wattbench
Inverter Fault Library

Huawei Inverter Error Codes

Huawei SUN2000 alarm reference with audience-separated, source-linked remedies for current M2 and M3 families; broader residential and backup codes remain explicitly unverified for those families.

Sources listedReviewed August 2026Source: Manufacturer documentationOur methodology

35 of 35 codes

About this fault librarySources · scope

A reference compiled by Wattbench from publicly available Huawei inverter documentation. Source-linked homeowner and installer remedies are reviewed against the Australian SUN2000-(8KTL–20KTL)-M2 and SUN2000-(20KTL–40KTL)-M3 manuals. The remaining residential, battery, backup and scheduling codes stay searchable as broader SUN2000 reference without inheriting M2/M3 applicability. Safety note: anything involving DC isolators, AC switches, wiring, electrical measurements or opening the unit is licensed-electrician work. If in doubt, record the alarm and contact your installer.

Key takeaways
  • 35 Huawei (SUN2000 series) fault and alarm codes, documented for the trade.
  • Compiled from published documentation and field references; Wattbench is independent and not affiliated with Huawei (SUN2000 series).
  • Codes involving DC/AC isolation, wiring or opening the unit are licensed electrical work. Isolate safely and follow AS/NZS procedure.

Resolution text is manufacturer/service context, not permission for an owner to perform electrical work. Stop at visible observations unless the exact product instructions identify an owner control. Isolation, configuration, testing, opening equipment and wiring are for an appropriately licensed worker and, where required, an SAA-accredited person. Where a card says Product fit is unknown, treat it as brand-level guidance and confirm the exact model, role, regional variant, firmware and current manual before acting.

  • 2001

    High string input voltage

    Open-circuit voltage exceeds the maximum input voltage.

    Product fit · Confirmed · 2 documented families

    Show field steps for 2001: High string input voltage

    Product fit

    • SUN2000-(8KTL–20KTL)-M2 · Three-phase string inverter

      Confirmed · Manual Issue 06 · AU/region not confirmed · Firmware not documented

    • SUN2000-(20KTL–40KTL)-M3 · Three-phase string inverter

      Confirmed · Manual Issue 02 · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the alarm and cause ID if shown, leave PV, AC and earthing wiring and isolators untouched, and contact the installer. Electrical measurements and recovery work require a licensed worker.

    Installer remedy

    A licensed installer should check the number of PV modules connected in series in the PV string, and ensure the string open-circuit voltage is no greater than the maximum operating voltage. Once the PV array is correctly configured, the alarm clears automatically.

    Remedy sourceSUN2000 M2 manualSUN2000 M3 manual

    Manufacturer / escalation handoff
  • 2002

    DC arc fault

    The PV string power cable arcs or is in poor contact. Cause ID 1 = PV1, Cause ID 2 = PV2.

    Product fit · Confirmed · 2 documented families

    Show field steps for 2002: DC arc fault

    Product fit

    • SUN2000-(8KTL–20KTL)-M2 · Three-phase string inverter

      Confirmed · Manual Issue 06 · AU/region not confirmed · Firmware not documented

    • SUN2000-(20KTL–40KTL)-M3 · Three-phase string inverter

      Confirmed · Manual Issue 02 · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the alarm and cause ID if shown, leave PV, AC and earthing wiring and isolators untouched, and contact the installer. Electrical measurements and recovery work require a licensed worker.

    Installer remedy

    A licensed installer should check whether the string cables arc or are in poor contact.

    Remedy sourceSUN2000 M2 manualSUN2000 M3 manual

    Manufacturer / escalation handoff
  • 2003

    DC arc fault

    The PV string power cable arcs or is in poor contact. Cause ID 1 = PV1, Cause ID 2 = PV2.

    Product fit · Confirmed · SUN2000-(20KTL–40KTL)-M3

    Show field steps for 2003: DC arc fault

    Product fit

    • SUN2000-(20KTL–40KTL)-M3 · Three-phase string inverter

      Confirmed · Manual Issue 02 · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the alarm and cause ID if shown, leave PV, AC and earthing wiring and isolators untouched, and contact the installer. Electrical measurements and recovery work require a licensed worker.

