP and battery documentation. Preserve the protection limits and escalate an abnormal or recurring low-voltage condition.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID86

    Bat Voltage Low Shut

    The inverter has shut down to protect the batteries because the battery voltage is too low.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID86: Bat Voltage Low Shut

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the code and allow the battery to recharge under its normal configured mode. Do not alter depth-of-discharge, voltage or charge settings; contact the installer if it recurs.

    Installer remedy

    Check battery state, configured limits and charging availability against the ME3000SP and battery documentation. Preserve the protection limits and escalate an abnormal or recurring low-voltage condition.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID94

    Software Version Is Not Consistent

    The firmware/software versions on the inverter's boards are not consistent and require updating.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID94: Software Version Is Not Consistent

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the exact code, inverter model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer or SOFAR if the event remains.

    Installer remedy

    Follow the ME3000SP troubleshooting procedure for this exact code, including one controlled restart only where the manual directs it. Stop repeated resets and escalate a persistent internal, battery or protection fault to SOFAR.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID95

    CommEEPROMFault

    The communication board EEPROM is faulty.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID95: CommEEPROMFault

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the exact code, inverter model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer or SOFAR if the event remains.

    Installer remedy

    Follow the ME3000SP troubleshooting procedure for this exact code, including one controlled restart only where the manual directs it. Stop repeated resets and escalate a persistent internal, battery or protection fault to SOFAR.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID96

    RTCFault

    Real-time clock (RTC) fault on the inverter.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID96: RTCFault

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the exact code, inverter model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer or SOFAR if the event remains.

    Installer remedy

    Follow the ME3000SP troubleshooting procedure for this exact code, including one controlled restart only where the manual directs it. Stop repeated resets and escalate a persistent internal, battery or protection fault to SOFAR.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID97

    InValidCountry

    The inverter's country code / grid-protection settings are invalid or need to be reset.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID97: InValidCountry

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the exact code, inverter model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer or SOFAR if the event remains.

    Installer remedy

    Follow the ME3000SP troubleshooting procedure for this exact code, including one controlled restart only where the manual directs it. Stop repeated resets and escalate a persistent internal, battery or protection fault to SOFAR.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID98

    SDfault

    SD card fault. The card needs replacement.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID98: SDfault

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the exact code, inverter model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer or SOFAR if the event remains.

    Installer remedy

    Follow the ME3000SP troubleshooting procedure for this exact code, including one controlled restart only where the manual directs it. Stop repeated resets and escalate a persistent internal, battery or protection fault to SOFAR.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID100

    BatOCD

    Battery overcurrent fault during discharge.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID100: BatOCD

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the exact code, inverter model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer or SOFAR if the event remains.

    Installer remedy

    Follow the ME3000SP troubleshooting procedure for this exact code, including one controlled restart only where the manual directs it. Stop repeated resets and escalate a persistent internal, battery or protection fault to SOFAR.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID101

    BatSCD

    Battery overcurrent fault during charging.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID101: BatSCD

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the exact code, inverter model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer or SOFAR if the event remains.

    Installer remedy

    Follow the ME3000SP troubleshooting procedure for this exact code, including one controlled restart only where the manual directs it. Stop repeated resets and escalate a persistent internal, battery or protection fault to SOFAR.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID102

    BatOV

    Battery overvoltage fault.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID102: BatOV

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the exact code, inverter model and time. Do not repeatedly restart the inverter, operate isolators or open equipment; contact the installer or SOFAR if the event remains.

    Installer remedy

    Follow the ME3000SP troubleshooting procedure for this exact code, including one controlled restart only where the manual directs it. Stop repeated resets and escalate a persistent internal, battery or protection fault to SOFAR.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID103

    BatUV

    Battery undervoltage fault.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID103: BatUV

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the code and allow the battery to recharge under its normal configured mode. Do not alter depth-of-discharge, voltage or charge settings; contact the installer if it recurs.

    Installer remedy

    Check battery state, configured limits and charging availability against the ME3000SP and battery documentation. Preserve the protection limits and escalate an abnormal or recurring low-voltage condition.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID104

    BatOTD

    Battery high-temperature protection while discharging.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID104: BatOTD

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    From a safe position, keep the equipment area clear and note any obvious heat source or blocked airflow. Do not open equipment or change charge settings; contact the installer if it remains.

    Installer remedy

    Check the ME3000SP or connected-battery ventilation and ambient conditions described by the manual. Review battery current settings only where the exact battery specification permits it, then escalate persistent alarms to SOFAR.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID105

    BatOTC

    Battery high-temperature protection while charging.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID105: BatOTC

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    From a safe position, keep the equipment area clear and note any obvious heat source or blocked airflow. Do not open equipment or change charge settings; contact the installer if it remains.

    Installer remedy

    Check the ME3000SP or connected-battery ventilation and ambient conditions described by the manual. Review battery current settings only where the exact battery specification permits it, then escalate persistent alarms to SOFAR.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID106

    BatUTD

    Battery low-temperature protection while discharging.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID106: BatUTD

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    From a safe position, keep the equipment area clear and note any obvious heat source or blocked airflow. Do not open equipment or change charge settings; contact the installer if it remains.

    Installer remedy

    Check the ME3000SP or connected-battery ventilation and ambient conditions described by the manual. Review battery current settings only where the exact battery specification permits it, then escalate persistent alarms to SOFAR.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff
  • ID107

    BatUTC

    Battery low-temperature protection while charging.

    Product fit · Confirmed · ME3000SP

    Show field steps for ID107: BatUTC

    Product fit

    • ME3000SP · AC-coupled inverter

      Confirmed · AU/region not confirmed · Firmware not documented

    Safe checks now

    From a safe position, keep the equipment area clear and note any obvious heat source or blocked airflow. Do not open equipment or change charge settings; contact the installer if it remains.

    Installer remedy

    Check the ME3000SP or connected-battery ventilation and ambient conditions described by the manual. Review battery current settings only where the exact battery specification permits it, then escalate persistent alarms to SOFAR.

    Remedy sourceME3000SP manual

    Manufacturer / escalation handoff

Sources

Continue this work

Did this help you move the job forward?

Tell us what is missing
Good to know

Frequently asked

Where do these Sofar fault codes come from?
Compiled from publicly available Sofar inverter and battery documentation and field references, then rewritten for the trade. Wattbench is independent and not affiliated with Sofar.
Which of these can I clear on site?
Some clear on their own once grid or environmental conditions return to normal. Anything involving DC isolation, AC switching, wiring or opening the unit is licensed electrical work. Isolate safely, follow AS/NZS 5033 and AS/NZS 3000 procedure and use appropriate PPE before touching a live system.
The exact code isn't listed. Why not?
Firmware and model variants differ, and manufacturers revise their code tables. We document the most common ones; for a variant that isn't here, check the unit's current manual or the manufacturer's service portal.
How current is this reference?
This reference was last reviewed on 2 August 2026. We revise entries when the underlying manufacturer documentation changes.