    Installer remedy

    A licensed installer should check whether the string cables arc or are in poor contact.

    Remedy sourceSUN2000 M3 manual

    Manufacturer / escalation handoff
  • 2011

    String reversed

    The PV string is reverse-connected. Cause ID 1 = PV1, Cause ID 2 = PV2.

    Product fit · Confirmed · 2 documented families

    Show field steps for 2011: String reversed

    Product fit

    • SUN2000-(8KTL–20KTL)-M2 · Three-phase string inverter

      Confirmed · Manual Issue 06 · AU/region not confirmed · Firmware not documented

    • SUN2000-(20KTL–40KTL)-M3 · Three-phase string inverter

      Confirmed · Manual Issue 02 · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the alarm and cause ID if shown, leave PV, AC and earthing wiring and isolators untouched, and contact the installer. Electrical measurements and recovery work require a licensed worker.

    Installer remedy

    A licensed installer should check whether the PV string is reverse-connected to the inverter.

    Remedy sourceSUN2000 M2 manualSUN2000 M3 manual

    Manufacturer / escalation handoff
  • 2012

    String current back-feed

    Only a few PV modules are connected in series in the string, so its end voltage is lower than the other strings. Cause ID 1 = PV1, Cause ID 2 = PV2.

    Product fit · Confirmed · 2 documented families

    Show field steps for 2012: String current back-feed

    Product fit

    • SUN2000-(8KTL–20KTL)-M2 · Three-phase string inverter

      Confirmed · Manual Issue 06 · AU/region not confirmed · Firmware not documented

    • SUN2000-(20KTL–40KTL)-M3 · Three-phase string inverter

      Confirmed · Manual Issue 02 · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the alarm and cause ID if shown, leave PV, AC and earthing wiring and isolators untouched, and contact the installer. Electrical measurements and recovery work require a licensed worker.

    Installer remedy

    A licensed installer should compare the module count with parallel strings, check for shading, and verify the string open-circuit voltage. Any reconfiguration must follow the exact model procedure and only occur after the circuit is made safe.

    Remedy sourceSUN2000 M2 manualSUN2000 M3 manual

    Manufacturer / escalation handoff
  • 2021

    AFCI check failure

    The AFCI self-check fails. Either the AFCI check circuit is abnormal, or the AFCI circuit is faulty.

    Product fit · Confirmed · 2 documented families

    Show field steps for 2021: AFCI check failure

    Product fit

    • SUN2000-(8KTL–20KTL)-M2 · Three-phase string inverter

      Confirmed · Manual Issue 06 · AU/region not confirmed · Firmware not documented

    • SUN2000-(20KTL–40KTL)-M3 · Three-phase string inverter

      Confirmed · Manual Issue 02 · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the alarm and cause ID if shown, leave PV, AC and earthing wiring and isolators untouched, and contact the installer. Electrical measurements and recovery work require a licensed worker.

    Installer remedy

    A licensed installer should follow the exact M2 or M3 manual's controlled diagnostic and recovery procedure for this alarm. Do not substitute a generic switching sequence; if the alarm persists after the documented check, preserve the event evidence and escalate to Huawei support.

    Remedy sourceSUN2000 M2 manualSUN2000 M3 manual

    Manufacturer / escalation handoff
  • 2031

    Phase wire short-circuit to PE

    The impedance of the output phase wire is low, or it is short-circuited to PE.

    Product fit · Confirmed · 2 documented families

    Show field steps for 2031: Phase wire short-circuit to PE

    Product fit

    • SUN2000-(8KTL–20KTL)-M2 · Three-phase string inverter

      Confirmed · Manual Issue 06 · AU/region not confirmed · Firmware not documented

    • SUN2000-(20KTL–40KTL)-M3 · Three-phase string inverter

      Confirmed · Manual Issue 02 · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the alarm and cause ID if shown, leave PV, AC and earthing wiring and isolators untouched, and contact the installer. Electrical measurements and recovery work require a licensed worker.

    Installer remedy

    A licensed installer should check the impedance of the output phase wire to PE, locate the position with low impedance, and restore it.

    Remedy sourceSUN2000 M2 manualSUN2000 M3 manual

    Manufacturer / escalation handoff
  • 2032

    Grid failure

    The grid is experiencing an outage, the AC circuit is disconnected, or the AC switch is off.

    Product fit · Confirmed · 2 documented families

    Show field steps for 2032: Grid failure

    Product fit

    • SUN2000-(8KTL–20KTL)-M2 · Three-phase string inverter

      Confirmed · Manual Issue 06 · AU/region not confirmed · Firmware not documented

    • SUN2000-(20KTL–40KTL)-M3 · Three-phase string inverter

      Confirmed · Manual Issue 02 · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the alarm, cause ID if shown, and time; check only whether the property has grid supply and allow the inverter to recover. If it repeats, contact the installer; do not change protected grid settings.

    Installer remedy

    Check whether grid supply is available and record the switch states without operating them. If supply is present, a licensed installer should verify the AC cable and switch connection.

    Remedy sourceSUN2000 M2 manualSUN2000 M3 manual

    Manufacturer / escalation handoff
  • 2033

    Grid under-voltage

    The grid voltage is below the lower threshold, or the under-voltage duration exceeds the value specified by LVRT.

    Product fit · Confirmed · 2 documented families

    Show field steps for 2033: Grid under-voltage

    Product fit

    • SUN2000-(8KTL–20KTL)-M2 · Three-phase string inverter

      Confirmed · Manual Issue 06 · AU/region not confirmed · Firmware not documented

    • SUN2000-(20KTL–40KTL)-M3 · Three-phase string inverter

      Confirmed · Manual Issue 02 · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the alarm, cause ID if shown, and time; check only whether the property has grid supply and allow the inverter to recover. If it repeats, contact the installer; do not change protected grid settings.

    Installer remedy

    The inverter normally recovers when the grid returns to range. If repeated, the installer should verify the measured voltage and AC connection; contact the network operator if supply is out of range. Change protection settings only with network approval.

    Remedy sourceSUN2000 M2 manualSUN2000 M3 manual

    Manufacturer / escalation handoff
  • 2034

    Grid over-voltage

    The grid voltage is above the upper threshold, or the over-voltage duration exceeds the value specified by HVRT.

    Product fit · Confirmed · 2 documented families

    Show field steps for 2034: Grid over-voltage

    Product fit

    • SUN2000-(8KTL–20KTL)-M2 · Three-phase string inverter

      Confirmed · Manual Issue 06 · AU/region not confirmed · Firmware not documented

    • SUN2000-(20KTL–40KTL)-M3 · Three-phase string inverter

      Confirmed · Manual Issue 02 · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the alarm, cause ID if shown, and time; check only whether the property has grid supply and allow the inverter to recover. If it repeats, contact the installer; do not change protected grid settings.

    Installer remedy

    The inverter normally recovers when the grid returns to range. If repeated, the installer should verify the voltage at the grid connection point and contact the network operator if it is out of range. Change protection settings only with network approval.

    Remedy sourceSUN2000 M2 manualSUN2000 M3 manual

    Manufacturer / escalation handoff
  • 2035

    Unbalanced grid voltage

    The difference between grid phase voltages exceeds the upper threshold.

    Product fit · Confirmed · 2 documented families

    Show field steps for 2035: Unbalanced grid voltage

    Product fit

    • SUN2000-(8KTL–20KTL)-M2 · Three-phase string inverter

      Confirmed · Manual Issue 06 · AU/region not confirmed · Firmware not documented

    • SUN2000-(20KTL–40KTL)-M3 · Three-phase string inverter

      Confirmed · Manual Issue 02 · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the alarm, cause ID if shown, and time; check only whether the property has grid supply and allow the inverter to recover. If it repeats, contact the installer; do not change protected grid settings.

    Installer remedy

    The inverter normally recovers when the grid returns to range. If repeated, a licensed installer should verify the phase voltages and AC output cables, then escalate an out-of-range supply to the network operator.

    Remedy sourceSUN2000 M2 manualSUN2000 M3 manual

    Manufacturer / escalation handoff
  • 2036

    Grid over-frequency

    Grid exception: the actual grid frequency is higher than the local grid standard allows.

    Product fit · Confirmed · 2 documented families

    Show field steps for 2036: Grid over-frequency

    Product fit

    • SUN2000-(8KTL–20KTL)-M2 · Three-phase string inverter

      Confirmed · Manual Issue 06 · AU/region not confirmed · Firmware not documented

    • SUN2000-(20KTL–40KTL)-M3 · Three-phase string inverter

      Confirmed · Manual Issue 02 · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the alarm, cause ID if shown, and time; check only whether the property has grid supply and allow the inverter to recover. If it repeats, contact the installer; do not change protected grid settings.

    Installer remedy

    The inverter normally recovers when frequency returns to range. If repeated, verify the event data and contact the network operator if supply is out of range. Change protection settings only with network approval.

    Remedy sourceSUN2000 M2 manualSUN2000 M3 manual

    Manufacturer / escalation handoff
  • 2037

    Grid under-frequency

    Grid exception: the actual grid frequency is lower than the local grid standard requires.

    Product fit · Confirmed · 2 documented families

    Show field steps for 2037: Grid under-frequency

    Product fit

    • SUN2000-(8KTL–20KTL)-M2 · Three-phase string inverter

      Confirmed · Manual Issue 06 · AU/region not confirmed · Firmware not documented

    • SUN2000-(20KTL–40KTL)-M3 · Three-phase string inverter

      Confirmed · Manual Issue 02 · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the alarm, cause ID if shown, and time; check only whether the property has grid supply and allow the inverter to recover. If it repeats, contact the installer; do not change protected grid settings.

    Installer remedy

    The inverter normally recovers when frequency returns to range. If repeated, verify the event data and contact the network operator if supply is out of range. Change protection settings only with network approval.

    Remedy sourceSUN2000 M2 manualSUN2000 M3 manual

    Manufacturer / escalation handoff
  • 2038

    Unstable grid frequency

    Grid exception: the rate of change of grid frequency does not comply with the local grid standard.

    Product fit · Confirmed · 2 documented families

    Show field steps for 2038: Unstable grid frequency

    Product fit

    • SUN2000-(8KTL–20KTL)-M2 · Three-phase string inverter

      Confirmed · Manual Issue 06 · AU/region not confirmed · Firmware not documented

    • SUN2000-(20KTL–40KTL)-M3 · Three-phase string inverter

      Confirmed · Manual Issue 02 · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the alarm, cause ID if shown, and time; check only whether the property has grid supply and allow the inverter to recover. If it repeats, contact the installer; do not change protected grid settings.

    Installer remedy

    The inverter normally recovers when the grid stabilises. If the event repeats, have the installer verify the frequency data and contact the network operator if it is outside range.

    Remedy sourceSUN2000 M2 manualSUN2000 M3 manual

    Manufacturer / escalation handoff
  • 2039

    Output over-current

    The grid voltage drops dramatically or the grid is short-circuited, so the inverter's transient output current exceeds the upper threshold and protection is triggered.

    Product fit · Confirmed · 2 documented families

    Show field steps for 2039: Output over-current

    Product fit

    • SUN2000-(8KTL–20KTL)-M2 · Three-phase string inverter

      Confirmed · Manual Issue 06 · AU/region not confirmed · Firmware not documented

    • SUN2000-(20KTL–40KTL)-M3 · Three-phase string inverter

      Confirmed · Manual Issue 02 · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the alarm, cause ID if shown, and time; check only whether the property has grid supply and allow the inverter to recover. If it repeats, contact the installer; do not change protected grid settings.

    Installer remedy

    The inverter monitors for recovery automatically. If the event repeats or affects production, a licensed installer should check the AC output for a short circuit and contact Huawei support if unresolved.

    Remedy sourceSUN2000 M2 manualSUN2000 M3 manual

    Manufacturer / escalation handoff
  • 2040

    Output DC component over-high

    The DC component of the inverter output current exceeds the specified upper threshold.

    Product fit · Confirmed · 2 documented families

    Show field steps for 2040: Output DC component over-high

    Product fit

    • SUN2000-(8KTL–20KTL)-M2 · Three-phase string inverter

      Confirmed · Manual Issue 06 · AU/region not confirmed · Firmware not documented

    • SUN2000-(20KTL–40KTL)-M3 · Three-phase string inverter

      Confirmed · Manual Issue 02 · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the alarm, cause ID if shown, and time; check only whether the property has grid supply and allow the inverter to recover. If it repeats, contact the installer; do not change protected grid settings.

    Installer remedy

    The inverter monitors for recovery automatically. If the event repeats, contact the installer, dealer or Huawei technical support.

    Remedy sourceSUN2000 M2 manualSUN2000 M3 manual

    Manufacturer / escalation handoff
  • 2051

    Abnormal residual current

    The insulation impedance of the input side to PE decreases while the inverter is operating.

    Product fit · Confirmed · 2 documented families

    Show field steps for 2051: Abnormal residual current

    Product fit

    • SUN2000-(8KTL–20KTL)-M2 · Three-phase string inverter

      Confirmed · Manual Issue 06 · AU/region not confirmed · Firmware not documented

    • SUN2000-(20KTL–40KTL)-M3 · Three-phase string inverter

      Confirmed · Manual Issue 02 · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the alarm and cause ID if shown, leave PV, AC and earthing wiring and isolators untouched, and contact the installer. Electrical measurements and recovery work require a licensed worker.

    Installer remedy

    A transient event may clear automatically. If it repeats or persists, a licensed installer should test the impedance between each PV string and earth and rectify any insulation fault.

    Remedy sourceSUN2000 M2 manualSUN2000 M3 manual

    Manufacturer / escalation handoff
  • 2061

    Abnormal grounding

    The N cable or ground cable is not connected. When a PV array is grounded, the inverter output is not connected to an isolation transformer.

    Product fit · Confirmed · 2 documented families

    Show field steps for 2061: Abnormal grounding

    Product fit

    • SUN2000-(8KTL–20KTL)-M2 · Three-phase string inverter

      Confirmed · Manual Issue 06 · AU/region not confirmed · Firmware not documented

    • SUN2000-(20KTL–40KTL)-M3 · Three-phase string inverter

      Confirmed · Manual Issue 02 · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the alarm and cause ID if shown, leave PV, AC and earthing wiring and isolators untouched, and contact the installer. Electrical measurements and recovery work require a licensed worker.

    Installer remedy

    A licensed installer should power off the inverter using the exact model procedure, verify the PE and neutral connections, and confirm any isolation-transformer configuration before changing the grounding-inspection setting.

    Remedy sourceSUN2000 M2 manualSUN2000 M3 manual

    Manufacturer / escalation handoff
  • 2062

    Low insulation resistance

    The PV array is short-circuited to PE, or the array's environment is damp and insulation between the array and ground is poor.

    Product fit · Confirmed · 2 documented families

    Show field steps for 2062: Low insulation resistance

    Product fit

    • SUN2000-(8KTL–20KTL)-M2 · Three-phase string inverter

      Confirmed · Manual Issue 06 · AU/region not confirmed · Firmware not documented

    • SUN2000-(20KTL–40KTL)-M3 · Three-phase string inverter

      Confirmed · Manual Issue 02 · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the alarm and cause ID if shown, leave PV, AC and earthing wiring and isolators untouched, and contact the installer. Electrical measurements and recovery work require a licensed worker.

    Installer remedy

    A licensed installer should test the impedance between the PV array and PE, locate any short circuit or insulation defect, and verify the inverter PE connection. Do not lower the protection threshold without confirming the exact model requirements and site conditions.

    Remedy sourceSUN2000 M2 manualSUN2000 M3 manual

    Manufacturer / escalation handoff
  • 2063

    Over-temperature

    The inverter is installed in a poorly ventilated location, or the ambient temperature is too high.

    Product fit · Confirmed · 2 documented families

    Show field steps for 2063: Over-temperature

    Product fit

    • SUN2000-(8KTL–20KTL)-M2 · Three-phase string inverter

      Confirmed · Manual Issue 06 · AU/region not confirmed · Firmware not documented

    • SUN2000-(20KTL–40KTL)-M3 · Three-phase string inverter

      Confirmed · Manual Issue 02 · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the alarm and check only for safely visible blocked ventilation or direct sun. Do not open the inverter; contact the installer if the alarm remains after the unit cools.

    Installer remedy

    Check the ventilation and ambient temperature at the install location. If ventilation is poor or the ambient temperature is above the upper threshold, improve airflow and heat dissipation. If both meet requirements, contact your dealer or Huawei technical support.

    Remedy sourceSUN2000 M2 manualSUN2000 M3 manual

    Manufacturer / escalation handoff
  • 2064

    Device fault

    An unrecoverable fault has occurred on a circuit inside the inverter.

    Product fit · Confirmed · 2 documented families

    Show field steps for 2064: Device fault

    Product fit

    • SUN2000-(8KTL–20KTL)-M2 · Three-phase string inverter

      Confirmed · Manual Issue 06 · AU/region not confirmed · Firmware not documented

    • SUN2000-(20KTL–40KTL)-M3 · Three-phase string inverter

      Confirmed · Manual Issue 02 · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the alarm, inverter indicators and software version if visible. Do not power-cycle, load firmware or alter communication wiring; contact the installer or Huawei support.

    Installer remedy

    A licensed installer should follow the exact M2 or M3 manual's controlled diagnostic and recovery procedure for this alarm. Do not substitute a generic switching sequence; if the alarm persists after the documented check, preserve the event evidence and escalate to Huawei support.

    Remedy sourceSUN2000 M2 manualSUN2000 M3 manual

    Manufacturer / escalation handoff
  • 2065

    Upgrade failed / software version mismatch

    The upgrade did not complete normally.

    Product fit · Confirmed · 2 documented families

    Show field steps for 2065: Upgrade failed / software version mismatch

    Product fit

    • SUN2000-(8KTL–20KTL)-M2 · Three-phase string inverter

      Confirmed · Manual Issue 06 · AU/region not confirmed · Firmware not documented

    • SUN2000-(20KTL–40KTL)-M3 · Three-phase string inverter

      Confirmed · Manual Issue 02 · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the alarm, inverter indicators and software version if visible. Do not power-cycle, load firmware or alter communication wiring; contact the installer or Huawei support.

    Installer remedy

    Retry the supported inverter upgrade. If it fails repeatedly, contact the dealer or Huawei technical support; do not install an unverified firmware package.

    Remedy sourceSUN2000 M2 manualSUN2000 M3 manual

    Manufacturer / escalation handoff
  • 2066

    Licence expired

    The privilege certificate has entered its grace period; the privileged feature will become invalid soon.

    Product fit · Confirmed · 2 documented families

    Show field steps for 2066: Licence expired

    Product fit

    • SUN2000-(8KTL–20KTL)-M2 · Three-phase string inverter

      Confirmed · Manual Issue 06 · AU/region not confirmed · Firmware not documented

    • SUN2000-(20KTL–40KTL)-M3 · Three-phase string inverter

      Confirmed · Manual Issue 02 · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the alarm, inverter indicators and software version if visible. Do not power-cycle, load firmware or alter communication wiring; contact the installer or Huawei support.

    Installer remedy

    Apply for and load a new privilege certificate through the authorised Huawei workflow.

    Remedy sourceSUN2000 M2 manualSUN2000 M3 manual

    Manufacturer / escalation handoff
  • 2067

    Faulty power collector

    Communication with the power meter is interrupted.

    Product fit · Confirmed · 2 documented families

    Show field steps for 2067: Faulty power collector

    Product fit

    • SUN2000-(8KTL–20KTL)-M2 · Three-phase string inverter

      Confirmed · Manual Issue 06 · AU/region not confirmed · Firmware not documented

    • SUN2000-(20KTL–40KTL)-M3 · Three-phase string inverter

      Confirmed · Manual Issue 02 · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the alarm and note whether monitoring or power-flow data is missing. Do not access the meter, RS485 wiring or switchboard; contact the installer if it persists.

    Installer remedy

    A licensed installer should confirm the power meter settings match the actual model, that its communications parameters match the inverter's RS485 settings, that it is powered on, and that the RS485 cable is connected correctly.

    Remedy sourceSUN2000 M2 manualSUN2000 M3 manual

    Manufacturer / escalation handoff
  • 2068

    Battery abnormal

    The battery is faulty or disconnected, or the battery circuit breaker is off while the battery is running.

    Show documented next step for 2068: Battery abnormal

    Documented next step

    Record the battery indicator and alarm details. A qualified installer should verify the battery power, enable and communication connections and configuration; contact the battery supplier or Huawei if the alarm persists.

  • 2070

    Active islanding

    During a grid AC outage, the inverter proactively detects islanding.

    Show documented next step for 2070: Active islanding

    Documented next step

    Contact your installer. Check that the grid-connection voltage of the inverter is normal.

  • 2072

    Transient AC over-voltage

    The inverter detects that the phase voltage exceeds the transient AC over-voltage protection threshold.

    Product fit · Confirmed · 2 documented families

    Show field steps for 2072: Transient AC over-voltage

    Product fit

    • SUN2000-(8KTL–20KTL)-M2 · Three-phase string inverter

      Confirmed · Manual Issue 06 · AU/region not confirmed · Firmware not documented

    • SUN2000-(20KTL–40KTL)-M3 · Three-phase string inverter

      Confirmed · Manual Issue 02 · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the alarm, cause ID if shown, and time; check only whether the property has grid supply and allow the inverter to recover. If it repeats, contact the installer; do not change protected grid settings.

    Installer remedy

    A licensed installer should verify voltage at the grid connection point and its peak value. Contact the network operator if supply is too high; change the protection threshold only with network approval.

    Remedy sourceSUN2000 M2 manualSUN2000 M3 manual

    Manufacturer / escalation handoff
  • 2077

    Off-grid output overload

    The off-grid output is overloaded or short-circuited.

    Show documented next step for 2077: Off-grid output overload

    Documented next step

    Reduce non-essential loads on the backed-up circuit. If it does not clear, a licensed installer should check for an output short circuit and verify that the load configuration is within the device rating.

  • 2080

    Abnormal PV module configuration

    PV module configuration does not meet requirements, or the module output is reverse-connected or short-circuited. Cause IDs: 2: too many optimisers in a single string; 3: too few optimisers in a string, or abnormal sunlight; 5: abnormal optimiser output voltage; 6: abnormal string or parallel connection; 7: string configuration changed.

    Show documented next step for 2080: Abnormal PV module configuration

    Documented next step

    Contact your installer. Check that the total number of PV modules, the number per string, and the number of strings meet requirements, and that module output is not reverse-connected.

  • 2081

    Optimiser fault

    The optimiser is offline or faulty.

    Show documented next step for 2081: Optimiser fault

    Documented next step

    Contact your dealer or Huawei technical support for optimiser replacement.

  • 2082

    Grid-tied / off-grid controller abnormal

    The inverter fails to communicate with the Smart Backup Box, or an unrecoverable fault has occurred inside the Smart Backup Box.

    Show documented next step for 2082: Grid-tied / off-grid controller abnormal

    Documented next step

    A licensed installer should follow the exact model shutdown procedure, inspect the power and RS485 connections between the inverter and backup controller, and contact Huawei if the alarm persists.

  • 2085

    Built-in PID operation abnormal

    The output resistance of the PV arrays to ground is low, or the system insulation resistance is low.

    Product fit · Confirmed · SUN2000-(20KTL–40KTL)-M3

    Show field steps for 2085: Built-in PID operation abnormal

    Product fit

    • SUN2000-(20KTL–40KTL)-M3 · Three-phase string inverter

      Confirmed · Manual Issue 02 · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the alarm and cause ID if shown, leave PV, AC and earthing wiring and isolators untouched, and contact the installer. Electrical measurements and recovery work require a licensed worker.

    Installer remedy

    A licensed installer should follow the exact M2 or M3 manual's controlled diagnostic and recovery procedure for this alarm. Do not substitute a generic switching sequence; if the alarm persists after the documented check, preserve the event evidence and escalate to Huawei support.

    Remedy sourceSUN2000 M3 manual

    Manufacturer / escalation handoff
  • 2090

    Abnormal active power scheduling instruction

    The DI input is abnormal, or inconsistent with the configuration.

    Show documented next step for 2090: Abnormal active power scheduling instruction

    Documented next step

    A qualified installer should verify the DI-port wiring and active-power dry-contact mapping, then confirm the required mapping with the network operator.

  • 2091

    Abnormal reactive power scheduling instruction

    The DI input is abnormal, or inconsistent with the configuration.

    Show documented next step for 2091: Abnormal reactive power scheduling instruction

    Documented next step

    A qualified installer should verify the DI-port wiring and reactive-power dry-contact mapping, then confirm the required mapping with the network operator.

  • 61440

    Monitoring unit faulty

    The flash memory is insufficient, or it has bad sectors.

    Product fit · Confirmed · 2 documented families

    Show field steps for 61440: Monitoring unit faulty

    Product fit

    • SUN2000-(8KTL–20KTL)-M2 · Three-phase string inverter

      Confirmed · Manual Issue 06 · AU/region not confirmed · Firmware not documented

    • SUN2000-(20KTL–40KTL)-M3 · Three-phase string inverter

      Confirmed · Manual Issue 02 · AU/region not confirmed · Firmware not documented

    Safe checks now

    Record the alarm, inverter indicators and software version if visible. Do not power-cycle, load firmware or alter communication wiring; contact the installer or Huawei support.

    Installer remedy

    A licensed installer should follow the exact M2 or M3 manual's controlled diagnostic and recovery procedure for this alarm. Do not substitute a generic switching sequence; if the alarm persists after the documented check, preserve the event evidence and escalate to Huawei support.

    Remedy sourceSUN2000 M2 manualSUN2000 M3 manual

    Manufacturer / escalation handoff

Sources

Continue this work

Did this help you move the job forward?

Tell us what is missing
Good to know

Frequently asked

Where do these Huawei fault codes come from?
Compiled from publicly available Huawei inverter and battery documentation and field references, then rewritten for the trade. Wattbench is independent and not affiliated with Huawei.
Which of these can I clear on site?
Some clear on their own once grid or environmental conditions return to normal. Anything involving DC isolation, AC switching, wiring or opening the unit is licensed electrical work. Isolate safely, follow AS/NZS 5033 and AS/NZS 3000 procedure and use appropriate PPE before touching a live system.
The exact code isn't listed. Why not?
Firmware and model variants differ, and manufacturers revise their code tables. We document the most common ones; for a variant that isn't here, check the unit's current manual or the manufacturer's service portal.
How current is this reference?
This reference was last reviewed on 2 August 2026. We revise entries when the underlying manufacturer documentation changes.